background image

E5AX-LA/-MA

E5AX-LA/-MA

4

 Communications

Protocol

RS-232C, RS-422

RS-485

BCD

Transmission output

Transmission method

Half-duplex

Data select code

4 to 20 mA DC
Load: 600 

W

 max.

Resolution: Approx. 3,200

Synchronization method

Start-stop synchronization

---

---

Baud rate

150/300/600/1,200/2,400/4,800/9,600 bps

Transmission code

ASCII (7-bit)

Communications

Write to
Digital
Controller

Main setting, set alarm value, proportional
band, integral time, derivative time, AT
start/stop etc.

Main setting, set
alarm value

Write disabled

Read from
Digital
Controller

Main setting, set alarm value, proportional
band, integral time, derivative time, output
value, scaling value, process value, error
codes, etc.

Main setting, set
alarm value,
process value, error
codes, etc.

Process value (see note 3),
output value

Note:

1. The maximum total cable length must not exceed the following limits.

RS-422: 500 m; RS-232C: 15 m; RS-485: 500 m

$

 Recommended connectors for E5AX.

RS-485, -422, Transmission output

XM4 D-sub connector (9 pin) (OMRON)

RS-232C, BCD

XM4, D-sub connector (25 pin) (OMRON)

2. A maximum of 32 Digital Controllers can be connected to one host computer using serial communications (RS-422, RS-485).

3. Outputs process value within the set limits.

Nomenclature

Process Value (PV) Display

Displays not only the process value but also in-
dicates the character for parameter being dis-
played on the SV display and error messages.

Auto-tuning Indicator

Flashes on and off every
second when auto-tun-
ing is taking place.

Display Key

Press to shift the display
to the next parameter.

Level Key

Press for 2 seconds mini-
mum to change levels to
set different groups of pa-
rameters.

Output Indicator

Lights when the control
output is ON. Lights off
when the current output is
ON.

Shift Set Indicator

Lights when shift set func-
tion is in operation.

Manual Mode Indicator

Lights when in manual
mode.

Set Value (SV) Display

Displays set value and other
parameters.

Alarm 1 Indicator

Lights when the alarm 1 output is ON.

Alarm 2 Indicator

Lights when the alarm 2 output is ON.

A/M Key (Automatic/Manual)

Press for 1 second minimum to switch
between auto output mode and manual
output mode.

Up Key

Press to increase the set value or oth-
er parameters. Successively in-
creases the value when held down.

Front Cover

Down Key

Press to decrease the set value or other pa-
rameters. Successively decreases the val-
ue when held down.

Summary of Contents for E5AX-LA

Page 1: ...equipped with a terminal block to connect communications Specify a terminal block by adding X to the model number Example E5AX LA02 X Capable of transmitting the process value or output value but remo...

Page 2: ...ons character heights PV 15 mm and SV 11 mm Color PV red SV green Shift set input No voltage contact signal input set value shifted when ON Contact impedance 100 W max Other functions Upper and lower...

Page 3: ...0 ms Shift set 999 to 9999 Decimal point is displayed at set position Input shift 999 to 9999 Decimal point is displayed at set position Insulation resistance 20 MW min at 500 VDC Dielectric strength...

Page 4: ...e connected to one host computer using serial communications RS 422 RS 485 3 Outputs process value within the set limits Nomenclature Process Value PV Display Displays not only the process value but a...

Page 5: ...Output Unit is mounted Set the output selector to CUR current when a Current Output Unit is mounted To remove a Control Output Unit push it up with the tip of a flat blade screwdriver as shown below F...

Page 6: ...tion Pin number Pin setting Control setting Control mode 1 ON ON OFF operation OFF PID operation Control output 2 ON Normal OFF Reverse Input shift 3 ON Enabled OFF Disabled SP set point 4 ON Enabled...

Page 7: ...imit of a proportional band When the temperature rises to the upper limit of the proportional band point B in the figure the alarm output is turned ON This alarm function is convenient when the main s...

Page 8: ...disabled SW201 pin 6 ON Proportional Band p When the character p is displayed on the PV display the propor tional band P constant can be changed using the Up and Down Keys The new value will be displ...

Page 9: ...t shift 10 0 10 0 1 0 shifted by 1 0 10 0 11 0 1 0 shifted by 1 0 10 0 9 0 This function can be used mainly for fine tuning compensation while leaving the set value unaffected Select this function by...

Page 10: ...2 seconds so that the control operation can be performed more accurately Control output ON OFF 20 seconds When control period is set to 20 seconds Hysteresis hys The hysteresis value for the ON OFF co...

Page 11: ...ant control operations to be performed while setting parameters turn off the power and then turn it back on after setting the desired parameters Auto tuning When the Level Key and Mode Key are pressed...

Page 12: ...ed the input range OFF Approx 1 mA The output will turn ON ac cording to the alarm mode when the input goes to maximum except in the proportional alarm mode in which it will remain OFF e111 flashes e3...

Page 13: ...ons connector RS 232C and BCD connector is shown Communications board RS 422 and 485 terminals are shown Communications board 4 to 20 mA transmission output is shown 4 to 20 mA transmission output RS...

Page 14: ...ipment may prevent proper operation Attach the two mounting brackets supplied with E5AX on the top and bottom of the Digital Controller Tighten the screws of the mounting brackets with your fingers Mo...

Page 15: ...C are supplied with the Digital Controller Attach the proper stickers to the front panel as shown below allowing the input type and Control Output Unit mounted in the Digital Controller to be easi ly...

Reviews: