Profinet Quick Start Guide 

Configuration outline 

1.  Create IO Table in Cx-Programmer (for new Cx1W-PNT21) 
2.  Create the network topology in Cx-Configurator FDT 
3.  Set ‘names’ in real IO Devices using Ethernet connection (Search Devices) 
4.  Set same names of IO Devices to IO Controller in network topology 
5.  Download Configuration of IO Devices to IO Controller (via Serial connection) 
6.  Restart system to finish configuration (IO Controller connects to IO Devices) 

Create a network using Cx-Configurator FDT 

Using Cx-Configurator FDT, open the Device Catalogue and show PROFINET IO. Highlight 
PROFINET IO Controller (e.g. CJ1W-PNT21) and click ‘Add Device’. 

 

 
Now add any IO Devices to the Controller (Controller must be highlighted in ‘MyNetwork’ tree). 

 

 
Device Catalogue can be closed now. 

Configure IO Device with correct set of IO Modules (Slices) 

Double click on ‘iodevice1’ to configure the correct slices used in real system. 
If GRT1-END-M is used, then this must be added as last slice – configuration error will occur if not. 

 

Rev 1.01 

 

2 of 8 

Summary of Contents for GRT1-PNT

Page 1: ...etting PROFINET devices PLC I O Controller and IO Devices at least one for configuration I O table on PLC should be created using Cx Programmer Network It is recommended that the PROFINET network is s...

Page 2: ...guration IO Controller connects to IO Devices Create a network using Cx Configurator FDT Using Cx Configurator FDT open the Device Catalogue and show PROFINET IO Highlight PROFINET IO Controller e g C...

Page 3: ...by searching for MAC addresses so IP does not need to be configured at this point Once all devices have been recognised the IO devices now require unique Device names set Use the Configure button and...

Page 4: ...t The IO Controller will respond with data in Unit Information The IO Controller Setup allows user to specify name and IP address for network leave as defaults if unsure IO Device Setup The IO Device...

Page 5: ...the configuration on the screen does not match that stored on Disk Before downloading Configuration changes to the IO Controller please make sure the project is saved disappear Download Configuration...

Page 6: ...e This should result in communication between IO Device s and IO Controller and hence cyclic IO exchange Where is my data Data is mapped to from PLC where IO Device configuration was set In this examp...

Page 7: ...n diagram for Smart Slice Parameter configuration Ethernet to configure Smart Slices of IO Devices The PC running Cx Configurator FDT must have a unique IP address set on the same network as the Profi...

Page 8: ...on layout details It is not possible to connect with a blank Cx Configurator FDT network and upload devices that are connected to resurrect Cx Configurator FDT configuration Further Information For mo...

Reviews: