E5AX-LA/-MA

E5AX-LA/-MA

14

Installation

For relay
output

For
SSR
output

For current
output

Control

output

Alarm output 1

Shift set input

Alarm output 2

4 to 20 mA

Note

:

Do not connect unused terminals.

100 to 240 VAC, 50/60 Hz

Ground FG terminal 18 under
noise-interfered environment

For 1 to 5 V,
0 to 5 V, 0 to 1 V

For 4 to 20 mA,
0 to 20 mA

For 0 to 100 mV

For 0 to 10 mV
–10 to 10 mV

E5AX-LA

E5AX-MA

For voltage
output

Precautions

Mounting

The dimensions of the Digital Controller conform to DIN 43700.
Recommended panel thickness is 1 to 8 mm.

Do not install the Digital Controller in a location exposed to exces-
sive dust or corrosive gases. Moreover, avoid locations subject to
heavy vibration or shock, water or oil spray, or high temperatures.
Any of these condition will affect product life.

Isolate the Digital Controller from equipment that generates strong,
high-frequency noises such as high-frequency welders, because
such equipment may prevent proper operation.

Attach the two mounting brackets supplied with E5AX on the top
and bottom of the Digital Controller. Tighten the screws of the
mounting brackets with your fingers.

Mounting bracket

Connection Examples

With Solderless Terminal

Use M3.5 solderless terminals with the Digital Controller’s M3.5
self-rising pressure plate screws.

Solder-dipped Leads

Strip 6 to 12 mm of the lead wires and carefully arrange the wire tips.
Do not tighten the terminal screw with excessive force, because do-
ing so may damage them. The terminal block of the Digital Control-
ler is constructed so that the lead wires can be connected to all the
terminals from the same direction.

Top

Bottom

Input Connection

To reduce inductive noise influence, the lead wires connecting the
input to the Digital Controller must be separated from the power
lines and load lines.

Sequenced Circuits

Several seconds are required until the relay in turned ON after pow-
er has been supplied to the Digital Controller. Therefore, take this
time delay into consideration when designing sequenced circuits
which incorporate a Digital Controller.

Summary of Contents for E5AX-LA

Page 1: ...equipped with a terminal block to connect communications Specify a terminal block by adding X to the model number Example E5AX LA02 X Capable of transmitting the process value or output value but remo...

Page 2: ...ons character heights PV 15 mm and SV 11 mm Color PV red SV green Shift set input No voltage contact signal input set value shifted when ON Contact impedance 100 W max Other functions Upper and lower...

Page 3: ...0 ms Shift set 999 to 9999 Decimal point is displayed at set position Input shift 999 to 9999 Decimal point is displayed at set position Insulation resistance 20 MW min at 500 VDC Dielectric strength...

Page 4: ...e connected to one host computer using serial communications RS 422 RS 485 3 Outputs process value within the set limits Nomenclature Process Value PV Display Displays not only the process value but a...

Page 5: ...Output Unit is mounted Set the output selector to CUR current when a Current Output Unit is mounted To remove a Control Output Unit push it up with the tip of a flat blade screwdriver as shown below F...

Page 6: ...tion Pin number Pin setting Control setting Control mode 1 ON ON OFF operation OFF PID operation Control output 2 ON Normal OFF Reverse Input shift 3 ON Enabled OFF Disabled SP set point 4 ON Enabled...

Page 7: ...imit of a proportional band When the temperature rises to the upper limit of the proportional band point B in the figure the alarm output is turned ON This alarm function is convenient when the main s...

Page 8: ...disabled SW201 pin 6 ON Proportional Band p When the character p is displayed on the PV display the propor tional band P constant can be changed using the Up and Down Keys The new value will be displ...

Page 9: ...t shift 10 0 10 0 1 0 shifted by 1 0 10 0 11 0 1 0 shifted by 1 0 10 0 9 0 This function can be used mainly for fine tuning compensation while leaving the set value unaffected Select this function by...

Page 10: ...2 seconds so that the control operation can be performed more accurately Control output ON OFF 20 seconds When control period is set to 20 seconds Hysteresis hys The hysteresis value for the ON OFF co...

Page 11: ...ant control operations to be performed while setting parameters turn off the power and then turn it back on after setting the desired parameters Auto tuning When the Level Key and Mode Key are pressed...

Page 12: ...ed the input range OFF Approx 1 mA The output will turn ON ac cording to the alarm mode when the input goes to maximum except in the proportional alarm mode in which it will remain OFF e111 flashes e3...

Page 13: ...ons connector RS 232C and BCD connector is shown Communications board RS 422 and 485 terminals are shown Communications board 4 to 20 mA transmission output is shown 4 to 20 mA transmission output RS...

Page 14: ...ipment may prevent proper operation Attach the two mounting brackets supplied with E5AX on the top and bottom of the Digital Controller Tighten the screws of the mounting brackets with your fingers Mo...

Page 15: ...C are supplied with the Digital Controller Attach the proper stickers to the front panel as shown below allowing the input type and Control Output Unit mounted in the Digital Controller to be easi ly...

Reviews: