Page 9

DC Power

This module is intended for installation in restricted access areas. (“Les matériels 

sont destinés à être installés dans des EMPLACEMENTS À ACCÈS RESTREINT”). 

A restricted access area can be accessed only through the use of a special key, or 

other means of security.
The over current protection for connection with centralized DC shall be provided in 

the building installation, and shall be a UL listed circuit breaker rated 20 Amps, and 

installed per the National Electrical Code, ANSI/NFPA-70.

The DC power requirements for each port configuration is outlined in the table below.  

Voltage ranges are inclusive of tolerances.

1 RJ-45 Port

+12 to +57VDC; 0.19A @ 56VDC
2 Pin Terminal 

2 RJ-45 Ports

+12 to +57VDC; 0.25A @ 56VDC
2 Pin Terminal 

Appropriate overloading protection should be provided on the DC power source 

outlets utilized.

DC Models Rear View: 2-Pin Terminal for DC Power

WARNING REGARDING EARTHING GROUND:

o

o

o

o

This equipment shall be connected to the DC supply

system earthing electrode conductor or to a bonding
jumper from an earthing terminal bar or bus to which the
DC supply system earthing electrode is connected.

This equipment shall be located in the same immediate

area (such as adjacent cabinets) as any other equipment
that has a connection between the earthed conductor of
the same DC supply circuit and the earthing conductor,
and also the point of earthing of the DC system. The DC
system shall not be earthed elsewhere.

The DC supply source is to be located within the same

premises as this equipment.

There shall be no switching or disconnecting devices in

the earthed circuit conductor between the DC source and
the earthing electrode conductor.

WARNING: Only a DC power source that complies with
safety extra low voltage (SELV) requirements can be
connected to the DC-input power supply.

Page 10

Locate the DC circuit breaker of the external power source, and switch the circuit 

breaker to the OFF position.
Prepare a power cable using a three conductor insulated wire (not supplied) with 

12AWG to 14AWG thickness.  Cut the power cable to the length required.
Strip approximately 3/8 of an inch of insulation from the power cable wires.
Connect the ground wire to the grounding screws on the back of the module.
Connect the power cables to the module by fastening the stripped ends to the DC 

power connector.

DC Models Rear View: Power Connections

WARNING:  The positive lead of the power source must be connected to the 

“+” terminal on the module and the negative lead of the power source to the 

“-“ terminal on the module as shown above. 

Power Options

WARNING: Note the wire colors used in making the positive, negative and 

ground connections. Use the same color assignment for the connection at 

the circuit breaker.

Connect the power wires to the circuit breaker and switch the circuit breaker ON. 

If any module are installed, the Power LED will indicate the presence of power.
During the installation, ensure that the ground potentials are maintained throughout 

the system connections.  This includes but not limited to the power source ground 

and any shielded cabling grounds.

NEVER ATTEMPT TO OPEN THE CHASSIS OR

SERVICE THE POWER SUPPLY. OPENING THE

CHASSIS MAY CAUSE SERIOUS INJURY OR DEATH.

THERE ARE NO USER REPLACEABLE OR

SERVICEABLE PARTS IN THIS UNIT.

WARNING!!!

Make sure to disconnect the power and ground cables before removing the 

equipment.

Summary of Contents for OmniConverter 10G

Page 1: ...ter can be extended to five 5 years by registering the product at www omnitron systems com support within ninety 90 days from the date of shipment During the warranty period Omnitron will at its optio...

Page 2: ...nter problems while installing this product contact Omnitron Technical Support Phone 949 250 6510 Fax 949 250 6514 Address Omnitron Systems Technology Inc 38 Tesla Irvine CA 92618 USA Email support om...

Page 3: ...media converter Please refer to the table above for the port configuration Page 6 SW1 Mode Of Operation Normal Directed This DIP switch is only supported on models with 2 RJ 45 ports The module suppor...

Page 4: ...040 08250 001x or 040 08251 001x for the proper installation guidelines Page 8 3 Apply Power AC Power Secure the ground wire to the ground screw See the figure below for the location of the grounding...

Page 5: ...s in the earthed circuit conductor between the DC source and the earthing electrode conductor WARNING Only a DC power source that complies with safety extra low voltage SELV requirements can be connec...

Page 6: ...ps 100Mbps 1Gbps 2 5Gbps 5Gbps and 10Gbps 5 Verify Operation Verify the module is operational by viewing the LED indicators Power LED Indicators Legend Indicator Description Pwr OFF Unit not powered G...

Page 7: ...Only 1 1 lbs 498 9 grams Module w Adapter 1 6 lbs 725 7 grams Operating Temperature Commercial 0 to 50 C Wide 40 to 60 C 20 C AC cold start Storage 40 to 80 C Humidity 5 to 95 non condensing Altitude...

Page 8: ...Mechanical Page 15 Page 16...

Reviews: