Profinet Quick Start Guide 

Configuring individual Smart Slice parameters 

To configure/setup parameters on individual Smart Slices (e.g. changing range on an Analogue input 
from 0V-5V to 4mA-20mA), Cx-Configurator FDT must be connected to the Profinet using an Ethernet 
connection (same connection to set ‘names’).  It is not currently possible to use another 
communication option (e.g. via USB on PLC CPU). 
Once ‘on-line’, configuration data for Individual Smart Slices can be modified, compared and 
uploaded. 
 

Connection diagram for Smart Slice Parameter configuration 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Ethernet to configure Smart Slices of IO Devices

 
 
 
The PC running Cx-Configurator FDT must have a unique IP address set on the same network as the 
Profinet.  For example, if the PROFINET IO Controller is 192.168.9.100, PROFINET IO Device is 
192.168.9.90, then set PC IP address to 192.168.9.20 (say). 
 
Messages sent from Cx-Configurator FDT to the Smart Slice coupler are sent as FINS packets over 
PROFINET/Ethernet. 
 
In the project tree ‘open’ the Smart Slice component.  Also right click on the same component in the 
tree and ‘Work Online’.  When connected, the buttons along the component will no longer be greyed 
out. 
 

 

Italic

 

= online

 

Online = not greyed out

 

Rev 1.01 

 

7 of 8 

Summary of Contents for GRT1-PNT

Page 1: ...etting PROFINET devices PLC I O Controller and IO Devices at least one for configuration I O table on PLC should be created using Cx Programmer Network It is recommended that the PROFINET network is s...

Page 2: ...guration IO Controller connects to IO Devices Create a network using Cx Configurator FDT Using Cx Configurator FDT open the Device Catalogue and show PROFINET IO Highlight PROFINET IO Controller e g C...

Page 3: ...by searching for MAC addresses so IP does not need to be configured at this point Once all devices have been recognised the IO devices now require unique Device names set Use the Configure button and...

Page 4: ...t The IO Controller will respond with data in Unit Information The IO Controller Setup allows user to specify name and IP address for network leave as defaults if unsure IO Device Setup The IO Device...

Page 5: ...the configuration on the screen does not match that stored on Disk Before downloading Configuration changes to the IO Controller please make sure the project is saved disappear Download Configuration...

Page 6: ...e This should result in communication between IO Device s and IO Controller and hence cyclic IO exchange Where is my data Data is mapped to from PLC where IO Device configuration was set In this examp...

Page 7: ...n diagram for Smart Slice Parameter configuration Ethernet to configure Smart Slices of IO Devices The PC running Cx Configurator FDT must have a unique IP address set on the same network as the Profi...

Page 8: ...on layout details It is not possible to connect with a blank Cx Configurator FDT network and upload devices that are connected to resurrect Cx Configurator FDT configuration Further Information For mo...