MINiBOX 0-10V X3/X2/X1 

 

 

 

 

 

Multifunction Actuator with 3/2/1 fold 0-10V analog 

input/output 

 

 

 

 

 

 

 

 

ZIO3X010 / ZIO2X010 / ZIO1X010 

 

U

S

E

R

 M

A

N

U

A

L

 

 

 
 
 

 

Application program version: [1.2]  

User manual edition: [1.2]_a 

 

 

 

www.zennio.com

  

 

 

Summary of Contents for MINiBOX 0-10V X1

Page 1: ... MINiBOX 0 10V X3 X2 X1 Multifunction Actuator with 3 2 1 fold 0 10V analog input output ZIO3X010 ZIO2X010 ZIO1X010 USER MANUAL Application program version 1 2 User manual edition 1 2 _a www zennio com ...

Page 2: ...es 3 1 Introduction 4 1 1 MINiBOX 0 10V X3 X2 X1 4 1 2 Installation 5 1 3 Start Up and Power Loss 6 2 Configuration 7 2 1 General 7 2 2 Analog Input 9 2 3 Analog Voltage Output 10 2 3 1 Operating Time Counter 10 2 4 Fan Coil 12 2 5 Thermostats 13 2 6 Logic Functions 14 2 7 Manual Control 15 ANNEX I Communication Objects 18 ...

Page 3: ...cal Support https support zennio com 3 DOCUMENT UPDATES Version Changes Page s 1 2 _a New devices MINiBOX 0 10V X2 y MINiBOX 0 10V X1 Changes in the software library Analog inputs module is added Optimisation of the analog output heartbeat and fan coil ...

Page 4: ... MINiBOX 0 10V X1 1 channel and all their characteristics will be mentioned respectively and following this order along the entire document 3 2 1 fan coil analog modules to control 2 and 4 pipes units with 0 10V fan or valves 3 2 1 independent 0 10V analog voltage outputs configurable as fan or valve of a fan coil unit or other adjustable load between these voltage levels 3 2 1 independent analog ...

Page 5: ...ce into the programming mode making the associated LED 5 light in red Note if this button is held while plugging the device into the KNX bus the device will enter into safe mode In such case the LED will blink in red every 0 5 seconds Inputs Outputs 1 inputs output ports for the insertion of the stripped cables of the systems being controlled by the actuator see sections 2 2 and 2 3 Please secure ...

Page 6: ...rticular state and whether the device should send certain objects to the bus after the power recovery Please consult the next sections of this document for further details On the other hand when a bus power failure takes place the MINiBOX 0 10V devices will interrupt any pending actions and will save its state so it can be recovered once the power supply is restored Also after failure recovery the...

Page 7: ...ossible to activate deactivate all the required functionality The following image corresponds to the MINiBOX 0 10V X3 The reduced versions only show the number of channels corresponding to each device Figure 2 General MINiBOX 0 10V X3 Channel X disabled input output 1 enables or disables the Analog Inputs see section 2 2 and or Analog Voltage Outputs see section 2 3 tabs on the left menu Fan Coils...

Page 8: ...otification Note The first sending after download or bus failure takes place with a delay of up to 255 seconds to prevent bus overload The following sendings match the period set Device Recovery Objects Send 0 and 1 disabled enabled this parameter lets the integrator activate two new communication objects Heartbeat Device Recovery which will be sent to the KNX bus with values 0 and 1 whenever the ...

Page 9: ...nputs which can be used to connect different sensors with different voltage 0 10V 0 1V y 1 10V or current 0 20mA y 4 20mA measurement ranges Please refer to the specific user manual Analog Inputs available in the MINiBOX 0 10V product sections at the Zennio website www zennio com for detailed information about the functionality and the configuration of the related parameters ...

Page 10: ...ctionality and the configuration of the related parameters 2 3 1 OPERATING TIME COUNTER When an analog output is enabled it is possible to configure the operating time counter a function that offers the possibility to record the time the output is on or off It is possible to select the counting mode as wells as reading and updating the counters values by directly acting over the enabled objects fo...

Page 11: ...counter record in hours of the time that the output remains switched on off The maximum value is 65535 when the maximum limit is reached this value is maintained Counting Mode Output Off Output On sets whether the counter will save the time the output remains on or the time the output remains off Initial Operating Time Keep Value Defined Value defines the initial value after download When selectin...

Page 12: ...es incorporate three two one modules to control the fan and valves of a 2 or 4 pipes fan coil unit Please refer to the specific user manual Fan Coil Analog available in the MINiBOX 0 10V product sections at the Zennio website www zennio com for detailed information about the functionality and the configuration of the related parameters ...

Page 13: ...incorporate three two one Zennio thermostats that can be enabled and configured independently Please refer to the specific Zennio Thermostat user manual available in the MINiBOX 0 10V product sections at the Zennio website www zennio com for detailed information about the functionality and the configuration of the related parameters ...

Page 14: ...h The execution of each function can depend on a configurable condition which will be evaluated every time the function is triggered through specific parameterizable communication objects The result after executing the operations of the function can also be evaluated according to certain conditions and afterwards sent or not to the KNX bus which can be done every time the function is executed peri...

Page 15: ... the beginning On the contrary switching to the Test On mode unless disabled by parameter needs to be done by long pressing the Prog Test button for at least three seconds until the LED is no longer red and turns yellow From that moment once the button is released the LED light will remain green to confirm that the device has switched from the Test Off mode to the Test On mode After that an additi...

Page 16: ...control the outputs through the on board pushbuttons Orders received through communication objects will be ignored regardless of the channel or the output they are addressed to Individual output the action performed on the output by pressing the physical buttons will be the same as described in the Test Off mode except that the status objects will not be affected Note unlike in test off mode in te...

Page 17: ... while switching to Test On mode does require long pressing the Prog Test button Lock Manual Control disabled enabled unless the above parameter has been Disabled the Lock Manual Control parameter provides an optional procedure for locking the manual control in runtime When this checkbox is enabled object Manual Control Lock turns visible as well as two more parameters Value 0 Lock 1 Unlock 0 Unlo...

Page 18: ...68 32767 AIx Measured Value 2 Byte Signed 2 Bytes O C R T 9 xxx 671088 64 670433 28 AIx Measured Value 2 Byte Float 4 Bytes O C R T 14 xxx AIx Measured Value 4 Byte Float 1 Byte O C R T DPT_Scaling 0 100 AIx Measured Value 1 Byte Percentage 6 13 20 1 Bit O C R T DPT_Alarm 0 1 AIx Lower Range Error 0 No Alarm 1 Alarm 7 14 21 1 Bit O C R T DPT_Alarm 0 1 AIx Upper Range Error 0 No Alarm 1 Alarm 8 15 ...

Page 19: ...47 62 1 Bit I C W DPT_DayNight 0 1 AOx Day Night Mode 0 Day Mode 1 Night Mode 1 Bit I C W DPT_DayNight 0 1 AOx Day Night Mode 0 Night Mode 1 Day Mode 33 48 63 1 Bit I C W DPT_Switch 0 1 AOx Day Night Mode On Off 0 Off 1 On 34 49 64 1 Bit I C W DPT_Start 0 1 AOx Simple Timer 0 Deactivate 1 Activate 35 50 65 1 Bit I C W DPT_Start 0 1 AOx Flashing 0 Deactivate 1 Activate 36 51 66 1 Bit I C W T U DPT_...

Page 20: ...e Protection Status 0 Not Active 1 Active 1 Bit O C R T DPT_Switch 0 1 FCx Valve Anti Seize Protection Status 0 Not Active 1 Active 81 114 147 1 Bit I C W T U DPT_Switch 0 1 FCx Heating Valve Control Variable 1 Bit 0 Close Valve 1 Open Valve 82 115 148 1 Byte O C R T DPT_Scaling 0 100 FCx Heating Valve Control 1 Byte 0 100 1 Bit O C R T DPT_OpenClose 0 1 FCx Heating Valve Control 1 Bit 0 Open 1 Cl...

Page 21: ... FCx Manual Fan Enumeration Control S0 0 S1 25 S2 50 S3 75 S4 100 1 Byte I C W T U DPT_Fan_Stage 0 255 FCx Manual Fan Enumeration Control S0 0 S1 100 99 132 165 1 Byte I C W T U DPT_Scaling 0 100 FCx Manual Fan Percentage Control 0 100 100 133 166 2 Bytes I C W T U DPT_TimePeriodMin 0 65535 FCx Manual Fan Manual Control Duration 0 Endless 1 1440 min 2 Bytes I C W T U DPT_TimePeriodHrs 0 65535 FCx ...

Page 22: ...r 0 1 Tx Window Status Input 0 Closed 1 Open 180 218 256 1 Bit I C W DPT_Trigger 0 1 Tx Comfort Prolongation 0 Nothing 1 Timed Comfort 181 219 257 1 Byte O C R T DPT_HVACMode 1 Comfort 2 Standby 3 Economy 4 Building Protection Tx Special Mode Status 1 Byte HVAC Mode 182 220 258 2 Bytes I C W DPT_Value_Temp 273 00º 670433 28º Tx Setpoint Thermostat Setpoint Input 2 Bytes I C W DPT_Value_Temp 273 00...

Page 23: ...ontrol 1 Bit O C R T DPT_Switch 0 1 Tx Sx Control Variable PI Control PWM 201 207 239 245 277 283 1 Bit O C R T DPT_Switch 0 1 Tx Sx PI State Cool 0 PI Signal 0 1 PI Signal Greater than 0 202 208 240 246 278 284 1 Bit O C R T DPT_Switch 0 1 Tx Sx PI State Heat 0 PI Signal 0 1 PI Signal Greater than 0 1 Bit O C R T DPT_Switch 0 1 Tx Sx PI State 0 PI Signal 0 1 PI Signal Greater than 0 285 286 287 2...

Page 24: ...g 0 100 LF Function x Result 1 Byte Percentage 2 Bytes O C R T DPT_Value_2_Count 32768 32767 LF Function x Result 2 Byte Signed 2 Bytes O C R T 9 xxx 671088 64 670433 28 LF Function x Result 2 Byte Float 367 369 371 4 Bytes I O C R W T DPT_LongDeltaTimeSec 2147483648 2147483647 AOx Operating Time s Time in Seconds 368 370 372 2 Bytes I O C R W T DPT_TimePeriodHrs 0 65535 AOx Operating Time h Time ...

Page 25: ...in and send us your inquiries about Zennio devices https support zennio com Zennio Avance y Tecnología S L C Río Jarama 132 Nave P 8 11 45007 Toledo Spain Tel 34 925 232 002 www zennio com info zennio com ...