Input 8 High-High Limit
65
Input 8 High Limit
66
Input 8 Low Limit
67
Input 8 Low-Low Limit
68
Input 8 Deadband
69
7.17 M1433B
– 6RTD ISO – 6 way Isolated Resistance Bulb Input Module
ANALOGUE INPUT DATA SPACE
DIT (Offset)
Analogue Input 1
0
Analogue Input 2
1
Analogue Input 3
2
Analogue Input 4
3
Analogue Input 5
4
Analogue Input 6
5
Analogue Data is read as a signed integer as specified in the “Temperature Scale” configuration
register.
DIGITAL INPUT DATA SPACE
DIT (Offset)
Digital Inputs 1-16
where individual inputs are allocated as follows:
0
Bit 0: Input 1 >= High Limit
Bit 1: Input 1 >= High-High Limit
Bit 2: Input 1 <= Low Limit
Bit 3: Input 1 <= Low-Low Limit
Bit 4: Input 1 Calibration Error
Bit 5: Input 1 Configuration Corrupted
Bit 6: Input 1 Incorrect Input Type
Bit 7: Unused (will read as 0)
Bit 8: Input 2 >= High Limit
Bit 9: Input 2 >= High-High Limit
Bit 10: Input 2 <= Low Limit
Bit 11: Input 2 <= Low-Low Limit
Bit 12: Input 2 Calibration Error
Bit 13: Input 2 Configuration Corrupted
Bit 14: Input 2 Incorrect Input Type
Bit 15: Unused (will read as 0)
Digital Inputs 17-32
where individual inputs are allocated as follows:
1
Bit 0: Input 3 >= High Limit
Bit 1: Input 3 >= High-High Limit
Bit 2: Input 3 <= Low Limit
Bit 3: Input 3 <= Low-Low Limit
Bit 4: Input 3 Calibration Error
Bit 5: Input 3 Configuration Corrupted
Bit 6: Input 3 Incorrect Input Type
Bit 7: Unused (will read as 0)
Bit 8: Input 4 >= High Limit
Bit 9: Input 4 >= High-High Limit
Bit 10: Input 4 <= Low Limit
Bit 11: Input 4 <= Low-Low Limit
Bit 12: Input 4 Calibration Error
Bit 13: Input 4 Configuration Corrupted
Bit 14: Input 4 Incorrect Input Type
Bit 15: Unused (will read as 0)
Digital Inputs 33-48
where individual inputs are allocated as follows:
2
Bit 0: Input 5 >= High Limit
Bit 1: Input 5 >= High-High Limit
Bit 2: Input 5 <= Low Limit
Bit 3: Input 5 <= Low-Low Limit
Bit 4: Input 5 Calibration Error
Bit 5: Input 5 Configuration Corrupted
Bit 6: Input 5 Incorrect Input Type
Bit 7: Unused (will read as 0)
Bit 8: Input 6 >= High Limit
Bit 9: Input 6 >= High-High Limit
Bit 10: Input 6 <= Low Limit
Bit 11: Input 6 <= Low-Low Limit
Bit 12: Input 6 Calibration Error
Bit 13: Input 6 Configuration Corrupted
Bit 14: Input 6 Incorrect Input Type
Bit 15: Unused (will read as 0)