Limit Controller

 E5CN-FR

15

Precautions for Correct Use 

Service Life 

1.

Use the Limit Controller within the following temperature and 
humidity ranges:
Temperature: 

10 to 55

°

C (with no icing or condensation)

Humidity: 25% to 85%
If the Controller is installed inside a control board, the ambient 
temperature must be kept to under 55

°

C, including the 

temperature around the Controller. 

2.

The service life of electronic devices like Limit Controllers is 
determined not only by the number of times the relay is switched 
but also by the service life of internal electronic components. 
Component service life is affected by the ambient temperature: 
the higher the temperature, the shorter the service life and, the 
lower the temperature, the longer the service life. Therefore, the 
service life can be extended by lowering the temperature of the 
Limit Controller. 

3.

When two or more Limit Controllers are mounted horizontally 
close to each other or vertically next to one another, the internal 
temperature will increase due to heat radiated by the Limit 
Controllers and the service life will decrease. In such a case, use 
forced cooling by fans or other means of air ventilation to cool 
down the Limit Controllers. When providing forced cooling, 
however, be careful not to cool down the terminals sections alone 
to avoid measurement errors.

Measurement Accuracy 

1.

When extending or connecting the thermocouple lead wire, be 
sure to use compensating wires that match the thermocouple 
types. 

2.

When extending or connecting the lead wire of the platinum 
resistance thermometer, be sure to use wires that have low 
resistance and keep the resistance of the three lead wires the 
same. 

3.

Mount the Limit Controller so that it is horizontally level. 

4.

If the measurement accuracy is low, check to see if input shift has 
been set correctly. 

Waterproofing

The degree of protection is as shown below. Sections without any 
specification on their degree of protection or those with IP

@

0 are not 

waterproof.

Front panel: NEMA4X for indoor use (equivalent to IP66)
Rear case: IP20, Terminal section: IP00

Operating Precautions

1.

It takes approximately two seconds for the outputs to turn ON 
from after the power supply is turned ON. Due consideration must 
be given to this time when incorporating Limit Controllers in a 
sequence circuit. 

2.

Avoid using the Controller in places near a radio, television set, or 
wireless installing. These devices can cause radio disturbances 
which adversely affect the performance of the Controller. 

Mounting

Mounting to a Panel 

1.

To mount the Controller so that it is waterproof, insert the 
waterproof packing onto the Controller. Group mounting does not 
allow waterproofing. The waterproof packing is not required if 
waterproof is not necessary.

2.

Insert the E5CN-FR into the mounting hole in the panel.

3.

Push the adapter along the Controller body from the terminals up 
to the panel, and fasten it temporarily.

4.

Tighten the two fixing screws on the adapter. Alternately tighten 
the two screws a little at time to keep them balanced. Tighten 
them to a torque of 0.29 to 0.39 N·m.

Attaching the Terminal Cover 

Make sure that the “UP” letters on the E5CN-FR are at the top and 
insert the terminal cover into the holes at the top and bottom of the 
Controller.

Removing the Controller from the Case 

When carrying out maintenance on the Controller, the Controller can 
be removed from the case leaving the terminal leads attached. The 
Controller can be removed from the case only with the E5CN-FR. 

1.

Insert the tool into the slots (one on the top and one on the 
bottom) and release the hooks.

2.

Insert the tool into the gap between the front panel and rear case 
and pull out the front panel slightly. Hold both sides of the front 
panel and draw out the Controller towards you. Do not apply 
unnecessary force. 

3.

Before inserting the Controller, confirm that the sealing rubber is 
in place. Insert the Controller into the rear case until you hear a 
click. Press on the hooks on the top and bottom of the rear case 
to be sure that the hooks are securely locked in place.Be sure 
that electronic parts do not come in contact with the case.

Wiring Precautions

Separate input leads and power lines to protect the Controller and 
its lines from external noise.

Use wires of a thickness of AWG24 (0.205 mm

2

) to AWG14 

(2.081 mm

2

).

The exposed current-carrying part to be inserted into terminals 
must be 5 to 6 mm.

We recommend using crimp terminals when wiring the terminals.

Tighten terminal screws to a torque of 0.74 to 0.90 N·m.

Use the following type of crimp terminals for M3.5 screws.

Terminal Cover  
(order separately)

Mounting Adapter  
(Accessory)

E5CN-FR

Waterproof packing

Panel

20 min.

0.4

2.0

E5CN

PV

SV

ALM1

 

ALM2

 

ALM

HA

OUT1

   STO

 OUT

2   CM

W   M

ANU

(1)

(1)

(2)

(3)

Tool insertion hole

Flat-blade screwdriver
(Unit: mm)

7.2 mm min.

7.2 mm min.

Summary of Contents for E5CN-FR

Page 1: ...mit over continuation time and limit over max min value measuring functions New Annunciator Output Warning Function Hazard lights and buzzers on the devices alert the user of errors when limit over errors occur Reset Limit Outputs Using Event Inputs Models with Event Inputs Limit outputs can be reset using event inputs enabling multiple limit outputs to be reset altogether from a distance Input Er...

Page 2: ...53 CN N Size Power supply voltage Number of alarm points Control outputs Model 1 16 DIN 48 48 78 W H D 100 to 240 VAC 0 Limit output E5CN FRMT 500 2 Limit output E5CN FR2MT 500 Functions Model Communications E53 CN03N Two event inputs E53 CNBN Two event inputs External power supply for ES1B E53 CNPBN This data sheet is provided as a guideline for selecting products Be sure to refer to the followin...

Page 3: ...d individual indicators Character height PV 11 mm SV 6 5 mm Other functions Limit over continuation time measurement function Limit over max min value measurement function Annunciator output Input error output PV display two color switching function Input digital filter Input compensation Protection functions Ambient operating temperature 10 to 55 C with no icing or condensation for 3 year warrant...

Page 4: ...upper limit for alarm 2 type Set value Alarm type Alarm output operation When X is positive When X is negative 0 Alarm function OFF Output OFF 1 See note 1 Upper and lower limit deviation See note 2 2 Upper limit deviation 3 Lower limit deviation 4 See note 1 Upper and lower limit range deviation See note 3 5 See note 1 Upper and lower limit with standby sequence deviation See note 5 See note 4 6 ...

Page 5: ...Destruction 300 m s2 min 3 times each in X Y and Z directions Weight Controller Approx 150 g Mounting Bracket Approx 10 g Degree of protection Front panel NEMA4X for indoor use equivalent to IP66 Rear case IP20 Terminal section IP00 Memory protection Non volatile memory number of writes 1 000 000 operations EMC Emission Enclosure EN55011 Group1 ClassA Emission AC Mains EN55011 Group1 ClassA Immuni...

Page 6: ...ote Alarm 2 Infrared temperature sensor Communications Platinum resistance thermometer Event input 1 Event input 2 Event inputs 6 7 8 9 10 11 12 13 14 15 1 3 2 4 5 11 12 13 14 15 B Pt TC A B B A 6 7 8 1 2 RS 485 11 12 13 14 15 Input power supply 100 to 240 VAC 11 12 13 14 15 Event input 1 Event input 2 Event inputs External power supply for ES1B 12 VDC 10 20 mA External power Note Output when an i...

Page 7: ...in the specified mounting space between Controllers To mount the Controller so that it is waterproof insert the waterproof packing onto the Controller When two or more Controllers are mounted make sure that the surrounding temperature does not exceed the allowable operating temperature specified in the specifications Note The terminal block cannot be removed The suffix 500 is added to the model nu...

Page 8: ...ctions shorts and input type See note 3 OFF Operates as above the upper limit lo Over lower limit indication range See note 2 Input value is smaller than control range Check the control range Upper limiter Normal operation Operates as above the lower limit Lower limiter OFF hi Over upper limit indication range See note 2 Input value is larger than control range Check the control range Upper limite...

Page 9: ...Limit Controller E5CN FR 9 ...

Page 10: ...lue 1 al1l F 0 M Alarm value 2 al 2 F 0 M Upper limit alarm value 2 al2h F 0 M Set either of these parameters Lower limit alarm value 2 al2l F 0 M Press the Level Key for less than 1 s Press the Level Key for less than 1 s Power ON sp s 100 M Limit over continuation time time M Limit over max value p hi F M Limit over min value p lo F Monitor only Press the Level Key for at least 3 s Press the Lev...

Page 11: ...Alarm 2 type alt2 2 M Move to advanced function level amov 0 Advanced Function Setting Level Parameter initialization init off M Event input assignment 1 ev 1 none Standby sequence reset method rest a M Alarm 1 open in alarm al1n n o Alarm 1 hysteresis alh1 0 2 M Alarm 2 open in alarm al2n n o M M M Alarm 2 hysteresis alh2 0 2 M Input digital filter inf 0 0 Additional PV display pvad on Automatic ...

Page 12: ...ey for 1 second min while in the operation level The limit output reset operation can be used to reset limit outputs and annunciator outputs When the limit status is OFF the limit output is cleared and the limit output relay turns ON When the limit status is ON limit over status limit outputs will not be reset The annunciator output turns OFF regardless of the limit status Event inputs used as res...

Page 13: ...requiring a high degree of safety take into account all ratings performance capacities failsafe measures and other safety measures required by the application and consult with your OMRON representative to confirm specifications and capabilities Controlled device Furnace oven Sensor input Limit Sensor Temperature Sensor Heater Temperature Controller e g E5CN E5CN FR Limit Controller Limit output Co...

Page 14: ...et after power ON 15 The output may turn OFF when shifting to certain levels Take this into consideration when performing control 16 Refer to the instruction sheet for installing Option Unit E53 CN03N E53 CNBN E53 CNPBN Do not touch the terminals while power is being supplied Doing so may occasionally result in minor injury due to electric shock Do not allow pieces of metal wire clippings or fine ...

Page 15: ...t 2 Avoid using the Controller in places near a radio television set or wireless installing These devices can cause radio disturbances which adversely affect the performance of the Controller Mounting Mounting to a Panel 1 To mount the Controller so that it is waterproof insert the waterproof packing onto the Controller Group mounting does not allow waterproofing The waterproof packing is not requ...

Page 16: ...ller Digital Temperature Controller E5CN E5CN U This Best selling General purpose 48 48 mm Temperature Controller Is Now Better USB Serial Conversion Cable and Support Software Are Also Available CatalogNumber H126 Infrared Thermosensor ES1B Achieve Low cost Measurements with an Infrared Thermosensor CatalogNumber H127 ...

Page 17: ...Limit Controller E5CN FR 17 ...

Page 18: ...18 Limit Controller E5CN FR ...

Page 19: ...Limit Controller E5CN FR 19 ...

Page 20: ...t exceed the individual price of the product on which liability is asserted IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY REPAIR OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED STORED INSTALLED AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION ABUSE MISUSE OR INAPPROPRIATE MODIFICATION OR REPAIR Application Considerations SUITABIL...

Reviews: