F3SP-U3P-TGR
User's manual
14
Please, note:
•
All models can be connected in all the possible combinations for a
maximum of two pairs of sensors with at least one pair connected.
In the following paragraph you can find the codes of the available
models which can be used in the configuration.
•
The
power
supply which is necessary to power the system must
conform to standard EN 60742 (double insulation) or with equal
insulation, for instance VDE 0551.
•
It is necessary to protect the control unit with an outer fuse having a
nominal interruption current equal to 1 A.
•
The TEST and RESET pushbuttons must be positioned in such a way
that the operator can see the protected area when he restarts, or
carries out a
test
or
override
operation.
•
The Muting lamp (F39-A11) must be positioned in a place where it
can be seen from any operative point.
•
Read the paragraph relating to the
muting
function and its use for the
positioning of the activation sensors of this function.
•
Both safety contacts OUT1 and OUT2 must be connected. If the
machine has a single locking circuit, the two normally opened
contacts must be connected in series.
•
Photocells of the type
E3FS
,
S5-5 and S10-5 are delivered with wired
cable or standard M12 connector and the wiring on the control unit is
indicated according to the cable colour, or to the male connector pin
number.
•
Photocells of the type S30-5 are available also in the version with
terminal board.
•
The connection cables of the photocells, of
muting
request,
start
and
test
must be masked with minimum section 22AWG. The screen
braids must be all earthed towards the control unit side.