background image

E5AX-LA/-MA

E5AX-LA/-MA

7

Switch

Mode (SW203, 205)

Alarm output

Setting range

setting

Alarm operation

Display

When X is positive

When X is negative

0

No alarm

No display

OFF

---

1

Upper- and lower-limit alarm

)––(

X

X

---

0 to 9999

2

Upper-limit alarm

–––(

X

X

–999 to 9999

3

Lower-limit alarm

)–––

X

X

4

Upper- and lower-limit range
alarm

–()–

X

X

---

0 to 9999

5

Upper- and lower-limit alarm with
standby sequence

3––e

X

X

---

6

Upper-limit alarm with standby
sequence

–––e

X

X

–999 to 9999

7

Lower-limit alarm with standby
sequence

3–––

X

X

8

Absolute-value alarm

1––(

Y

0

Y

0

9

SW205: Proportional alarm*

pro

X

X

SW203: No alarm

No display

OFF

*The proportional alarm is detected when the temperature reaches
the set alarm point (A in the figure on the right), which is the lower
limit of a proportional band. When the temperature rises to the upper
limit of the proportional band (point B in the figure), the alarm output
is turned ON. This alarm function is convenient when the main set-
ting is used for heating control, while the proportional alarm function
is used for cooling control, so that heating and cooling control can be
easily performed.

Note:

PB: proportional band (fixed to 10.0% FS)
Proportional period is 20 seconds.
The operation of the alarm is not affected by pin
2 of the operating mode selector (SW201).

PB

X

A

B

SP

ON

 Key Protection Switch (SW101, PROTECT)

When the key protection switch is set to the ON position, the Level Key, Up and Down Keys, and Auto-tuning Key cannot be operated. In effect,
the Digital Controller is write-protected and the set values (such as the alarm value) can be read out only. The set point, however, will not be
protected if the SP protection disable is turned ON (pin 4 of SW201).

Summary of Contents for E5AX-LA

Page 1: ...equipped with a terminal block to connect communications Specify a terminal block by adding X to the model number Example E5AX LA02 X Capable of transmitting the process value or output value but remo...

Page 2: ...ons character heights PV 15 mm and SV 11 mm Color PV red SV green Shift set input No voltage contact signal input set value shifted when ON Contact impedance 100 W max Other functions Upper and lower...

Page 3: ...0 ms Shift set 999 to 9999 Decimal point is displayed at set position Input shift 999 to 9999 Decimal point is displayed at set position Insulation resistance 20 MW min at 500 VDC Dielectric strength...

Page 4: ...e connected to one host computer using serial communications RS 422 RS 485 3 Outputs process value within the set limits Nomenclature Process Value PV Display Displays not only the process value but a...

Page 5: ...Output Unit is mounted Set the output selector to CUR current when a Current Output Unit is mounted To remove a Control Output Unit push it up with the tip of a flat blade screwdriver as shown below F...

Page 6: ...tion Pin number Pin setting Control setting Control mode 1 ON ON OFF operation OFF PID operation Control output 2 ON Normal OFF Reverse Input shift 3 ON Enabled OFF Disabled SP set point 4 ON Enabled...

Page 7: ...imit of a proportional band When the temperature rises to the upper limit of the proportional band point B in the figure the alarm output is turned ON This alarm function is convenient when the main s...

Page 8: ...disabled SW201 pin 6 ON Proportional Band p When the character p is displayed on the PV display the propor tional band P constant can be changed using the Up and Down Keys The new value will be displ...

Page 9: ...t shift 10 0 10 0 1 0 shifted by 1 0 10 0 11 0 1 0 shifted by 1 0 10 0 9 0 This function can be used mainly for fine tuning compensation while leaving the set value unaffected Select this function by...

Page 10: ...2 seconds so that the control operation can be performed more accurately Control output ON OFF 20 seconds When control period is set to 20 seconds Hysteresis hys The hysteresis value for the ON OFF co...

Page 11: ...ant control operations to be performed while setting parameters turn off the power and then turn it back on after setting the desired parameters Auto tuning When the Level Key and Mode Key are pressed...

Page 12: ...ed the input range OFF Approx 1 mA The output will turn ON ac cording to the alarm mode when the input goes to maximum except in the proportional alarm mode in which it will remain OFF e111 flashes e3...

Page 13: ...ons connector RS 232C and BCD connector is shown Communications board RS 422 and 485 terminals are shown Communications board 4 to 20 mA transmission output is shown 4 to 20 mA transmission output RS...

Page 14: ...ipment may prevent proper operation Attach the two mounting brackets supplied with E5AX on the top and bottom of the Digital Controller Tighten the screws of the mounting brackets with your fingers Mo...

Page 15: ...C are supplied with the Digital Controller Attach the proper stickers to the front panel as shown below allowing the input type and Control Output Unit mounted in the Digital Controller to be easi ly...

Reviews: