Appendix B
Specifications
152
Triac Output Unit C200H-OA224
Max. Switching Capacity
0.5 A 250 VAC, 50/60 Hz (2 A/Unit)
Max. inrush current
10 A (pulse width: 100ms)
20 A (pulse width: 10 ms)
Min. Switching Capacity
100 mA 10 VAC/50 mA 24 VAC/10 mA 100 VAC
min.
Leakage Current
1.5 mA (120 VAC) max./3 mA (240 VAC) max.
Residual Voltage
1.5 VAC max. (50 to 500 mA)/5 VAC max. (10 to
50 mA)
ON Response Time
1 ms max.
OFF Response Time
1/2 of load fre 1 ms or less.
No. of Circuits
1 (12 points/common)
Internal Current Consumption
270 mA 5 VDC max.
Fuse Rating
3.15 A 250 V (5.2-dia.x20)
Power for External Supply
N/A
Weight
300 g max.
Dimensions
B-shape
Circuit Configuration
L
Internal
Circuit
OUT
COM
OUT
Output indicator
L
250 VAC max.
Fuse: 3.15 A 250 V (5.2-dia.x20) MT4 (SOC)
Fuse
Note 1. No blown fuse detector circuit is provided.
2. Check the fuse when there is no output.
Terminal Connections
A0
A1
A2
A3
A4
A5
A6
A7
A8
B0
B1
B2
B3
B4
B5
B6
B7
B8
B9
COM
1
3
5
7
9
11
NC
0
2
4
6
8
10
NC
NC
NC
NC
250 VAC max.
(0.5 A max., 2 A/Unit)
L
L
L
L
L
L
L
L
L
L
L
L
NC