Temperature Controller CompoWay/F Driver
GP-Pro EX Device/PLC Connection Manual
38
6
Supported device
Range of supported device address is shown in the table below. Please note that the actually supported range of
the devices varies depending on the External Device to be used. Please check the actual range in the manual of
your External Device.
6.1
THERMAC NEO (E5AN/E5EN/E5CN/E5GN)
This address can be specified as system data area.
Command code list
Device
Bit Address
Word Address
32bit
Remarks
11-segment
display
7-segment
display
11-segment
display
7-segment
display
Variable
Areas
*1
*1
Available variable area range varies depending on the using Temperature Controller. Refer to the manual of
OMRON Temperature Controller for setting.
C00000.00-
C00009.31
C00000.00-
C00005.31
C00000-
C00009
C00000-
C00005
Double Word Device
*2*3
*2
When you write the bit address, the Display reads the word address corresponding to that of the External Device
first. Then, it changes the target bit address among the word data once read and returns the word data to the
External Device. Note that the correct data may not be written if you change the word address value in the ladder
program while the Display reads the data of the External Device and returns it to the External Device.
*3
Write disable
C10000.00-
C1002A.31
C10000.00-
C1001C.31
C10000-
C1002A
C10000-
C1001C
Double Word Device
C30000.00-
C30056.31
C30000.00-
C30037.31
C30000-
C30056
C30000-
C30037
Double Word Device
*2*4
*4
When writing, switch the setting area of the Temperature Controller to setting area 1.
Operation
command
*6
-
-
A0000-
A0011
A0000-
A0008
Word Device
*5
*5
Read disable
*6
When executing the operation command (write), specify the directive code for the device address. Set the
related information for the writing value. Set the related information in hexadecimal number, such as 0x00,
0x01. Set the device code to be used in the painting software as A, and enter each command code instead of the
device address.
Command
code
Related information
Command comment
Device address
00
00: OFF(Disabled)
01: ON (Enabled)
Communication writing
A0000
01
00: Run
01: Stop
Run/Stop
A0001
02
00: Target value 0
01: Target value 1
02: Target value 2
03: Target value 3
Multi-SP
A0002
03
00: Cancel
01: AT execute
ATexecute/cancel
A0003
04
00: Backup
01: RAM
Write mode
A0004
05
00
Save RAM data
A0005