142
Service Code
For normal completion, the value when the left-most bit of the service code
specified in the command turns ON is stored as shown in the following table.
/i
When an error response is returned for an explicit message, the value is
always 94 Hex.
Data
Read data is included only when a read command is executed.
Error Codes
The explicit message error codes as listed in the following table.
/i
Function
Command service code
Response service code
Write data
10 Hex
90 Hex
Read data
0E Hex
8E Hex
Reset
05 Hex
85 Hex
Save
16 Hex
96 Hex
Response
code
Error name
Cause
08FF
Service not supported
The Service code is incorrect.
09FF
Invalid Attribute value
The specified Attribute value is not supported.
The data written was outside valid range.
16FF
Object does not exist
The specified Instance ID is not supported.
15FF
Too much data
The data is larger than the specified size.
13FF
Not enough data
The data is smaller than the specified size.
0CFF
Object state conflict
The specified command cannot be executed
due to an internal error.
20FF
Invalid parameter
The specified operation command data is not
supported.
0EFF
Attribute not settable
An Attribute ID supported only for reading has
been executed for a write service code.
10FF
Device state conflict
The specified command cannot be executed
due to an internal error.
14FF
Attribute not supported
The specified Attribute is not supported.
19FF
Store operation failure
The data cannot be stored in memory.
2AFF
Group 2 only server
general failure
The specified command or Attribute is not
supported or the Attribute was not set.
Summary of Contents for CJ1W-CRM21
Page 1: ...CJ1W PNT21 PROFINET IO Controller Unit OPERATION MANUAL Cat No W12E EN 02 ...
Page 2: ......
Page 7: ...vii ...
Page 16: ......
Page 26: ...Basic operating procedure Section 2 4 10 ...
Page 46: ...Installation of Configuration Software Section 3 5 30 ...
Page 76: ...Generic IO Device DTM Section 4 4 60 ...
Page 156: ...140 ...
Page 164: ...146 ...
Page 168: ...150 ...
Page 170: ...Section 152 ...