background image

G70D-B7A

G70D-B7A

46

G70D-R6M

j

1-B7A (Power MOS FET Relay Outputs)

Item

Specification

Contacts

16 SPST-NO contacts

Isolation method

Photocoupler

Operating time

6 ms max.

Release time

10 ms max.

Output ON resistance

2.4 

 max.

Current leakage when the relay is closed

10 

µ

A max. (at 125 VDC)

Insulation resistance

100 M

 min. (500 V)

Dielectric strength

1,000 VAC, 1 min between each terminal and external parts

Noise immunity

Power supply normal:

600 V, 10 min; pulse width: 100 ns to 1 

µ

s

Power supply common:

1.5 kV, 10 min; pulse width: 100 ns to 1 

µ

s

Transmission path wrapping: 1.5 kV, 10 min; pulse width: 100 ns to 1 

µ

s

Link Terminal wrapping:

600 V, 10 min; pulse width: 100 ns to 1 

µ

s

Vibration resistance

Destruction

10 to 55 Hz, 1.0-mm double amplitude for 2 hours each in X, Y, and Z
directions

Malfunction

10 to 55 Hz, 0.75-mm double amplitude for 2 hours each in X, Y, and Z
directions

Shock resistance

Destruction

300 m/s

2

S oc

es s a ce

Malfunction

100 m/s

2

Operating voltage range

24 VDC 

+10%

/

–15%

Current consumption (See note.)

24 VDC, approx. 300 mA

Cable length (between Unit and connected device)

Depends on the load

Color of indicators

Operation indicator: orange
Power supply indicator: green (red for errors)

Coil surge suppressor

Diode (400 V, 300 mA)

Ambient temperature

Operating: 0 to 55

°

C

Storage:

–20 to 65

°

C

Ambient humidity

Operating: 35% to 85%

Mounting strength

No damage when 49-N pull is applied for 1 s each in all directions (only 9.8-N
pull in direction of DIN track)

Terminal strength

Tightening strength: 0.78 to 0.98 N

m

Tensile strength: 49 N for 1 minute

Weight

Approx. 230 g

Note:

1. The values above are for the Terminal in its initial state.

2. The value given for current consumption is for when all points are ON and includes the input current for the G3DZ. It does not include

the current for external loads or error output.

 Ratings

Relay Specifications

The following specifications are for the G6D when it is mounted on the G70D. They are not the specifications for the G6D by itself.
Coil Ratings (for each G6D Relay)

Rated voltage

Rated current

Coil resistance

Must-operate

voltage

Must-release

voltage

Maximum

allowable

voltage

Power

consumption

24 VDC

10.5 mA

2,880 

70% max.
(See note 1.)

10% min.

130%

Approx. 200 mW

Note:

1. The must-operate voltage is 70% max. if the Relay is mounted upside down.

2. The values for rated current and coil resistance are for a coil temperature of 23

°

C with a tolerance of 

±

10%.

3. The values for operating characteristics are for a coil temperature of 23

°

C.

4. The maximum allowable voltage is the maximum value of the allowable voltage range for the relay coil operating power supply. It

does not apply in the case of continuous voltages.

5. The rated current includes the Link Terminal’s rated current.

Summary of Contents for G70D B7A Series

Page 1: ...g Information Product List Classification Number of I O points Rated voltage I O delay time Error processing Model Relay output 16 SPST NO 16 24 VDC Normal typical 19 2 HOLD See note 2 G70D R6R11 B7A e ay ou u 6 S S O 6 C o a y ca 19 2 ms See note 1 LOAD OFF See note 3 G70D R6R31 B7A Power MOS FET l t t HOLD See note 2 G70D R6M11 B7A o e OS relay output LOAD OFF See note 3 G70D R6M31 B7A Note 1 No...

Page 2: ...5 Hz 0 75 mm double amplitude for 2 hours each in X Y and Z directions Shock resistance Destruction 300 m s2 S oc es s a ce Malfunction 100 m s2 Operating voltage range 24 VDC 10 15 Current consumption See note 2 24 VDC approx 300 mA Cable length between Unit and connected device Depends on the load Color of indicators Operation indicator orange Power supply indicator green red for errors Coil sur...

Page 3: ...ating 0 to 55 C Storage 20 to 65 C Ambient humidity Operating 35 to 85 Mounting strength No damage when 49 N pull is applied for 1 s each in all directions only 9 8 N pull in direction of DIN track Terminal strength Tightening strength 0 78 to 0 98 N m Tensile strength 49 N for 1 minute Weight Approx 230 g Note 1 The values above are for the Terminal in its initial state 2 The value given for curr...

Page 4: ...Z Power MOS FET Relay Rated voltage Operating voltage Must operate voltage level Must release voltage level Input impedance Rated current 24 VDC 19 2 to 28 8 VDC 19 2 VDC max 1 VDC max 4 kΩ 20 8 2 mA 20 Note The rated current includes the Link Terminal s LED current Output for each G3DZ Power MOS FET Relay Load voltage Load current Inrush current 3 to 264 VAC 3 to 125 VDC 100 µΑ to 0 3 A 6 A 10 ms...

Page 5: ...raph shows the characteris tics for the Relay when it is mounted to the G70D Ambient temperature C Energizing time ms Load current A Inrush current A Peak Operation I O Combinations Screw terminal model 32 points Input Transmission Output Reception Input Transmission Relay output model 16 points G70D B7A Note Not connectable to high speed B7A models Screw terminal model 16 output points Modular mo...

Page 6: ...r See note Note The above diagram is for G70D R6Rj1 B7A models G6D mounting With G70D R6Mj1 B7A models G3DZ Power MOS FET Relays are used Terminal Arrangement G70D R6jjj B7A Power supply Load Load Load Load Load Load Load Load Power supply Power supply Power supply Power supply Power supply Power supply Power supply Load Load Load Load Load Load Load Load 24 VDC Note 1 Internal connections are ind...

Page 7: ...ink Terminals use 24 VDC G6D 1A Relays and G70D R6Mj1 B7A Link Terminals use 24 VDC G3DZ 2R6PL Relays When replacing relays use the yellow Relay Removal Tool at the corner of the screw terminal except for G7TC Do not mount or dismount relays with the power supplied Opening the Front Cover Rotating Type Hold the two bottom corners of the front cover labelled A in the dia gram below and lift upwards...