10
< I/O Units and CPU Bus Units>
Unit name
C200H-series Unit
CS1-series Unit
Description
Communication Unit
[SYSMAC BUS]
Wired: C200H-RM201
Optical: C200H-RM001-PV1
[SYSMAC BUS]
Wired: C200H-RM201
Optical:
C200H-RM001-PV1
[CompoNet]
CS1W-CRM21
[DeviceNet]
CS1W-DRM21-V1
[CompoBus/S]
CS1W-SRM21
SYSMAC BUS can be used with the
CS1-series CPU Unit. However, area
allocation must be changed.
To improve the system performance and to
facilitate maintenance, we recommend you
to use left networks instead.
Refer to the
CS/CJ series CompoNet Master
Units OPERATION MANUAL
(Cat. No.
W456) and
CompoNet Slave Units and
Repeater Unit OPERATION MANUAL
(Cat.
No. W457) for details of CompoNet.
Refer to the
CS1W-DRM21(-V1),CJ1W-DRM21 CS/CJ
SERIES DeviceNet UNITS OPERATION
MANUAL
(Cat. No. W380) for details of
DeviceNet.
Refer to the
C200HW/CS1W/CJ1W/CQM1/SRT1/SRT2
CompoBus/S OPERATION MANUAL
(Cat.
No. W266) for details of CompoBus/S.
< Support Software and Peripheral Devices >
Unit name
C200H-series Unit
CS1-series Unit
Description
Support Software
SYSMAC C-series Ladder
Support Software
C500-SF610-V6 (5 inches)
C500-SF410-V6 (3.5 inches)
CX-Programmer
CX-One
CXONE-AL
□□C-V□/AL□□D-
V
□
(CX-Programmer Ver3.0 or
higher)
SYSMAC Support Software cannot be used
with the CS1-series CPU Unit.
Peripheral Interface
Unit, Connecting Cable
CQM1-CIF02
CS1W-CN226/626
Programming Console
C200H-PRO27
(+C200H-CN222/422)
(+C200HS-CN222/422)
CQM1-PRO01
(+C200HS-CN222 attached)
C200H-PRO27
(+CS1W-CN
□□4)
CQM1-PRO01
(+CS1W-CN114)
CS1W-CN
□□4 is a Programming Console
Connecting Cable.
A cassette interface cannot be used.
Other remarks
(1) The CS1-series CPU Unit is separated from the Power Supply Unit although the C200HS-series CPU Unit
is combined with the Power Supply Unit. The two series use different CPU Backplanes. However, the
mounting hole positions are the same.
(2) The PFP-50N/100N/100N2 DIN Track and C200H-DIN01 Mounting Bracket can be used for the CS1-series
Backplane.
(3) The CS1-series Backplane has an installation structure to be insulated from the control panel. The
C200HW-ATT31/51/81/A1 Insulation Plate for CPU Backplane is not required.
(4) The I/O Unit Mounting Bracket cannot be used with the CS1-series Backplane. CS1-series Units can be
secured with screws. They do not require brackets.