![Omron C200HE-CPU -Z Series Installation Manual Download Page 164](http://html1.mh-extra.com/html/omron/c200he-cpu-z-series/c200he-cpu-z-series_installation-manual_742479164.webp)
Appendix B
Specifications
149
Triac Output Unit C200H-OA221
Max. Switching Capacity
1 A 250 VAC, 50/60 Hz (4 A/Unit)
Min. Switching Capacity
10 mA (resistive load)/40 mA (inductive load) 10
VAC
Leakage Current
3 mA (100 VAC) max./6 mA (200 VAC) max.
Residual Voltage
1.2 V max.
ON Response Time
1 ms max.
OFF Response Time
1/2 of load frequency or less.
No. of Circuits
1 (8 points/common)
Internal Current Consumption
140 mA 5 VDC max.
Fuse Rating
5 A 250 V (5.2-dia.x20)
Power for External Supply
N/A
Weight
250 g max.
Dimensions
A-shape
Circuit Configuration
Internal
Circuit
L
OUT
COM
OUT
Output indicator
L
250 VAC max.
F indicator
Fuse: 5 A 250 V (5.2-dia.x20) MF51SH (JIS)
Fuse blowout
detection circuit
Fuse
Note When the fuse blows, the F indicator lights and bit 08 turns ON. Bits 08 through 15 cannot be used as IR bits.
Terminal Connections
A0
A1
A2
A3
A4
A5
A6
A7
A8
A9
0
1
2
3
4
5
6
7
L
L
L
L
L
L
L
L
COM
250 VAC max
(1 A max. 4 A/Unit)
NC