G70D-B7A

G70D-B7A

47

Contact Ratings (for each G6D Relay)

Load

Resistive load (cos

φ

 = 1)

Rated load

250 VAC 3 A, 30 VDC 3 A

Rated carry current

3 A

Maximum switching voltage

250 VAC, 30 VDC

Maximum switching current

3 A

Maximum switching capacity
(reference value)

750 VA, 90 W

Minimum permissible load
(reference value; see note 2)

5 VDC, 10 mA

Electrical life

100,000 operations min. (at the rated load and a switching frequency of 1,800 operations/hour)

Mechanical life

20,000,000 operations min. (at a switching frequency of 18,000 operations/hour)

Note:

1. The maximum carry current for output power supply common terminals (B0 to B6) is 3 A.

2. This value fulfills the P reference value for switching at a frequency of 120 times per minute (ambient operating environment and

determination criteria according to JIS C5442).

Power MOS FET Relay Specifications

The following specifications are for the G3DZ when it is mounted on the G70D. They are not the specifications for the G3DZ by itself.
Input (for each G3DZ Power MOS FET Relay)

Rated voltage

Operating voltage

Must-operate

voltage level

Must-release

voltage level

Input impedance

Rated current

24 VDC

19.2 to 28.8 VDC

19.2 VDC max.

1 VDC max.

4 k

 

±

20%

8.2 mA 

±

20%

Note:

The rated current includes the Link Terminal’s LED current.

Output (for each G3DZ Power MOS FET Relay)

Load voltage

Load current

Inrush current

3 to 264 VAC
3 to 125 VDC

100 

µΑ

 to 0.3 A

6 A (10 ms)

Engineering Data

The following data was obtained from measurements of samples taken from the production line. Relays are mass produced and performance
characteristics will differ from product to product. Therefore, use the following data as reference only.

G6D-1A (24 VDC) (Power Relay Mounted to G70D-R6R

j

1-B7A)

Life Expectancy

Maximum Switching Capacity

Note:

The above graph shows the characteris-
tics for the Relay when it is mounted to
the G70D.

Note:

The above graph shows the characteris-
tics for the Relay when it is mounted to
the G70D.

250 VAC, 30 VDC resistive load

250 VAC, 30 VDC inductive load
(cos

φ

 = 0.4, L/R = 7 ms)

Switching current (A)

DC resistive load

AC resistive load

DC inductive load

AC inductive load
(cos

φ

 = 0.4)

Switching voltage (V)

Life expectancy (x10   operations)

4

Switching current (A)

Summary of Contents for G70D B7A Series

Page 1: ...g Information Product List Classification Number of I O points Rated voltage I O delay time Error processing Model Relay output 16 SPST NO 16 24 VDC Normal typical 19 2 HOLD See note 2 G70D R6R11 B7A e ay ou u 6 S S O 6 C o a y ca 19 2 ms See note 1 LOAD OFF See note 3 G70D R6R31 B7A Power MOS FET l t t HOLD See note 2 G70D R6M11 B7A o e OS relay output LOAD OFF See note 3 G70D R6M31 B7A Note 1 No...

Page 2: ...5 Hz 0 75 mm double amplitude for 2 hours each in X Y and Z directions Shock resistance Destruction 300 m s2 S oc es s a ce Malfunction 100 m s2 Operating voltage range 24 VDC 10 15 Current consumption See note 2 24 VDC approx 300 mA Cable length between Unit and connected device Depends on the load Color of indicators Operation indicator orange Power supply indicator green red for errors Coil sur...

Page 3: ...ating 0 to 55 C Storage 20 to 65 C Ambient humidity Operating 35 to 85 Mounting strength No damage when 49 N pull is applied for 1 s each in all directions only 9 8 N pull in direction of DIN track Terminal strength Tightening strength 0 78 to 0 98 N m Tensile strength 49 N for 1 minute Weight Approx 230 g Note 1 The values above are for the Terminal in its initial state 2 The value given for curr...

Page 4: ...Z Power MOS FET Relay Rated voltage Operating voltage Must operate voltage level Must release voltage level Input impedance Rated current 24 VDC 19 2 to 28 8 VDC 19 2 VDC max 1 VDC max 4 kΩ 20 8 2 mA 20 Note The rated current includes the Link Terminal s LED current Output for each G3DZ Power MOS FET Relay Load voltage Load current Inrush current 3 to 264 VAC 3 to 125 VDC 100 µΑ to 0 3 A 6 A 10 ms...

Page 5: ...raph shows the characteris tics for the Relay when it is mounted to the G70D Ambient temperature C Energizing time ms Load current A Inrush current A Peak Operation I O Combinations Screw terminal model 32 points Input Transmission Output Reception Input Transmission Relay output model 16 points G70D B7A Note Not connectable to high speed B7A models Screw terminal model 16 output points Modular mo...

Page 6: ...r See note Note The above diagram is for G70D R6Rj1 B7A models G6D mounting With G70D R6Mj1 B7A models G3DZ Power MOS FET Relays are used Terminal Arrangement G70D R6jjj B7A Power supply Load Load Load Load Load Load Load Load Power supply Power supply Power supply Power supply Power supply Power supply Power supply Load Load Load Load Load Load Load Load 24 VDC Note 1 Internal connections are ind...

Page 7: ...ink Terminals use 24 VDC G6D 1A Relays and G70D R6Mj1 B7A Link Terminals use 24 VDC G3DZ 2R6PL Relays When replacing relays use the yellow Relay Removal Tool at the corner of the screw terminal except for G7TC Do not mount or dismount relays with the power supplied Opening the Front Cover Rotating Type Hold the two bottom corners of the front cover labelled A in the dia gram below and lift upwards...

Reviews: