![background image](http://html.mh-extra.com/html/omron/e5cn-fr/e5cn-fr_manual_744343003.webp)
Limit Controller
E5CN-FR
3
Specifications
■
Ratings
■
Input Ranges
Thermocouples/Platinum Resistance Thermometers
Item
Power supply
voltage
100 to 240 VAC, 50/60 Hz
Operating voltage range
85% to 110% of rated supply voltage
Power consumption
7.5 VA max.
Sensor input
Models with temperature inputs
Thermocouple: K, J, T, E, L, U, N, R, S, or B
Platinum resistance thermometer: Pt100 or JPt100
Infrared temperature sensor: 10 to 70
°
C, 60 to 120
°
C, 115 to 165
°
C, or 160 to 260
°
C
Control output FM Limit output
relay
SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations,
minimum applicable load: 5 V, 10 mA
Alarm output
SPST-NO, 250 VAC, 1 A (resistive load), electrical life: 100,000 operations,
minimum applicable load: 1 V, 1 mA
Event input
Contact input
ON: 1 k
Ω
max., OFF: 100 k
Ω
min.
Non-contact input
ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
Outflow current: Approx. 7 mA per point
External power supply for ES1B
12 VDC ±10%, 20 mA, Short-circuit protection provided.
Setting method
Digital setting using front panel keys
Indication method
11-segment digital display and individual indicators
Character height: PV: 11 mm, SV: 6.5 mm
Other functions
•
Limit over continuation time measurement function
•
Limit over max./min. value measurement function
•
Annunciator output
•
Input error output
•
PV display two-color switching function
•
Input digital filter
•
Input compensation
•
Protection functions
Ambient operating temperature
−
10 to 55
°
C (with no icing or condensation), for 3-year warranty:
−
10 to 50
°
C
Ambient operating humidity
25% to 85%
Storage temperature
−
25 to 65
°
C (with no icing or condensation)
3200
3000
2300
1500
1400
1200
1100
1000
900
800
700
600
500
400
300
200
100
0
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
Input Type
Name
Platinum resistance
thermometer
Thermocouple
Infrared temperature
sensor
Pt100
JPt100
K
J
T
E
L
U
N
R
S
B
10 to
70ºC
60 to
120ºC
115 to
165ºC
160 to
260ºC
1300
−
100.0
−
300.0
−
200.0
Temperature range (ºF)
1500
900.0
900.0
210.0
210.0
−
300
−
199.9
0.0
0.0
0.0
−
300
−
199.9
2300
900.0
0.0
−
100
1500
1500
750.0
700
700
700
700
−
300
−
199.9
−
199.9
−
300
0
−
100
−
300
0
0
0
2300
3000
3000
3200
300
0
0
0
190
240
320
500
1100
Setting number
The applicable standards for the input types
are as follows:
K, J, T, E, N, R, S, B: IEC584-1
L: Fe-CuNi, DIN 43710-1985
U: Cu-CuNi, DIN 43710-1985
Pt100: IEC 751
Shaded settings are the default settings.
Summary of Contents for E5CN-FR