E5AX-LA/-MA

E5AX-LA/-MA

10

Decimal Point: 

dp

Set the position of the decimal point by pressing the Up and Down
Keys. A value between 0 and 3 will be displayed to indicate the posi-
tion of the decimal point as shown in the following table. The decimal
point is factory-set to 1.

Value of 

dp

Decimal point

0

1

0000

1

0.1

000.0

2

0.01

00.00

3

0.001

0.000

Scale Value for 0% Input: 

inl

Set the scale value for 0% input by pressing the Up and Down Keys.
The value can be set between –999 and 9998 in increments of 1 and
is factory-set to 0.0.

Scale Value for 100% Input: 

inh

Set the scale value for 100% input by pressing the Up and Down
Keys. The value can be set between –

inl

 +1 and 9999 in increments

of 1 and is factory-set to 100.0.

Example:
When measuring liquid flow between 100.0 and 510.5 m

3

/h using a

4 to 20 mA input.

1. The decimal point is set to “1.”

dp

1

PV

SV

a

2. The 0% scale value is set to the value to be displayed for 4

mA, i.e.,100.0.

inl

100.0

PV

SV

a

3. The 100% scale value is set to the value to be displayed for

20 mA, i.e.,510.5.

inh

510.5

PV

SV

a

Control Period: 

cp

Control period for PID control with feed-forward can be set. To set
the control period, pin 1 on the operating mode selector (SW201)
must be set to the OFF position. When 

cp

 is displayed on the PV dis-

play, the control period can be set or changed in a range from 1 to 99
seconds in units of 1 second. The factory setting is 20 seconds.
When a Voltage Output Unit is used, it is recommended that the con-
trol period be set to 20 seconds or less (ideally, about 2 seconds), so
that the control operation can be performed more accurately.

Control output

ON

OFF

20 seconds

When control period is
set to 20 seconds

Hysteresis: 

hys

The hysteresis value for the ON/OFF control can be set between
0.0% and 100.0% FS while 

hy5

 is displayed on the PV display using

the Up and Down Keys. The factory setting is 0.2% FS.

Reverse operation

Normal operation

SP

Hysteresis

Low

High

Hysteresis

SP

High

ON

OFF

ON

OFF

Low

Hysteresis Alarm: 

hysa

The hysteresis alarm value for the alarm 1 and 2 can be set between
0.0% and 100.0% FS while 

hy5

 is displayed on the PV display using

the Up and Down Keys. The factory setting is 0.1% FS.

Shift Set: 

sp–s

By short-circuiting the shift set input terminal, the control value is
shifted from the set value by the value input for the shift set. When

sp–s

  is displayed, the  Up and Down Keys can be pressed to set the

shift set between –999 and 9999.

Set
value

200

150

Shift set input
short-circuited

With a set value of
200 and a shift set
of –50

LED (SHIFT) is lit when a shift set input is short-circuited. 

sp–s

  is

factory-set to 0.

Level 2

In level 2 the control output value, selected input type, and modes
for alarm output can be monitored. Note that level 2 is a monitoring
level only and thus no parameters can be changed. When the Level
Key is pressed for 2 seconds minimum after power application, 

5l–l

is displayed on the PV display. Hold down the Level Key again for 2
seconds minimum to display 

o

 on the PV display. Then the control

output value, selected input sensor, and alarm modes can be moni-
tored each time the Display Key is pressed.

o

in–t

al–1

al–2

0

cur 1

–––C

–––C

Press 

a

.

Press 

a

.

Press 

a

.

Control output value

Alarm 1 mode

Press 

a

.

Alarm 2 mode

Input sensor

PV

SV

Summary of Contents for E5AX-LA

Page 1: ...equipped with a terminal block to connect communications Specify a terminal block by adding X to the model number Example E5AX LA02 X Capable of transmitting the process value or output value but remo...

Page 2: ...ons character heights PV 15 mm and SV 11 mm Color PV red SV green Shift set input No voltage contact signal input set value shifted when ON Contact impedance 100 W max Other functions Upper and lower...

Page 3: ...0 ms Shift set 999 to 9999 Decimal point is displayed at set position Input shift 999 to 9999 Decimal point is displayed at set position Insulation resistance 20 MW min at 500 VDC Dielectric strength...

Page 4: ...e connected to one host computer using serial communications RS 422 RS 485 3 Outputs process value within the set limits Nomenclature Process Value PV Display Displays not only the process value but a...

Page 5: ...Output Unit is mounted Set the output selector to CUR current when a Current Output Unit is mounted To remove a Control Output Unit push it up with the tip of a flat blade screwdriver as shown below F...

Page 6: ...tion Pin number Pin setting Control setting Control mode 1 ON ON OFF operation OFF PID operation Control output 2 ON Normal OFF Reverse Input shift 3 ON Enabled OFF Disabled SP set point 4 ON Enabled...

Page 7: ...imit of a proportional band When the temperature rises to the upper limit of the proportional band point B in the figure the alarm output is turned ON This alarm function is convenient when the main s...

Page 8: ...disabled SW201 pin 6 ON Proportional Band p When the character p is displayed on the PV display the propor tional band P constant can be changed using the Up and Down Keys The new value will be displ...

Page 9: ...t shift 10 0 10 0 1 0 shifted by 1 0 10 0 11 0 1 0 shifted by 1 0 10 0 9 0 This function can be used mainly for fine tuning compensation while leaving the set value unaffected Select this function by...

Page 10: ...2 seconds so that the control operation can be performed more accurately Control output ON OFF 20 seconds When control period is set to 20 seconds Hysteresis hys The hysteresis value for the ON OFF co...

Page 11: ...ant control operations to be performed while setting parameters turn off the power and then turn it back on after setting the desired parameters Auto tuning When the Level Key and Mode Key are pressed...

Page 12: ...ed the input range OFF Approx 1 mA The output will turn ON ac cording to the alarm mode when the input goes to maximum except in the proportional alarm mode in which it will remain OFF e111 flashes e3...

Page 13: ...ons connector RS 232C and BCD connector is shown Communications board RS 422 and 485 terminals are shown Communications board 4 to 20 mA transmission output is shown 4 to 20 mA transmission output RS...

Page 14: ...ipment may prevent proper operation Attach the two mounting brackets supplied with E5AX on the top and bottom of the Digital Controller Tighten the screws of the mounting brackets with your fingers Mo...

Page 15: ...C are supplied with the Digital Controller Attach the proper stickers to the front panel as shown below allowing the input type and Control Output Unit mounted in the Digital Controller to be easi ly...

Reviews: