6-5
Section
LED Indicators
54
6-5
LED Indicators
Indicator Status
Condition
Remarks
MS
NS
Lit green
Lit green
Remote I/O
communications in
progress.
Communications are operating normally.
OFF
Node number
duplication check in
progress.
Check for the following problems and
restart the F150.
S
Are the baud rate settings the same
on the Master and F150?
S
Are the cable lengths (trunk and
branch lines) within specifications?
Flashing
green
Waiting for connection
to be established by
Master.
branch lines) within specifications?
S
Are any cables loose or broken?
S
Is there a terminator on each end of
the trunk line?
S
Is there excessive noise in the
network?
Lit red
Node number
duplication
Change the node number settings to
eliminate the duplication and then
restart the entire CompoBus/D network.
Bus off occurred.
(Communications
stopped due to
excessive data errors.)
Check for the following problems and
restart the F150.
S
Are the baud rate settings the same
on the Master and F150?
S
Are the cable lengths (trunk and
branch lines) within specifications?
A
bl
l
b k
?
Flashing
red
Communications
timeout occurred.
S
Are any cables loose or broken?
S
Is there a terminator on each end of
the trunk line?
S
Is there excessive noise in the
network?
Lit red
OFF
Watchdog timer error
occurred in the F150.
The F150 is faulty. Replace the F150.
Flashing
red
OFF
Incorrect setting on the
DIP switch or
elsewhere.
Check the switch settings and restart
the F150.
Summary of Contents for F150-2
Page 1: ...Cat No Z132 E1 02 Manual 1 SETUP MANUAL F150 2 Vision Sensor...
Page 2: ......
Page 3: ...F150 2 Vision Sensor Setup Manual Revised May 2004...
Page 4: ...vi...
Page 10: ......
Page 14: ......
Page 20: ......
Page 72: ......
Page 84: ......
Page 86: ......
Page 87: ......
Page 88: ...Z132 E1 02...