H8BM-R

2

Specifications

Ratings

Note 1. Ripple content: 20% max.

2. This signal is output as a carry signal when the Counter is used as a 

total counter.

Characteristics

Applicable Standards

Note 1. Attach a waterproof cover of Y92A-72N.

2. Industrial electromagnetic environment (EN/IEC  61326-1 Table 2)

Rated supply voltage

24 VDC

Operating voltage 
range

85% to 110% of rated supply voltage (See note 1.)

Power consumption

Approx. 1.7 W (at 26.4 VDC)

Max. counting speed

30 Hz for count inputs 1 to 7, 
Switchable between 30 Hz and 500 Hz for count 
inputs 8 and 9

Min. counting input 
signal width

Count inputs 1 to 7: 16.7 ms (ON:OFF = 1:1) 
Count inputs 8 and 9: 16.7 ms/1 ms selectable 
(ON:OFF = 1:1)
Reset input: 100 ms max.
Short input: 75 ms max.
Counter number selection input: 30 ms max.
I/O inhibit input: 16.7 ms max.

One-shot time

20 ms (See note 2.)

Count, reset, short, 
counter number 
selection, and I/O 
inhibit input

Voltage input
High level: 16 to 26.4 VDC
Low level: 0 to 3 VDC
(input resistance: approx. 2.2 k

Ω

)

Control output

Open-collector output: 100 mA max. at 30 VDC max.

Surrounding air 
temperature

10 to +55

°

C (with no icing or condensation)

Ambient storage 
temperature

25 to +65

°

C (with no icing or condensation)

Ambient operating 
humidity

25% to 85%

Case color

Dark gray (Munsell 5Y3/1)

Insulation 
resistance

100 M

Ω

 min. (at 500 VDC) (between current-carrying 

terminals and exposed non-current-carrying metal parts)

Dielectric 
strength voltage

1,000 VAC, 50/60 Hz for 1 min (between current-
carrying terminals and exposed non-current-carrying 
metal parts)

Impulse 
withstand 
voltage

1 kV (between power terminals)
1.5 kV (between current-carrying terminals and exposed 
non-current-carrying metal parts)

Noise immunity

±

480 kV (between power terminals) and 

±

480 V 

(between input terminals), square-wave noise by noise 
simulator (pulse width: 100 ns/1 

μ

s, 1-ns rise)

Static immunity

Malfunction: 8 kV; destruction: 15 kV

Vibra-
tion 
resis-
tance

Destruc-
tion

10 to 55 Hz with 0.75-mm single amplitude, 2 hours 
each in three directions

Malfunc-
tion

10 to 55 Hz with 0.5-mm single amplitude, 10 minutes 
each in three directions

Shock
resis-
tance

Destruc-
tion

300 m/s

2

 3 times each in 6 directions

Malfunc-
tion

200 m/s

2

 3 times each in 6 directions

Weight

Approx. 250 g (Counter only)

Safety standards

UL508 (See note 1.)/CSA C22.2 No.14
EN61326

EMC

(EMI) 

EN61326-1 (See note 2.)

Emission Enclosure:

EN61326-1 (EN55011 Group 1 Class A) 

Emission AC Mains:

EN61326-1 (EN55011 Group 1 Class A)

(EMS)

EN61326-1 (See note 2.)

Immunity ESD:

EN61326-1 (EN61000-4-2): Contact discharge: 4 kV, air discharge: 8 kV

Radiated electromagnetic field immunity: EN61326-1 (EN61000-4-3): 10 V/m (Amplitude modulated, 80 MHz to 1 GHz, 1,400 to 2,000 MHz)

10 V/m (Pulse-modulated, 900 MHz ±5 MHz) 

Immunity Burst: 

EN61326-1 (EN61000-4-4): 2 kV power-line, 1 kV I/O signal-line

Immunity Surge: 

EN61326-1 (EN61000-4-5): 1 kV line to line (power line), 2 kV line to ground (power line)

Immunity Conducted Disturbance: 

EN61326-1 (EN61000-4-6): 10 V (0.15 to 80 MHz) 

Summary of Contents for H8BM-R Series

Page 1: ...terminals Degree of protection IP54 oil proof type case front Input mode Up Output mode F mode Operation continues even when setting is reached Reset system External manual resets Timer operation Yes...

Page 2: ...ying metal parts Dielectric strength voltage 1 000 VAC 50 60 Hz for 1 min between current carrying terminals and exposed non current carrying metal parts Impulse withstand voltage 1 kV between power t...

Page 3: ...hts Forecast 9 outputs Each of these outputs turns ON when its forecast value has been reached When a total counter is used output one shot signals as carry signals Retain outputs until count values a...

Page 4: ...OM 8 9 10 11 12 13 14 RUN output Machine stoppage output Forecast output 1 Forecast output 2 Forecast output 3 Forecast output 4 Forecast output 5 1 2 3 4 5 6 7 Power supply 0 V Power supply 24 V Fore...

Page 5: ...ndicators light to show that the count value has reached the preset value and that the output has turned ON Time Range Indicator s seconds h hours I O Inhibit Indicator Indicates that the I O inhibit...

Page 6: ...cutout is as shown below according to DIN 43700 The mounting panel thickness must be 1 to 5 mm Mount the Counter so that the ambient temperature will not exceed 55 C Spacing with Other Devices Provide...

Page 7: ...s of the same size and type can be inserted into a single terminal 17 Separate the input devices input wiring and Counter as far as possible from sources of noise and power lines carrying noise 18 The...

Page 8: ...e 23456 3 200000 23456 3 200000 23456 3 500 23456 3 10000 Normal Mode Key Press for 4 s min Press for 4 s min This mode is for the operational state The present value set value counter number and outp...

Page 9: ...to pre forecast value mode is automatically displayed 2 Press the Key or turn ON the counter number selection input to select the counter whose data is to be set or changed Next press the Key to set...

Page 10: ...modes except initial setting mode and re monitor mode 2 Press the Key or turn ON the reset input to reset the count value to 0 for that counter only 2 Resetting of All Counters at the Same Time Press...

Page 11: ...ET Key protection is to be set Press the Key to enter the setting Note 1 The Reset of All Counters and All Clear using the RESET Key are disabled if the RESET Key Protection function is turned ON 2 Ke...

Page 12: ...eset input turns ON the re monitor value will flash 3 times and the only the count value for that counter will be returned to the value prior to being reset The following displays are made when errors...

Page 13: ...ther in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted Suitability of Use Omron Companies shall not be responsible for conformity...

Reviews: