Summary of Contents for In-Panel NEO Series

Page 1: ...ontroller CompoWay F Driver 1 System Configuration 3 2 Selection of External Device 7 3 Example of Communication Setting 8 4 Setup Items 18 5 Cable Diagram 23 6 Supported device 38 7 Device Code and Address Code 45 8 Error Messages 47 ...

Page 2: ...ernal Device Select a model series of the External Device to be connected and connection method 2 Selection of External Device page 7 3 Example of Communication Settings This section shows setting examples for communicating between the Display and the External Device 3 Example of Communication Setting page 8 4 Setup Items This section describes communication setup items on the Display Set communic...

Page 3: ...ngs Cable Diagram THERMAC NEO E5EN FLK E5AN FLK Terminal block on the controller RS232C Setting Example 1 page 8 Cable Diagram 1 page 24 E5EN FLK E5AN FLK E5CN FLK E5GN FLK RS485 2wire Setting Example 2 page 10 Cable Diagram 2 page 26 THERMAC R E5AR FLK E5ER FLK Terminal block on the controller RS485 2wire Setting Example 3 page 12 Cable Diagram 2 page 26 In Panel NEO E5ZN FLK Terminal block on th...

Page 4: ... PS 3711A COM1 1 COM2 2 COM2 2 COM2 2 PS4000 3 3 When making communication between an External Device and COM port on the Expansion slot only RS 232C is supported However ER DTR CTS control cannot be executed because of the specification of COM port For connection with External Device use user created cables and disable Pin Nos 1 4 6 and 9 Please refer to the IPC manual for details of pin layout C...

Page 5: ... DIP Switch The BOX Atom has not a switch to set the RS 232C RS 422 485 mode Use the BIOS for the setting 8 For the connection with the External Device on the user created cable read as if the connector on the Display side is a M12 A coding 8 pin socket The pin assignment is the same as described in the cable diagram For the M12 A coding connector use PFXZPSCNM122 DIP Switch Setting Description 1 ...

Page 6: ... None 7 OFF Short circuit of SDA TXA and RDA RXA Not available 8 OFF Short circuit of SDB TXB and RDB RXB Not available 9 OFF RS RTS Auto control mode Disabled 10 OFF DIP Switch Setting Description 1 OFF Reserved always OFF 2 ON SIO type RS 422 485 3 ON 4 OFF Output mode of SD TXD data Always output 5 OFF Terminal resistance 220Ω insertion to SD TXD None 6 OFF Terminal resistance 220Ω insertion to...

Page 7: ...PLCs to connect to the display Manufacturer Select the manufacturer of the External Device to connect Select OMRON Corporation Series Select the External Device model series and the connection method Select Temp Controller CompoWay F In System configuration make sure the External Device you are connecting is supported by Temp Controller CompoWay F 1 System Configuration page 3 Port Select the Disp...

Page 8: ...ication Setting Examples of communication settings of the Display and the External Device recommended by Digital Electronics Corp are shown 3 1 Setting Example 1 Setting of GP Pro EX Communication Settings To display the setup screen from the Project menu point to System Settings and select Device PLC ...

Page 9: ...to the manual of the Temperature Controller for more details Procedure 1 Press and hold the level key 3 minutes or more to transfer from the operation level to the default level 2 Press the level key again to transfer from the default level to the communication setting level 3 Press the mode key to select the parameter 4 Press the down up keys to change the setting 5 Press and hold the level key t...

Page 10: ... CompoWay F Driver GP Pro EX Device PLC Connection Manual 10 3 2 Setting Example 2 Setting of GP Pro EX Communication Settings To display the setup screen from the Project menu point to System Settings and select Device PLC ...

Page 11: ... to the manual of the Temperature Controller for more details Procedure 1 Press and hold the level key 3 minutes or more to transfer from the operation level to the default level 2 Press the level key again to transfer from the default level to the communication setting level 3 Press the mode key to select the parameter 4 Press the down up keys to change the setting 5 Press and hold the level key ...

Page 12: ... CompoWay F Driver GP Pro EX Device PLC Connection Manual 12 3 3 Setting Example 3 Setting of GP Pro EX Communication Settings To display the setup screen from the Project menu point to System Settings and select Device PLC ...

Page 13: ...the manual of the Temperature Controller for more details Procedure 1 Press and hold the level key 3 minutes or more to transfer from the operation level to the default level 2 Press the level key again to transfer from the default level to the communication setting level 3 Press the mode key to select the parameter 4 Press the down up keys to change the setting 5 Press and hold the level key to t...

Page 14: ... CompoWay F Driver GP Pro EX Device PLC Connection Manual 14 3 4 Setting Example 4 Setting of GP Pro EX Communication Settings To display the setup screen from the Project menu point to System Settings and select Device PLC ...

Page 15: ...Controller to set Unit No UNIT and Speed BPS 2 Press and hold the level key 3 minutes or more in front of the Display to transfer from the operation level to the default level 3 Press the level key several times to transfer from the default level to the communication setting level 4 Press the mode key to select the parameter 5 Press the down up keys to change the setting 6 Press and hold the level...

Page 16: ... CompoWay F Driver GP Pro EX Device PLC Connection Manual 16 3 5 Setting Example 5 Setting of GP Pro EX Communication Settings To display the setup screen from the Project menu point to System Settings and select Device PLC ...

Page 17: ...ontroller to set Unit No UNIT and Speed BPS 2 Press and hold the level key 3 minutes or more in front of the Display to transfer from the operation level to the default level 3 Press the level key several times to transfer from the default level to the communication setting level 4 Press the mode key to select the parameter 5 Press the down up keys to change the setting 6 Press and hold the level ...

Page 18: ... the Project menu point to System Settings and select Device PLC Setup Items Setup Description SIO Type Select a SIO type for communicating with an external device from RS232C RS422 485 2 wire and RS422 485 4 wire Speed Select speed bps between the External Device and the Display Data Length Select the data length bit for communication Select either 7 or 8 Parity Select how to check parity Select ...

Page 19: ...or the response from the External Device Retry In case of no response from the External Device use an integer from 0 to 255 to enter how many times the Display retransmits the command Wait To Send Use an integer from 0 to 255 to enter standby time ms for the Display from receiving packets to transmitting next commands RI VCC You can switch RI VCC of the 9th pin when you select RS232C for SIO type ...

Page 20: ... Description SIO Type Select a SIO type for communicating with an external device from RS232C RS422 485 2 wire and RS422 485 4 wire To make the communication settings correctly confirm the serial interface specifications of Display unit for SIO Type We cannot guarantee the operation if a communication type that the serial interface does not support is specified For details concerning the serial in...

Page 21: ...from the External Device Retry In case of no response from the External Device use an integer from 0 to 255 to enter how many times the Display retransmits the command Wait To Send Use an integer from 0 to 255 to enter standby time ms for the Display from receiving packets to transmitting next commands Setup Items Setup Description Device PLC name Select the External Device to set Device name is a...

Page 22: ...l Device you want to set from the displayed list and touch Option Setup Items Setup Description RI VCC Switches RI VCC of the 9th pin It is necessary to change RI 5V by changeover switch of IPC when connect with IPC Please refer to the manual of the IPC for more detail GP 4100 series GP 4 01TM GP Rear Module LT 4 01TM and LT Rear Module do not have the Option setting in the offline mode ...

Page 23: ...t be D class grounded Please refer to the manual of the External Device for more details SG and FG are connected inside the Display When connecting SG to the External Device design the system not to form short circuit loop Connect the isolation unit when communication is not stabilized under the influence of a noise etc Recommended cable RS232C RS485 Temperature Controller Cable E5EN FLK E5AN FLK ...

Page 24: ... Only the COM port which can communicate by RS 232C can be used IPC COM Port page 4 1A User created cable Cable length 15m or less GP 4105 COM1 GP 4115T COM1 GP 4115T3 COM1 1B User created cable Cable length 15m or less LT 4 01TM COM1 LT Rear Module COM1 1C RJ45 RS 232C Cable 5m by Pro face PFXZLMCBRJR21 Cable length 5m or less SD TXD 3 RD RXD 2 SG 5 SD RD 4 ER DTR SG RS RTS CS CTS 7 8 DR DSR 6 FG...

Page 25: ... Name Notes 1 RJ45 RS 232C Cable 5m by Pro face PFXZLMCBRJR21 SD TXD RD RXD SG SD RD ER DTR SG RS RTS CS CTS DR DSR Signal name Shield Terminal block External Device side Signal name Display Terminal block Display side SD RD SG Terminal block External Device side Signal name Display GND TXD RXD 1 ...

Page 26: ...500m or less 2D Online adapter by Pro face CA4 ADPONL 01 User created cable IPC 4 2E COM port conversion adapter by Pro face CA3 ADPCOM 01 Terminal block conversion adapter by Pro face CA3 ADPTRM 01 User created cable Cable length 500m or less 2F User created cable GP 4106 COM1 GP 4116T COM1 2G User created cable Cable length 500m or less GP 4107 COM1 GP 4 03T 5 COM2 GP 4203T COM1 2H User created ...

Page 27: ...r CA3 ADPTRM 01 instead of the RS 422 Terminal Block Conversion Adapter refer to Cable Diagram 2A 10 Only the COM port which can communicate by RS 422 485 2 wire can be used IPC COM Port page 4 RDB SDB SG FG B A 120Ω 1 2W CA3 ADPCOM 01 CA3 ADPTRM 01 120Ω 1 2W RDA SDA Display Termination resistance Signal name Shield Terminal block External Device side Signal name Termination resistance User create...

Page 28: ...6 1 8 Pin Shell SDA RDB SG ERA SDB ERB CSB FG RDA CSA Signalname D Sub 9 Pin socket Display side 120Ω Termination resistance 1 2W 120Ω 1 2W B A 120Ω 1 2W B A Termination resistance Shield Terminal block Signal name External Device side Shield Terminal block Signal name External Device side Termination resistance Display 3 2 5 4 7 9 6 1 8 Pin Shell SDA RDB SG ERA SDB ERB CSB FG RDA CSA Signalname D...

Page 29: ...rmination resistance Signal name Shield Terminal block Signal name External Device side Termination resistance User created cable RDB SDB SG FG CA4 ADPONL 01 CA3 ADPTRM 01 120Ω 1 2W RDA SDA B A 120Ω 1 2W B A Display Termination resistance Signal name Shield Terminal block Signal name External Device side Shield Terminal block Signal name External Device side Termination resistance User created cab...

Page 30: ...rnal Device side Termination resistance User created cable RDB RDA SDB TERMTX SDA FG TERMRX SG 3 2 5 7 9 Shell 1 8 Signalname Pin 120Ω 1 2W D Sub 9 pin plug Shield Display CA4 ADPONL 01 Termination resistance B A Terminal block Signal name External Device side 120Ω 1 2W B A Terminal block External Device side Signal name Termination resistance Shield User created cable RDB RDA SDB TERMTX SDA FG TE...

Page 31: ...rmination resistance Signal name Shield Terminal block External Device side Signal name Termination resistance User created cable RDB SDB SG FG B A 120Ω 1 2W CA3 ADPCOM 01 CA3 ADPTRM 01 120Ω 1 2W RDA SDA B A Display Termination resistance Signal name Shield Signal name Signal name Terminal block External Device side Terminal block External Device side Shield Termination resistance User created cab...

Page 32: ...esistance Signalname Pin Shell Shield Terminal block External Device side Signal name Termination resistance Display Display side 120Ω 1 2W NC 3 DATA 2 GND SG 5 NC 7 ERA 4 CSA 8 ERB 9 CSB 6 FG DATA 1 D Sub 9 Pin socket B A 120Ω 1 2W B A Termination resistance Signalname Pin Shell Shield Terminal block Signal name External Device side Shield Terminal block Signal name External Device side Terminati...

Page 33: ...No Set Value 1 OFF 2 OFF 3 ON 4 ON Display side Terminal block B A 120Ω Termination resistance 1 Shield Terminal block Signal name External Device side Termination resistance Display SDA RDB SG ERA SDB ERB CSB RDA CSA Signalname B A 120Ω 1 2W B A Termination resistance 1 Shield Terminal block Signal name External Device side Shield Terminal block Signal name External Device side Termination resist...

Page 34: ...rmination resistance Shield Terminal block External Device side Signal name Termination resistance Display Display side D sub 9 pin plug Signal name NC NC GND SG RS RTS 5V NC NC FG LINE LINE 3 8 1 2 5 4 6 7 9 Shell Pin 120Ω 1 2W B A 120Ω 1 2W B A Termination resistance Shield Terminal block Signal name External Device side Shield Terminal block Signal name External Device side Termination resistan...

Page 35: ...rmination resistance Signal name Shield Terminal block External Device side Signal name Termination resistance User created cable RDB SDB SG FG B A 120Ω 1 2W PFXZCBADTM1 120Ω 1 2W RDA SDA B A Display Termination resistance Signal name Shield Signal name Signal name Terminal block External Device side Terminal block External Device side Shield Termination resistance User created cable ...

Page 36: ...J45 RS 485 Cable 5m by Pro face PFXZLMCBRJR81 120Ω 1 2W B A Terminal block External Device side Signal name Termination resistance Display D0 D1 1 220Ω 1 4W B A 220Ω 1 4W B A Termination resistance Terminal block Signal name External Device side Shield Terminal block Signal name External Device side Termination resistance Display D0 D1 1 ...

Page 37: ...esistance Signalname Pin Shell Shield Terminal block External Device side Signal name Termination resistance Display Display side 120Ω 1 2W NC 3 DATA 1 GND 5 NC NC NC NC NC 7 4 8 9 6 FG DATA 2 D Sub 9 Pin socket B A 120Ω 1 2W B A Termination resistance Signalname Pin Shell Shield Terminal block Signal name External Device side Shield Terminal block Signal name External Device side Termination resi...

Page 38: ... Device Note that the correct data may not be written if you change the word address value in the ladder program while the Display reads the data of the External Device and returns it to the External Device 3 Write disable C10000 00 C1002A 31 C10000 00 C1001C 31 C10000 C1002A C10000 C1001C Double Word Device 2 C30000 00 C30056 31 C30000 00 C30037 31 C30000 C30056 C30000 C30037 Double Word Device 2...

Page 39: ...area setting of GP Pro EX may cause a malfunction Do not set Use System Area You can set only Read Area Size for the system area available to use in the Temperature Controller Please refer to the GP Pro EX Reference Manual for Read Area Size Cf GP Pro EX Reference Manual LS Area Direct Access Method Area Please refer to the precautions on manual notation for icons in the table Manual Symbols and T...

Page 40: ...200 C5027F C50300 C5037F Double Word Device 2 C60000 00 C6007F 31 C60100 00 C6017F 31 C60200 00 C6027F 31 C60300 00 C6037F 31 C60000 C6007F C60100 C6017F C60200 C6027F C60300 C6037F Double Word Device 2 C70000 00 C7007F 31 C70100 00 C7017F 31 C70200 00 C7027F 31 C70300 00 C7037F 31 C70000 C7007F C70100 C7017F C70200 C7027F C70300 C7037F Double Word Device 2 C80000 00 C8007F 31 C80100 00 C8017F 31 ...

Page 41: ... D30100 D30139 D30200 D30239 D30300 D30339 Double Word Device 2 4 Operation command 6 A0000 A000D Word Device 5 1 Available variable area range varies depending on the using Temperature Controller Refer to the manual of OMRON Temperature Controller for setting 2 When you write the bit address the Display reads the word address corresponding to that of the External Device first Then it changes the ...

Page 42: ...ual mode Auto Manual A0009 0A 0 to 3 F 2 0 Cancel AT cancel A000A 0B 0 1 0 Initialize settings A000B 0C 0 to 3 F 2 0 Cancel latch A000C 0D 0 to 3 F 2 0 LSP 1 RSP SP mode A000D 1 Operates for all channels 2 Specify for every channel 0 CH1 1 CH2 2 CH3 3 CH4 F All channels To enable Use System Area in the system area setting of GP Pro EX may cause a malfunction Do not set Use System Area You can set ...

Page 43: ...0 00 C3003E 31 C30100 00 C3013E 31 C30000 C3003E C30100 C3013E Double Word Device 2 4 4 When writing switch the setting area of the Temperature Controller to setting area 1 C50000 00 C50000 31 C50100 00 C50100 31 C50000 C50100 Double Word Device 2 C70000 00 C70001 31 C70100 00 C70101 31 C70000 C70001 C70100 C70101 Double Word Device 2 4 Operation command 6 A0000 A000C Word Device 5 5 Read disable ...

Page 44: ... for CH1 CH2 1 F1 Cancel alarm latch 2 for CH1 CH2 1 F2 Cancel alarm latch 3 for CH1 CH2 1 FF Cancel all alarm latches for CH2 1 Cancel alarm latch A000C 1 Upgraded pulse output models and analog output models can support these commands 2 Command codes for which the related information is indicated as 00 or 10 or 01 or 11 use the same command for both CH1 and CH2 You can use either value in the re...

Page 45: ...s C1 0081 Word Address C3 0082 Word Address Operation command A 0000 Word Address Device Device Name Device Code HEX Address Code Variable Areas C0 0080 Word Address C1 0081 Word Address C4 0083 Word Address C5 0084 Word Address C6 0085 Word Address C7 0086 Word Address C8 0087 Word Address C9 0088 Word Address CA 0089 Word Address CB 008A Word Address CC 008B Word Address CD 008C Word Address CE ...

Page 46: ...evice PLC Connection Manual 46 7 3 In Panel NEO Device Device Name Device Code HEX Address Code Variable Areas C0 0080 Word Address C1 0081 Word Address C3 0082 Word Address C5 0084 Word Address C7 0086 Word Address Operation command A 0000 Word Address ...

Page 47: ...l Device is a title of External Device set with GP Pro EX Initial value PLC1 Error Message Displays messages related to the error which occurs Error Occurrence Area Displays IP address or device address of External Device where error occurs or error codes received from External Device IP address is displayed such as IP address Decimal MAC address Hex Device address is displayed such as Address Dev...

Page 48: ...Temperature Controller CompoWay F Driver GP Pro EX Device PLC Connection Manual 48 ...