Three-phase Phase-sequence Phase-loss Relay

 K8AB-PM

3

Specifications

Input frequency range

45 to 65 Hz

Overload capacity

Continuous input: 115% of maximum input, 10 s max.: 125% of maximum input

Setting error

Operating value

Set value 

±

10% of full scale

Operating time

Startup lock time

Set value 

±

0.5 s

Repeat error

Operating value

Operating value 

±

2%

Error calculation: Error = ((Maximum operating value 

 Minimum operating value (over 10 operations))/2)/

Average value 

×

 100%

Reset value

Overvoltage: Operating value x 95% 

±

2%

Undervoltage: Operating value x 105% 

±

2%

Error calculation: Error = ((Maximum reset value 

 Minimum reset value (over 10 resets))/2)/Average value 

×

 100%

Operating time

Operating time repeat error: 

±

50 ms

Overvoltage: 

Measured when input suddenly changes from 70% to 120% of setting.

Undervoltage: 

Measured when input suddenly changes from 120% to 70% of setting.

The input voltage, however, must be between 70% and 125% of rating.

Startup lock time

Startup lock time repeat error: 

±

0.5 s

(The operating time when the operating time is set to the minimum value and the power supply suddenly 
changes from 0% to 100%.)

Temperature influence

Operating value

Drift based on measured value at standard temperature:

20

°

C to standard temperature: 

±

1,000 ppm/

°

C max.

Standard temperature to 60

°

C:  

±

1,000 ppm/

°

C max.

(Humidity: 25% to 80%)

Operating time

Fluctuation based on measured value at standard temperature:

20

°

C to standard temperature: 

±

10% max.

Standard temperature to 60

°

C:  

±

10% max.

(Humidity: 25% to 80%)

Humidity influence

Operating value

Based on ambient humidity of 65%
25% to 80%: 

±

5% max.

Operating time

Based on ambient room humidity
25% to 80%: 

±

10% max.

Influence of input frequency

At 45 to 65 Hz
Operating value 

±

5% max.

Operating time 

±

10% max.

Note:

 The error in the operating value and operating time under standard conditions.

Applicable 
standards

Conforming standards

EN60255-5 and EN60255-6
Installation environment (Pollution Degree 2, Overvoltage Category III)

EMC

EN61326

Safety standards

UL508

Insulation resistance

20 M

 min.

Between external terminals and case
Between input terminals and output 1 terminals
Between input terminals and output 2 terminals
Between output 1 terminals and output 2 terminals

Dielectric strength

2,000 VAC for one minute

Between external terminals and case
Between input terminals and output 1 terminals
Between input terminals and output 2 terminals
Between output 1 terminals and output 2 terminals

Noise immunity 

1,500 V power supply terminal common/normal mode
Square-wave noise of ±1 

µ

s/100 ns pulse width with 1-ns rise time

Vibration resistance

Frequency 10 to 55 Hz, 0.35-mm single amplitude, acceleration 50 m/s

2

10 sweeps of 5 min each in X, Y, and Z directions

Shock resistance

100 m/s

2

, 3 times each in 6 directions along three axes (up/down, left/right, forward/backward)

Degree of protection

Terminal section: Finger protection 

Summary of Contents for K8AB-PM Series

Page 1: ...Legend 1 Basic Model K8AB Measuring and Monitoring Relays 2 Functions PM Three phase Phase sequence Phase loss Relay Simultaneous upper and lower monitoring 3 Rated Input Voltage 1 115 127 133 138 20...

Page 2: ...oss 0 1 s max Startup lock time LOCK 1 s or 5 s Switched using DIP switch Indicators Power PWR Green Relay output RY Yellow OVER UNDER Red Output relays Two SPDT relays NC operation Output relay ratin...

Page 3: ...time Fluctuation based on measured value at standard temperature 20 C to standard temperature 10 max Standard temperature to 60 C 10 max Humidity 25 to 80 Humidity influence Operating value Based on a...

Page 4: ...L1 L2 L3 T T Note 1 The K8AB PM output relay is normally operative 2 The power ON lock prevents unnecessary alarms from being generated during the instable period when the power is first turned on Th...

Page 5: ...or Terminal block See notes 1 and 2 Terminal block See notes 1 and 2 0 1 Item Meaning Power indicator PWR Green Lit when power is being supplied see note Relay status indicator RY Yellow Lit when rela...

Page 6: ...ch Settings The power ON lock time number of wires and rated voltage are set using the DIP switch located on the bottom of the Unit Load Voltage input Signal output 14 12 L1 L2 L3 11 L1 N L2 L3 Signal...

Page 7: ...urn the knob while there is an input to the input terminals until the alarm indicator flashes when the set value and the input have reached the same level Use this as a guide to set the voltage The ra...

Page 8: ...in accident or corruption of the product 3 Do not use thinner or similar solvent for cleaning Use commercial alcohol 4 When discarding properly dispose of the product as industrial waste 5 Only use th...

Page 9: ...just the slide resistor so that the voltage applied to the K8AB terminals is 120 of the set value for overvoltage detection and 80 of the set value for undervoltage detection when the auxiliary relay...

Page 10: ...operation As the graph shows phase loss cannot be detected because the motor terminal voltage does not drop very much even if a phase is lost when the load on the motor is light To detect motor load...

Page 11: ...Cat No N146 E1 02 Three phase Phase sequence Phase loss Relay K8AB PM 11...

Page 12: ...TIAL DAMAGES LOSS OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED ON CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY In no event shall the responsibil...

Reviews: