Teaching With and Without Target Object (Located within Certain Range)
Step 1
Status of target object
Control panel
Indicators
(Excess gain level indicators)
Set the operation
mode selector to T.
Press the TEACH
button after locat-
ing the target
object at one edge
of the sensing
range.
Sensor Head
Sensing object at
a certain position
TEACH button
Sensor
Head side
ON
OK
Step 2
Status of target object
Control panel
Indicators
(Excess gain level indicators)
If all the indicators
flash, repeat from
step 1. Or, change
the Sensor Head
position or set the
resolution selector
to FINE and then
repeat from step 1.
Press the TEACH
button after locating
the other sensing
level in front of the
sensing surface.
Sensor Head
Sensing object at
a certain position
TEACH button
Sensor
Head side
Flashing
No good
Sensor
Head side
ON
OK
Step 3
Sensitivity setting
position
Control panel
Indicators
(Excess gain level indicators)
Set the operation
mode selector to
RUN.
Sensor Head
ON point
The ON point is located in
the middle of the edges.
Operation mode selector
OFF after the
indicators are
ON for 1 s.
Sensor
Head side
OK
Note: 1. The threshold level can be set to the same position by locating the target object at either one of the edges of the sensing range
when performing steps 1 and 2.
2. After setting the mode to RUN, confirm that all eight excess gain level indicators are ON.