F3SP-U4P-TGR
User's manual
27
12 TECHNICAL DATA.
•
The control unit can be used with all safety light curtains listed 11.1
Note that all safety light curtains to be used are certified according with the
EN61496-1 Type 4/ Type 2
•
Electrical input: 420 mA max. (for any model).
•
Voltage: 24 Vdc
±
10%.
•
Number of light curtains: 2 pairs max.
•
Indicators: 5 green LEDs, 1 red LED.
•
Response time: <= 18 ms
•
Working temperature: -10 a + 55 °C.
•
Humidity: from 15% to 95% (not condensing).
•
Output contacts: 2 NO, 2.5 A max, 250 Vac, cos
ϕ
0.6
÷
1
•
Switch capability: 1,500 VA, 180W
•
Electrical life expectance: 100.000 op. minimun at 1,800 oprs/hr.
•
Outer controls: test, reset, muting and override.
•
Housing: plastic case for installation on a din/omega rail
•
Protection class of control unit: IP 20.
•
Protection class of the cabinet containing the control-unit: IP54 at least.
•
Weight: control unit 600 g.
•
Features of fuses muting lamp: internal resettable fuse 315mA T 250V.
•
Muting lamp: F39-A11 incandescent lamp 24 V, 3 W min, 300 mA max.