Inputting Parameters
The Digital Controller has three display levels, 0, 1, and 2, in which only specific parameters can be set. Level 0 is the initial and is automatically
entered at power application. To change the mode to set or change a different group of parameters, hold down the Level Key for 2 seconds
minimum. The display level mode changes as shown below. Actual displays vary with models and switch settings. If a display does not appear
as expected, check your switch settings.
–––––––
–––––––
–––––––
Level 0
Power ON
Level 1
Level 2
Press the Level Key.
Press the Level Key.
Press the Level Key.
Manual output value,
main setting, alarm set
value, input shift
Decimal point setting, scaling
setting, control period, hyster-
esis, hysteresis alarm setting,
shift set
Control output value, in-
put type, alarm mode
Level 0
Process value
o 0
Process value
0.0
Press
a
.
al–1
0.0
al–2
0.0
in–5
0.0
p
10.0
i
240
d
60
Press
a
.
Press
a
.
Press
a
.
Press
a
.
Press
a
.
Press
a
.
Press
a
.
Manual output setting
Main setting
Alarm value 1
Alarm value 2
Input shift
Proportional band
Integral time
Derivative time
(Note 1)
(Note 2)
(Note 3)
(Note 4)
(Note 5)
(Note 5)
(Note 5)
PV
SV
Note:
1. Not displayed in auto output mode.
2. Not displayed when alarm 1 is disabled (SW205 set to
0).
3. Not displayed when alarm 2 is disabled (SW203 set to 0
or 9).
4. Not displayed when the input shift display is disabled
(SW201, pin 3 ON).
5. Not displayed when PID display is disabled (SW201, pin
6 ON).
Proportional Band:
p
When the character
p
is displayed on the PV display, the propor-
tional band (P constant) can be changed using the Up and Down
Keys. The new value will be displayed on the SV display. It can be
set in a range from 0.0 to 999.9% FS in units of 0.1% FS. The factory
setting is 10.0% FS.
Integral Time (Reset Time):
i
When the character
i
is displayed on the PV display, the integral time
(I constant) can be changed using the Up and Down Keys. It can be
set in a range from 0 to 3,999 seconds in units of 1 second. The fac-
tory setting is 240 seconds.
Derivative Time (Rate Time):
d
The derivative time (D constant) can be changed when the charac-
ter
d
is displayed on the PV display using the Up and Down Keys. It
can be set in a range from 0 to 3,999 seconds in units of 1 second.
The factory setting is 60 seconds.
Process Value
Manual output value (only in manual output mode) and main setting
can be changed when process value is displayed by using the Up
and Down keys.
Selecting the Output Mode
The A/M Key can be pressed for one second or longer to change
between the auto and manual output modes.
Auto Output Mode
In auto output mode, the control will function automatically. When
the A/M Key is pressed and the auto output mode is first entered,
displays like the following will appear (display level 0).
123
80
PV
SV
Process value
Main setting
Manual Output Mode
This mode is used to turn on outputs manually. Use the Up and
Down Keys to set the desired output value (as a percentage) in the
SV display. About 2 seconds after the desired value is set, outputs
will turn on accordingly.