background image

2

Three-phase Phase-sequence Phase-loss Relay

 

K8AB-PM

Cat. No. N146-E1-02

Ordering Information

List of Models

Note: 1.

Three-phase 3-wire or 4-wire and the input range are switched using a DIP switch. 

2.

The power supply is shared with the rated input voltage.

Ratings and Specifications

Ratings

Three-phase Phase-sequence Phase-loss Relay

Rated input (See note 2.)

Model

3-phase 3-wire mode

200, 220, 230, 240 VAC

K8AB-PM1

3-phase 4-wire mode

115, 127, 133, 138 VAC

3-phase 3-wire mode

380, 400, 415, 480 VAC

K8AB-PM2

3-phase 4-wire mode

220, 230, 240, 277 VAC

Rated input 
voltage

K8AB-PM1

Three-phase, three-wire Mode: 200, 220, 230 and 240 VAC
Three-phase, four-wire Mode:  115, 127, 133 and 138 VAC

K8AB-PM2

Three-phase, three-wire Mode: 380, 400, 415 and 480 VAC
Three-phase, four-wire Mode:  220, 230, 240 and 277 VAC

Input load

K8AB-PM1:  25 VA max.
K8AB-PM2:  45 VA max.

Operating value setting range (OVER, UNDER)

Overvoltage

30% to 25% of rated input voltage

Undervoltage

30% to 25% of rated input voltage

Note:

 The rated input voltage can be switched using the DIP switch.

Operating value

100% operation at set value

Reset value

5% of operating value (fixed)

Reset method

Automatic reset

Operating time 
setting range (T)

Overvoltage/undervoltage

0.1 to 30 s

Reversed phase/phase loss

0.1 s max.

Startup lock time (LOCK)

1 s or 5 s (Switched using DIP switch.)

Indicators

Power (PWR): Green, Relay output (RY): Yellow, OVER/UNDER: Red

Output relays

Two SPDT relays (NC operation)

Output relay ratings

Rated load

Resistive load
6 A at 250 VAC (cos

φ

 = 1)

6 A at 30 VDC (L/R = 0 ms)
Inductive load
1 A at 250 VAC (cos

φ

 = 0.4)

1 A at 30 VDC (L/R = 7 ms)

Maximum contact voltage: 

250 VAC

Maximum contact current: 

6 A AC

Maximum switching capacity:  1,500 VA
Minimum load: 

10 mA at 5 VDC

Mechanical life: 

10,000,000 operations

Electrical life:

Make: 50,000 times, Break: 30,000 times

Ambient operating temperature

20 to 60°C (with no condensation or icing)

Storage temperature

40 to 70°C (with no condensation or icing)

Ambient operating humidity

25% to 85% (with no condensation)

Storage humidity

25% to 85% (with no condensation)

Altitude

2,000 m max.

Terminal screw tightening torque

0.49 N·m

Terminal wiring method

Recommended wire

Solid wire: 

2.5 mm

2

Twisted wires:  AWG16, AWG18

Note: 1.

Ferrules with insulating sleeves must be used with twisted wires.

2.

Two wires can be twisted together.

Recommended ferrules

Al 1,5-8BK (for AWG16) manufactured by Phoenix Contact
Al 1-8RD (for AWG18) manufactured by Phoenix Contact
Al 0,75-8GY (for AWG18) manufactured by Phoenix Contact

Case color

Munsell 5Y8/1

Case material

ABS resin (self-extinguishing resin) UL94-V0

Weight

Approx. 130 g

Mounting

Mounted to DIN Track or via M4 screws (tightening torque: 1.2 N·m)

Dimensions

22.5 (W) 

×

 90 (H) 

×

 100 (D) mm

Summary of Contents for K8AB-PM Series

Page 1: ...Legend 1 Basic Model K8AB Measuring and Monitoring Relays 2 Functions PM Three phase Phase sequence Phase loss Relay Simultaneous upper and lower monitoring 3 Rated Input Voltage 1 115 127 133 138 20...

Page 2: ...oss 0 1 s max Startup lock time LOCK 1 s or 5 s Switched using DIP switch Indicators Power PWR Green Relay output RY Yellow OVER UNDER Red Output relays Two SPDT relays NC operation Output relay ratin...

Page 3: ...time Fluctuation based on measured value at standard temperature 20 C to standard temperature 10 max Standard temperature to 60 C 10 max Humidity 25 to 80 Humidity influence Operating value Based on a...

Page 4: ...L1 L2 L3 T T Note 1 The K8AB PM output relay is normally operative 2 The power ON lock prevents unnecessary alarms from being generated during the instable period when the power is first turned on Th...

Page 5: ...or Terminal block See notes 1 and 2 Terminal block See notes 1 and 2 0 1 Item Meaning Power indicator PWR Green Lit when power is being supplied see note Relay status indicator RY Yellow Lit when rela...

Page 6: ...ch Settings The power ON lock time number of wires and rated voltage are set using the DIP switch located on the bottom of the Unit Load Voltage input Signal output 14 12 L1 L2 L3 11 L1 N L2 L3 Signal...

Page 7: ...urn the knob while there is an input to the input terminals until the alarm indicator flashes when the set value and the input have reached the same level Use this as a guide to set the voltage The ra...

Page 8: ...in accident or corruption of the product 3 Do not use thinner or similar solvent for cleaning Use commercial alcohol 4 When discarding properly dispose of the product as industrial waste 5 Only use th...

Page 9: ...just the slide resistor so that the voltage applied to the K8AB terminals is 120 of the set value for overvoltage detection and 80 of the set value for undervoltage detection when the auxiliary relay...

Page 10: ...operation As the graph shows phase loss cannot be detected because the motor terminal voltage does not drop very much even if a phase is lost when the load on the motor is light To detect motor load...

Page 11: ...Cat No N146 E1 02 Three phase Phase sequence Phase loss Relay K8AB PM 11...

Page 12: ...TIAL DAMAGES LOSS OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED ON CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY In no event shall the responsibil...

Reviews: