E5AX-LA/-MA

E5AX-LA/-MA

3

 

Characteristics

Setting accuracy

+

0.3% FS 

+

1 digit max.

Indication accuracy

+

0.3% FS 

+

1 digit max. (Set value coincides with the indicated value, because no relative

error exists between both values.)

Indication range

–10% to 110% FS

Hysteresis

0.0% to 100.0% FS (in units of 0.1% FS)

Proportional band

0.0% to 999.9% FS (in units of 0.1% FS)

Integral time

0 to 3,999 s (in units of 1 s)

Derivative time

0 to 3,999 s (in units of 1 s)

Alarm output setting range

–999 to 9999 (Decimal point is displayed at set position)

Alarm output hysteresis

0.0% to 100.0% FS (in units of 0.1% FS)

Scaling setting range

–999 to 9999 (Decimal point is displayed at set position)

Manual output setting range

0% to 100% (in units of 1%)

Control period

Pulse output: 1 to 99 s (in units of 1 s)

Sampling period

500 ms

Output refresh period

Pulse output:

500 ms

Current output: 500 ms

Display refresh period

500 ms

Shift set

–999 to 9999 (Decimal point is displayed at set position)

Input shift

–999 to 9999 (Decimal point is displayed at set position)

Insulation resistance*

20 M

W

 min. (at 500 VDC)

Dielectric strength*

2,000 VAC 50/60 Hz for 1 min between terminals of different polarity

Vibration resistance

Malfunction: 2 to 55 Hz, 2G 10 min each in X, Y, and Z directions
Destruction: 10 to 55 Hz, 0.75-mm double amplitude 2 hrs each in X, Y, and Z directions

Shock resistance

Malfunction: 200 m/s

2

 3 times each in 6 directions

Destruction: 300 m/s

2

 3 times each in 6 directions

Ambient temperature

Operating: –10

%

 to 55

%

C (with no icing)

Storage:

–25

%

 to 65

%

C (with no icing)

Ambient humidity

Operating: 35% to 85%

Memory protection

Non-volatile memory

Enclosure ratings

Front panel: IEC standard IP50
Rear case: IEC standard IP20
Terminals:

IEC standard IP00

Weight

Standard: Approx. 350 g; Communications: Approx. 480 g; Mounting bracket: Approx. 50 g

*Tested with an Output Unit mounted.

 

Output Unit Characteristics

Relay unit life expectancy

Mechanical: 10,000,000 operations min.
Electrical:

100,000 operations min.

Summary of Contents for E5AX-LA

Page 1: ...equipped with a terminal block to connect communications Specify a terminal block by adding X to the model number Example E5AX LA02 X Capable of transmitting the process value or output value but remo...

Page 2: ...ons character heights PV 15 mm and SV 11 mm Color PV red SV green Shift set input No voltage contact signal input set value shifted when ON Contact impedance 100 W max Other functions Upper and lower...

Page 3: ...0 ms Shift set 999 to 9999 Decimal point is displayed at set position Input shift 999 to 9999 Decimal point is displayed at set position Insulation resistance 20 MW min at 500 VDC Dielectric strength...

Page 4: ...e connected to one host computer using serial communications RS 422 RS 485 3 Outputs process value within the set limits Nomenclature Process Value PV Display Displays not only the process value but a...

Page 5: ...Output Unit is mounted Set the output selector to CUR current when a Current Output Unit is mounted To remove a Control Output Unit push it up with the tip of a flat blade screwdriver as shown below F...

Page 6: ...tion Pin number Pin setting Control setting Control mode 1 ON ON OFF operation OFF PID operation Control output 2 ON Normal OFF Reverse Input shift 3 ON Enabled OFF Disabled SP set point 4 ON Enabled...

Page 7: ...imit of a proportional band When the temperature rises to the upper limit of the proportional band point B in the figure the alarm output is turned ON This alarm function is convenient when the main s...

Page 8: ...disabled SW201 pin 6 ON Proportional Band p When the character p is displayed on the PV display the propor tional band P constant can be changed using the Up and Down Keys The new value will be displ...

Page 9: ...t shift 10 0 10 0 1 0 shifted by 1 0 10 0 11 0 1 0 shifted by 1 0 10 0 9 0 This function can be used mainly for fine tuning compensation while leaving the set value unaffected Select this function by...

Page 10: ...2 seconds so that the control operation can be performed more accurately Control output ON OFF 20 seconds When control period is set to 20 seconds Hysteresis hys The hysteresis value for the ON OFF co...

Page 11: ...ant control operations to be performed while setting parameters turn off the power and then turn it back on after setting the desired parameters Auto tuning When the Level Key and Mode Key are pressed...

Page 12: ...ed the input range OFF Approx 1 mA The output will turn ON ac cording to the alarm mode when the input goes to maximum except in the proportional alarm mode in which it will remain OFF e111 flashes e3...

Page 13: ...ons connector RS 232C and BCD connector is shown Communications board RS 422 and 485 terminals are shown Communications board 4 to 20 mA transmission output is shown 4 to 20 mA transmission output RS...

Page 14: ...ipment may prevent proper operation Attach the two mounting brackets supplied with E5AX on the top and bottom of the Digital Controller Tighten the screws of the mounting brackets with your fingers Mo...

Page 15: ...C are supplied with the Digital Controller Attach the proper stickers to the front panel as shown below allowing the input type and Control Output Unit mounted in the Digital Controller to be easi ly...

Reviews: