Maxiflex P3 PAC User Manual
42
-© Omniflex
UMM126XR18.pdf
7.11 M1342A
– 32DO – 32way Digital Output Module
DIGITAL OUTPUT DATA SPACE
DIT (Offset)
Digital Outputs 1-16
where individual outputs are allocated as follows:
0
Output 1 = Bit 0 (LSB)
Output 2 = Bit 1
Output 3 = Bit 2
Output 4 = Bit 3
Output 5 = Bit 4
Output 6 = Bit 5
Output 7 = Bit 6
Output 8 = Bit 7
Output 9 = Bit 8
Output 10 = Bit 9
Output 11 = Bit 10
Output 12 = Bit 11
Output 13 = Bit 12
Output 14 = Bit 13
Output 15 = Bit 14
Output 16 = Bit 15 (MSB)
Digital Outputs 17-32
where individual outputs are allocated as follows:
1
Output 17 = Bit 0 (LSB)
Output 18 = Bit 1
Output 19 = Bit 2
Output 20 = Bit 3
Output 21 = Bit 4
Output 22 = Bit 5
Output 23 = Bit 6
Output 24 = Bit 7
Output 25 = Bit 8
Output 26 = Bit 9
Output 27 = Bit 10
Output 28 = Bit 11
Output 29 = Bit 12
Output 30 = Bit 13
Output 31 = Bit 14
Output 32 = Bit 15 (MSB)
All other Data Spaces are unused by this module
Example:
Output 23 of an M1342A module installed in Local Slot 4 can be energised by writing to DIT
Address 4517, Bit 6
7.12 M1372A
– 8RO – 8way Relay Output Module
DIGITAL OUTPUT DATA SPACE
DIT (Offset)
Digital Outputs 1-8
where individual outputs are allocated as follows:
0
Output 1 = Bit 0 (LSB)
Output 2 = Bit 1
Output 3 = Bit 2
Output 4 = Bit 3
Output 5 = Bit 4
Output 6 = Bit 5
Output 7 = Bit 6
Output 8 = Bit 7
Other bits are unused
All other Data Spaces are unused by this module
Example:
Output 1 of an M1372A module installed in Local Slot 1 can be energised by writing to DIT
Address 4504, Bit 0.