F3SP-U3P-TGR
User's manual
19
Typical application with four
muting
sensors:
Application with two muting sensors, passage permitted only for package 1:
A
S
B
d1 = D
Muting sensor connection:
contact of A
contact of B
24 V
DC
7
MUTE A
8
MUTE B
F3SP-U3P-TGR
terminals
D:
minimum distance so that the
muting
sensors keep active
the request; it depends on the parcel length: D < L.
d
1
:
necessary maximum distance so that the muting request is
accepted; it depends on the parcel speed:
d
max
[cm]= v[m/s] * 3[s] * 100
This distance must not allow to activate both sensors and
the
muting
with the accidental passage of a person.
To allow the muting function only for the first photocells it’s necessary to
set the unit with the dip-switch number 3 in ON.
To allow the muting function for both the photocells the dip-switch number
3 must be setted OFF.
A1
B1
S
A2
B2
d1
Muting sensor connection:
contact of A1
contact of A2
contact of B1
contact of B2
24 V
DC
F3SP-U3P-TGR
terminals
D
L
v
7
MUTE A
8
MUTE B