background image

R

169

Ramp/Soak Process Controller

E5CK-T

Advanced, 1/16-DIN Ramp/Soak
Process Controllers Ideal for
Worldwide Use

H

Offers one pattern of simple
programming control, up to four patterns
with communications (16 steps per
pattern)

H

Water-resistant front face meets
IP66/NEMA 4 (indoor use)

H

Modular structure, one-stock type

H

Heat/Cool control

H

Serial communications (RS-232C and
RS-485)

H

Temperature and analog inputs

H

High-accuracy: 100 ms sampling (for
analog input)

H

Conforms to international EMC and
safety standards

H

24V AC/DC type also available

H

3-year warranty

RC

Ordering Information

Order control output boards and option boards separately. A single output board and option board can be mounted to each base unit. For
example, for a relay control output, order the E53-R4 output board in addition to the E5CK-TAA1-500 Process Controller.

J

PROCESS CONTROLLERS

Description

DIN size

Supply voltage

Part number

Base unit with terminal cover

1/16 DIN

100-240 VAC

E5CK-TAA1-500 AC100-240

(48 x 48 mm)

24 VAC/VDC

E5CK-TAA1-500 AC/DC24

Summary of Contents for E5CK-AA1-500 AC100-240

Page 1: ...H High accuracy 100 ms sampling for analog input H Conforms to international EMC and safety standards H 24V AC DC type also available H 3 year warranty RC Ordering Information Order control output boa...

Page 2: ...DE0106 part 100 E5CK T 1 E53 COV07 Software For setup and monitoring requires optional computer communications board All 1 SYS CONFIG V2 0 Temperature Ranges Platinum Resistance Thermometer Input swit...

Page 3: ...units of 0 1 FS Integral reset time I 0 to 3 999 s in units of 1 s Derivative rate time D 0 to 3 999 s in units of 1 s Control period 1 to 99 s in units of 1 s Manual reset value 0 0 to 100 0 in unit...

Page 4: ...contact discharge level 2 8kV air discharge level 3 Immunity RF interference ENV50140 10V m amplitude modulated 80 MHz to 1 GHz level 3 10 V m pulse modulated 900 MHz Immunity Conducted Disturbance E...

Page 5: ...rd model set up the output boards for control outputs 1 and 2 before mounting the Controller 2 On a position proportional model the relay output board is already set so this setup operation is unneces...

Page 6: ...74 Dimensions Unit mm inch J E5CK T 60 2 36 min Panel Cutouts 65 2 56 min 48 1 89 58 2 28 13 3 0 52 100 3 94 53L x 53W 44 8 X 44 8 J ACCESSORIES ORDER SEPARATELY Terminal Cover E53 COV07 44 3 1 74 44...

Page 7: ...arefully pull the internal mechanism from the housing Refer to the drawing below J SETTING UP THE OUTPUT BOARD 1 Two rectangular holes are provided on the power board right side of Controller Fit the...

Page 8: ...cm Adapter Panel Watertight packing Input Jumper Setting Note The jumper is factory set to TC S PT temperature input Set the jumper to temperature voltage or current input according to the sensor con...

Page 9: ...s from external noise Solderless terminals are recommended when wiring the Controller Tighten the terminal screws using a torque no greater than 0 78 N S m or 8 kgf S cm max Be careful not to tighten...

Page 10: ...eter inputs set the inputs to a common position TC PT as the temperature input Control Output Terminal numbers 11 and 12 are for control output 1 OUT1 The five output types and internal equalizing cir...

Page 11: ...8 7 6 13 14 11 12 3 2 Relay specifications are as follows SPST NO 250 VAC 1 A Option Terminal numbers 1 13 and 14 are valid only when the option board is set in the Controller The following four conn...

Page 12: ...ay key sp0 0 4 Set the target value to 50 Target value Display key 50 sp0 Step number display 5 Press the Display Key to shift to the display for the time of Step 0 Time parameter for step 0 Step time...

Page 13: ...C 199 9 to 999 9 F Platinum resistance 1 Pt100 199 9 to 650 0 C 199 9 to 999 9 F thermometer 2 K1 200 to 1 300 C 300 to 2 300 F Thermocouple 3 K2 0 0 to 500 0 C 0 0 to 900 0 F 4 J1 100 to 850 C 100 t...

Page 14: ...and 2 and auxiliary outputs 1 and 2 The assignment destination of each output function is restricted Refer to the tables provided under the headings Standard Models and Position Proportionate Models...

Page 15: ...ce deviation X SP ON OFF X SP ON OFF 7 Lower limit alarm with standby sequence deviation X SP ON OFF X SP ON OFF 8 Absolute value upper limit alarm X 0 ON OFF 0 X ON OFF 9 Absolute value lower limit a...

Page 16: ...e alarm 1 to 3 open in alarm parameters setup mode Factory setting is close in alarm n o J PARAMETER OPERATION LIST Switching to modes other than manual or protect mode is carried out using the mode s...

Page 17: ...AT auto tuning set up the control period change PID parameters and set alarm values Level 2 Mode This is the auxiliary mode for adjusting control In this mode you can set the parameters for limiting...

Page 18: ...tors remote SP in the local SP mode Set Point During SP Ramp Monitors the set point when the SP ramp function is used J PROTECT MODE Press twice for 1 s min Security Key protect To level 0 Press twice...

Page 19: ...arameter of the Controller in standard control is 0 Hysteresis Heat Available when the Controller is in ON OFF control For heating cooling control Hysteresis Cool Available when the Controller is in O...

Page 20: ...ut Shift Lower Limit Available if the input type is a thermocouple or platinum resistance thermometer See Input Shift For models E5AK EK T only Open Close hysteresis Standby time Input Shift Temperatu...

Page 21: ...are used J OPTION MODE Event Input Assignment 1 Available for the event input function Event Input Assignment 2 Available for the event input function For models E5AK E5EK T only Event Input Assignme...

Page 22: ...t value step 0 time step 1 target value and step 1 time The step target value can be set within a range between the lower and upper target value limits The default value is zero The step time can be s...

Page 23: ...p 0 Set the ON OFF timing with the timing signal 1 2 ON time and time signal 1 2 OFF time parameters in Program mode ON Conditions If the ON time is shorter than the OFF time the signal will be reset...

Page 24: ...mal the probable cause may be external noise affecting the control system Check for external noise Operation at Error Control output functions turn OFF 2 mA max at 4 to 20 mA output and output equival...

Page 25: ...ol continues allowing normal operation Motor Calibration Error Displayed on the No 2 Display Meaning Motor calibration has ended with an error Action First correctly connect the wiring for the potenti...

Page 26: ...Unit must be approximately 0 78 N S m or 8 kgf S cm Use the following type of solderless terminals for M3 5 screws 7 2 mm max 7 2 mm max J OPERATION The alarm outputs of a model with an alarm functio...

Page 27: ...Model G3PA G3PB G3NH G3NA G3NE G3B Appear ance SSRs connected in parallel E5AK E5EK T 8 pcs E5CK T 4 pcs E5AK E5EK T 8 pcs E5CK T 4 pcs E5AK E5EK T 5 pcs E5CK T 2 pcs E5AK E5EK T 2 pcs E5CK T 1 piece...

Page 28: ...8 00 Specifications subject to change without notice Printed in U S A OMRON ELECTRONICS INC One East Commerce Drive Schaumburg IL 60173 1 800 55 OMRON OMRON CANADA INC 885 Milner Avenue Scarborough On...

Reviews: