F3SP-U4P-TGR
User's manual
19
Application with four muting sensors:
Application with two muting sensors:
A
S
B
d1 = D
Muting sensors connection:
contact of A
contact of B
24 V
DC
F3SP-U4P-TGR
terminals
9
MUTE A
8
MUTE B
11
MUTE C
10
MUTE D
N.C.
N.C.
D:
minimum distance so that the muting sensors keep active
the request; it depends on the parcel length: D < L.
d
1
:
necessary maximum distance so that the muting request is
accepted; it depends on object speed:
d
max
[cm]= v[m/s] x 3[s] x 100
This distance must not allow both sensors and the muting
cycle with the passage of a person.
N.C.
A1
B1
S
A2
B2
d1
Muting sensors connection:
contact of A1
contact of A2
contact of B1
contact of B2
24 V
DC
F3SP-U4P-TGR
terminals
D
L
v
9
MUTE A
8
MUTE B
11
MUTE C
10
MUTE D
N.C.