![Omron C200HE-CPU -Z Series Installation Manual Download Page 59](http://html1.mh-extra.com/html/omron/c200he-cpu-z-series/c200he-cpu-z-series_installation-manual_742479059.webp)
44
DeviceNet Systems
The DeviceNet is an I/O data communications system conforming to the Device-
Net standard being developed to standardize device-level networks for FA.
DeviceNet Master Unit
CQM1 (I/O Link Unit)
I/O Terminal
Adapter
Sensor Terminal
Analog Input Terminal
Analog Output Terminal
•
The DeviceNet Master Unit is mounted to the CPU Rack or an Expansion I/O
Rack. Only one Master Units can be mounted.
•
Up to 50 slaves can be connected for a maximum of 1,600 points of I/O data
communications (50 input words and 50 output words).
•
The IR Area is used for data transmissions (outputs: IR 50 to IR 99; inputs: IR
350 to IR 399).
•
A wide variety of slaves are available to support relay, sensor, analog and other
I/O.
Note
1. The DeviceNet System cannot be used at the same time as a Remote I/O
System.
2. The DeviceNet Master Units must be counted as Special I/O Units.
3. Slaves made by other manufacturers can be connected as long as they con-
form to the DeviceNet standard.
Expanded System Configurations
Section 2-4