4
DIP Switch Settings
Manual start mode
In this mode, the BASIC program is
not started upon power application.
To start the program, either press
the START/STOP switch or issue a
start command from the personal
computer connected to port 1.
OFF
ON
: 0
: 1
1 2 3 4 5 6 7 8
Start mode
Pin No.
1
Function
Setting
0
1
Automatic start mode
In this mode, the BASIC program
is started automatically on power
application.
Automatic program transfer from EEPROM to RAM
Pin No.
Function
Set this pin to “0” if only the
RAM is to be used.
2
Set this pin to “1” to automati-
cally transfer the program
from the EEPROM to RAM on
power application or reset.
0
1
Setting
Program No.
Pin No.
Function
3
4
0
0
1
0
0
1
1
1
No. 1
No. 2
No. 3
Setting
Screen size
Pin No.
Screen Size
Setting
40 columns x 7 lines
40 columns x 8 lines
40 columns x 15 lines
40 columns x 16 lines
80 columns x 16 lines
80 columns x 15 lines
80 columns x 24 lines
80 columns x 25 lines
6
7
8
0
0
0
1
1
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
1
These pins select which program will be executed on power
application or reset. The program number can be changed
later with the PGEN command.
Specifies 2 or 4 word setting for
the Data Section.
Pin No.
Function
5
0
1
Setting
Two word setting. Choose this setting
to use WRIT(87/191)/READ(88/190)
Four word setting. This setting is used
when the ASCII Unit is mounted to a
Slave Rack or when the PC does not
support WRIT(87/191)/READ(88/190).
Front Panel