F3SP-U4P-TGR
User's manual
10
5 CONNECTIONS.
5.1
TERMINAL BLOCK ASSIGNMENT.
TERMINAL OUTER
CONNECTION
1 - 2
Connect to the 24 VDC power supply, note the polarity indicated on the label.
3 - 4
RESET button; connect a normally opened contact (N.O.).
4 - 5
TEST button; connect a normally closed (N.C.).
6 - 7
Connect the muting lamp.
8
Input of the muting A sensor. Connect to the N.O. contact of the muting
sensor (photocell, proximity switch, other).
9
Input of the muting B sensor. Connect to the N.O. contact of the muting
sensor (photocell, proximity switch, other).
10
Input of the muting D sensor. Connect to the N.O. contact of the muting
sensor (photocell, proximity switch, others)
11
Input of the muting C sensor. Connect to the N.O. contact of the muting
sensor (photocell, proximity switch, others)
12
Earth. Connect to the plant’s earth
13 - 14
(OUT1) safety output 1 with N.O. contact.
15 - 16
(OUT2) safety output 2 with N.O. contact.
17 - 18
Power supply transmitters (TX1) for light curtain 1.
24VDC wire to terminal 17, 0V wire to terminal 18.
19 - 20
Terminal not used.
21 - 22
Power supply transmitters (TX2) for light curtain 2.
24VDC wire to terminal 21, 0V wire to terminal 22.
23 - 24
Terminal not used.
25 - 26
Power supply receivers (RX1) for light curtain 1.
24VDC wire to terminal 25, 0V wire to terminal 26.
27 - 28
Connect to the PNP output of the receivers (RX1) of light curtain
Control output 1 wire and Control output 2 wire to terminal 27 and 28.
(Two control outputs must be used.)
No use of light curtain1. (Use of only light curtain 2)
It shall be connected the terminal 27 and 28 to terminal 25.
29 - 30
Power supply receivers (RX2) for light curtain 2.
24VDC wire to terminal 29, 0V wire to terminal 30
31 - 32
Connect to the PNP output of the receivers (RX2) of light curtain 2
Control output 1 wire and Control output 2 wire to terminal 31 and 32.
(Two control outputs must be used.)
No use of light curtain 2. (Use of only light curtain 1)
It shall be connected the terminal 31 and 32 to terminal 29.