E5AX-LA/-MA

E5AX-LA/-MA

11

Control Output Value: 

o

When the Digital Controller enters level 2, the control output value is
displayed on the SV display in a range of 0.0% to 100.0%.

Input Type: 

in–t

When 

in–t

    is displayed on the PV display, the present setting of the

input type selector (SW206), is displayed on the SV display. The fol-
lowing table shows the messages that may be displayed:

Model

Display

Sensor

E5AX-LA

cur

  

1

4 to 20 mA

cur

  

2

0 to 20 mA

uol

  

1

1 to 5 V

uol

  

2

0 to 5 V

uol

  

3

0 to 1 V

E5AX-MA

uol

  

1

0 to 100 mV

uol

  

2

0 to 10 mV

uol

  

3

–10 to 10 mV

Alarm Mode: 

al–1

al–2

When 

al

 is displayed on the PV display in level 2, alarm output mode

or the present setting of the corresponding alarm mode selector is
displayed on the SV display. The following table shows the mes-
sages that may be displayed.

Display

Alarm mode

No display

No alarm

)––(

Upper- and lower-limit alarm

–––(

Upper-limit alarm

)–––

Lower-limit alarm

–()–

Upper- and lower-limit range
alarm

3––e

Upper- and lower-limit alarms
with standby sequence

–––e

Upper-limit alarm with standby
sequence

3–––

Lower-limit alarm with standby
sequence

1––c

Absolute-value alarm

pro

Proportional alarm

 Starting Control Operation

The E5AX will start control operations as soon as power is turned on
until power is turned off. If you don’t want control operations to be
performed while setting parameters, turn off the power and then turn
it back on after setting the desired parameters.

Auto-tuning

When the Level Key and Mode Key are pressed simultaneously for
1 second minimum, the Digital Controller automatically starts tuning
the PID constants. While auto-tuning is in operation, the auto-tuning
indicator on the front panel will flash. The Digital Controller executes
control based on the set PID constants (factory set to P = 10.0% FS,
I = 240 seconds, and D = 60 seconds) until process value of the con-
trolled system reaches main setting. After that, the Digital Controller
automatically adjusts the PID constants using the limit cycle meth-
od. When the auto-tuning indicator turns off, the auto-tuning is termi-
nated and PID constants are renewed.

Main
setting

Previous PID
constants

New PID constants

AT indicator flashes

Limit cycle method: The optimum PID constants are calculated by
this method by varying the control output variable and generating
external oscillation.

Auto-tuning can be carried out regardless of whether the Digital
Controller is performing reverse or normal operation. To stop auto-
tuning, hold down the Level Key and Mode Key again simultaneous-
ly for 1 second minimum. All settings will return to those prior to the
beginning of auto-tuning. Automatic tuning can be executed at any
time: at power application, while the temperature is rising, or after
the control action has stabilized.

Summary of Contents for E5AX-LA

Page 1: ...equipped with a terminal block to connect communications Specify a terminal block by adding X to the model number Example E5AX LA02 X Capable of transmitting the process value or output value but remo...

Page 2: ...ons character heights PV 15 mm and SV 11 mm Color PV red SV green Shift set input No voltage contact signal input set value shifted when ON Contact impedance 100 W max Other functions Upper and lower...

Page 3: ...0 ms Shift set 999 to 9999 Decimal point is displayed at set position Input shift 999 to 9999 Decimal point is displayed at set position Insulation resistance 20 MW min at 500 VDC Dielectric strength...

Page 4: ...e connected to one host computer using serial communications RS 422 RS 485 3 Outputs process value within the set limits Nomenclature Process Value PV Display Displays not only the process value but a...

Page 5: ...Output Unit is mounted Set the output selector to CUR current when a Current Output Unit is mounted To remove a Control Output Unit push it up with the tip of a flat blade screwdriver as shown below F...

Page 6: ...tion Pin number Pin setting Control setting Control mode 1 ON ON OFF operation OFF PID operation Control output 2 ON Normal OFF Reverse Input shift 3 ON Enabled OFF Disabled SP set point 4 ON Enabled...

Page 7: ...imit of a proportional band When the temperature rises to the upper limit of the proportional band point B in the figure the alarm output is turned ON This alarm function is convenient when the main s...

Page 8: ...disabled SW201 pin 6 ON Proportional Band p When the character p is displayed on the PV display the propor tional band P constant can be changed using the Up and Down Keys The new value will be displ...

Page 9: ...t shift 10 0 10 0 1 0 shifted by 1 0 10 0 11 0 1 0 shifted by 1 0 10 0 9 0 This function can be used mainly for fine tuning compensation while leaving the set value unaffected Select this function by...

Page 10: ...2 seconds so that the control operation can be performed more accurately Control output ON OFF 20 seconds When control period is set to 20 seconds Hysteresis hys The hysteresis value for the ON OFF co...

Page 11: ...ant control operations to be performed while setting parameters turn off the power and then turn it back on after setting the desired parameters Auto tuning When the Level Key and Mode Key are pressed...

Page 12: ...ed the input range OFF Approx 1 mA The output will turn ON ac cording to the alarm mode when the input goes to maximum except in the proportional alarm mode in which it will remain OFF e111 flashes e3...

Page 13: ...ons connector RS 232C and BCD connector is shown Communications board RS 422 and 485 terminals are shown Communications board 4 to 20 mA transmission output is shown 4 to 20 mA transmission output RS...

Page 14: ...ipment may prevent proper operation Attach the two mounting brackets supplied with E5AX on the top and bottom of the Digital Controller Tighten the screws of the mounting brackets with your fingers Mo...

Page 15: ...C are supplied with the Digital Controller Attach the proper stickers to the front panel as shown below allowing the input type and Control Output Unit mounted in the Digital Controller to be easi ly...

Reviews: