H8BM-R

4

Terminal Arrangement

I/O Connections

Input Circuits

Note: Although the input terminals are electrically insulated from the internal 

circuit, do not conduct an insulation resistance test on these terminals.

Output Circuits

Note: Although the output terminals are electrically insulated from the internal 

circuit, do not conduct an insulation resistance test on these terminals.

Example of Input Connections (Solid-state Switches)

Two-wire Sensors

The count input, counter number selection, reset input, I/O inhibit input, and short input signals are input when the two-wire Sensor turns 

ON.

22 23 24

25

26

27

28

15 16

17

18

19

20

21

8

9

10

11

12

13

14

1

2

3

4

5

6

7

22

23

24

25

26

27

28

Reset input

Counter No. 

selection

Count input 1

Count input 2

Count input 3

Count input 4

Count input 5

15

16

17

18

19

20

21

Short input

I/O inhibit input

Count input 6

Count input 7

Count input 8

Count input 9

Input COM

8

9

10

11

12

13

14

RUN output

Machine stoppage 

output 

Forecast output 1 Forecast output 2 Forecast output 3 Forecast output 4 Forecast output 5

1

2

3

4

5

6

7

Power supply: 0 V Power supply: 24 V Forecast output 6 Forecast output 7 Forecast output 8 Forecast output 9

Output COM

Photoco

u

pler

V

1.4 k

Ω

430 

Ω

1.4 k

Ω

I

N

COM

Inp

u

t

39 

V

O

u

tp

u

t

OUTCOM

39 

V

H

8

BM-R

All inp

u

ts

T

w

o-

w

ire Sensors

I

N

 COM

24 

V

DC

H

8

BM-R

All inp

u

ts

T

w

o-

w

ire Sensors

I

N

 COM

24 

V

DC

Note: Use the following two-wire Proximity Sensors:

(1) High-level: transistor ON

Switching capacity: 5 mA min. Residual 
voltage: 4 VDC max.

(2) Low-level: transistor OFF

Leakage current: 1.5 mA max.

(3) Operating voltage range: 

20.4 to 26.4 VDC

We recommend using OMRON E2E-X

@

D

@

-N 

Sensors.

Three-wire Sensors

NPN Type

PNP Type

 Example of Input Connections 
(Contact Switches)

*H: Contact ON.
*Use a contact which can adequately switch 

13 mA at 30 V.

All inp

u

ts

I

N

 COM

Sensor

main

circ

u

it

H

8

BM-R

All inp

u

ts

I

N

 COM

Sensor

main

circ

u

it

H

8

BM-R

All inp

u

ts

I

N

 COM

Sensor

main

circ

u

it

All inp

u

ts

I

N

 COM

Sensor

main

circ

u

it

H

8

BM-R

H

8

BM-R

All inp

u

ts

I

N

 COM

All inp

u

ts

I

N

 COM

H

8

BM-R

H

8

BM-R

Summary of Contents for H8BM-R Series

Page 1: ...terminals Degree of protection IP54 oil proof type case front Input mode Up Output mode F mode Operation continues even when setting is reached Reset system External manual resets Timer operation Yes...

Page 2: ...ying metal parts Dielectric strength voltage 1 000 VAC 50 60 Hz for 1 min between current carrying terminals and exposed non current carrying metal parts Impulse withstand voltage 1 kV between power t...

Page 3: ...hts Forecast 9 outputs Each of these outputs turns ON when its forecast value has been reached When a total counter is used output one shot signals as carry signals Retain outputs until count values a...

Page 4: ...OM 8 9 10 11 12 13 14 RUN output Machine stoppage output Forecast output 1 Forecast output 2 Forecast output 3 Forecast output 4 Forecast output 5 1 2 3 4 5 6 7 Power supply 0 V Power supply 24 V Fore...

Page 5: ...ndicators light to show that the count value has reached the preset value and that the output has turned ON Time Range Indicator s seconds h hours I O Inhibit Indicator Indicates that the I O inhibit...

Page 6: ...cutout is as shown below according to DIN 43700 The mounting panel thickness must be 1 to 5 mm Mount the Counter so that the ambient temperature will not exceed 55 C Spacing with Other Devices Provide...

Page 7: ...s of the same size and type can be inserted into a single terminal 17 Separate the input devices input wiring and Counter as far as possible from sources of noise and power lines carrying noise 18 The...

Page 8: ...e 23456 3 200000 23456 3 200000 23456 3 500 23456 3 10000 Normal Mode Key Press for 4 s min Press for 4 s min This mode is for the operational state The present value set value counter number and outp...

Page 9: ...to pre forecast value mode is automatically displayed 2 Press the Key or turn ON the counter number selection input to select the counter whose data is to be set or changed Next press the Key to set...

Page 10: ...modes except initial setting mode and re monitor mode 2 Press the Key or turn ON the reset input to reset the count value to 0 for that counter only 2 Resetting of All Counters at the Same Time Press...

Page 11: ...ET Key protection is to be set Press the Key to enter the setting Note 1 The Reset of All Counters and All Clear using the RESET Key are disabled if the RESET Key Protection function is turned ON 2 Ke...

Page 12: ...eset input turns ON the re monitor value will flash 3 times and the only the count value for that counter will be returned to the value prior to being reset The following displays are made when errors...

Page 13: ...ther in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted Suitability of Use Omron Companies shall not be responsible for conformity...

Reviews: