background image

13 | 

M 5 7 7 9

5.3.4

 

    Advanced Scaling Options 

The Layer N SP-006 allows for advanced scaling options on the pressure and temperature inputs.

 

The 

Advanced Scaling

 checkbox can be selected to expand additional configuration options. A gain and/or offset 

can be applied to the input reading and the displayed unit can be changed. 

To apply a gain or offset to the input, expand the 

Advanced

 

Scaling

 menu and ensure that both 

Apply 

Scaling

 and 

Lock

 are checked. Under Scaling, the gain and offset values can be adjusted. Both positive and 

negative values may be entered as well as decimal numbers. The equation for the scaled input value is given 

below.

 

𝑰𝑰𝑰𝑰𝑰𝑰𝑰𝑰𝑰𝑰

𝑺𝑺𝑺𝑺𝑺𝑺𝑺𝑺𝑺𝑺𝑺𝑺

= (

𝑰𝑰𝑰𝑰𝑰𝑰𝑰𝑰𝑰𝑰

𝑹𝑹𝑺𝑺𝑹𝑹

×

𝑮𝑮𝑺𝑺𝑮𝑮𝑰𝑰

) +

𝑶𝑶𝑶𝑶𝑶𝑶𝑶𝑶𝑺𝑺𝑰𝑰

 

The displayed units can be changed by entering a new value in the 

Unit

 field and clicking 

Apply Settings

. This 

field is limited to a maximum of 4 characters. Note that changing the Unit field does not change the base 

unit type, only the display name. The 

Lock

 checkbox must be selected to use the user-defined Unit field. 

Unchecking the Lock checkbox and clicking Apply Settings will revert the unit display back to the default 

setting. 

5.4

 

Output Configuration 

The SP-006 offers two discrete outputs that share circuitry with the discrete inputs. If an output is to be used then 

the corresponding input pin must be set to 

Disable

. See section 

5.3.3 Discrete Input/Output (DIO)

 for more 

information. 

There are three types of output options – On/Off, Pulse-Width Modulation (PWM), or Servo. See section 

5.4.1

 for 

more information on each type. 

Outputs may be configured as either Active High or Active Low. When configured as Active High the output 

conducts normally and becomes high impedance when activated. When configured as Active Low, the Open-Drain 

output is high impedance normally and will conduct when activated.  

Option 

Value 

Description 

Active 

LOW 

When the output is inactive, it is in a high impedance state. 

HIGH 

When the output is active, it is in a high impedance state. 

Figure 13: SYNC interface SP-006 DIO_0 and DIO_1 set to Disable 

Figure 14: SYNC interface Output Configuration 

Summary of Contents for SP-006

Page 1: ...1 M 5 7 7 9 TM User sGuide Shop online at omega com e mail info omega com For latest product manuals www omegamanual info SP 006 Layer N Pressure Monitoring and Control Smart Probe...

Page 2: ...6 USA Canada only U S A Headquarters Tel 203 359 1660 e mail info omega com Fax 203 359 7700 The information contained in this document is believed to be correct but OMEGA accepts no liability for any...

Page 3: ...r Output Mapping 15 5 4 3 ON OFF Control Module 17 5 4 4 Setting an Alarm 18 6 Appendix SP 006 Registers 19 6 1 Register Base Addresses 19 6 2 Pressure Sensor 19 6 2 1 Pressure Descriptor 19 6 2 1 1 P...

Page 4: ...Configuration 26 6 4 2 DIO IPSO Definition 27 6 4 2 1 Sensor Trigger Function 27 6 5 Output Configuration Registers 27 6 5 1 Scaling Minimum Maximum Values 28 6 5 2 Output Values 28 6 5 3 Output Names...

Page 5: ...s device as it contains important information relating to safety and EMC Failure to follow all the safety precautions may result in injury and or damage to the equipment The following labels identify...

Page 6: ...autonomous independent decision making capabilities to generate local alarms or provide control outputs based on sensor inputs The optional M12 8 T SPLIT Sensor Splitter can be used to access the Dis...

Page 7: ...on 0 1 kPa Absolute Maximum Pressure 1 5 time full scale for each range Caution Do not exceed 500 psi TEMPERATURE Range 10 to 80 C 14 to 176 F Accuracy 1 5 C Resolution 0 1 C ENVIRONMENTAL Storage Tem...

Page 8: ...t i e ordering code C Inquire with Omega Engineering for other pressure port options Refer to Figure 3 4 Hardware Setup 4 1 Connecting your Layer N Smart Interface The SP 006 requires a Layer N Smart...

Page 9: ...End Device Probe 5 2 1 Communication Interface Set the communication parameters for the Layer N Smart Interface that you are connecting Note The connection type and parameters must be accurate for a...

Page 10: ...s for your device click Finish 5 3 Input Configuration The SP 006 provides readings for pressure temperature and discrete I O DIO To use these features click the Inputs configuration tab on SYNC and c...

Page 11: ...the user must follow the onscreen directions to calibrate the device Figure 8 SYNC pressure user calibration 5 3 2 Temperature The SP 006 Temperature readings may be configured under the advanced sca...

Page 12: ...ol signal to turn on the output driver which will force the output low When the state of the DIO input signal is to be read the processor applies 3 3 VDC to the Input Bias signal and reads the level d...

Page 13: ...must be selected to use the user defined Unit field Unchecking the Lock checkbox and clicking Apply Settings will revert the unit display back to the default setting 5 4 Output Configuration The SP 0...

Page 14: ...ses of a discrete signal PWM consists of a duty cycle and frequency The Duty Cycle measures the amount of time a signal is in the ON state as a percentage The frequency controls how fast the PWM cycle...

Page 15: ...varies between 0 5 and 2 5 msec Example For the percent of angular travel if the pulse width range is set to a range of 1 0 2 0 msec then an output of 50 of angular travel represents 1 5 msec or 90 d...

Page 16: ...output direct mapped to a Rate input The minimum expected input rate is 25 Hz and the maximum expected rate is 150 Hz A value of 50 Hz read at the input is then mapped to a PWM output with an 80 duty...

Page 17: ...the chosen Input The Control Actions dropdown has options for direct or reverse control In direct mode once the Setpoint value is reached then the output will be set to ON In reverse mode once the Se...

Page 18: ...transmit or not transmit a notification can be set The option to enable Turn On an output can also be set The output chosen must not be currently used in a sensor mapping or ON OFF control module The...

Page 19: ...responding sensor values Additional sensor information is provided in sensor specific IPSO object descriptions which include extended measurement type precision and tracking of minimum maximum reading...

Page 20: ...values may not be overwritten 6 2 1 3 Temperature Configuration Byte Pressure Sensor Configuration 7 6 5 4 3 2 1 0 Available Assigned Channel Apply Scaling Lock Sensor Range Type 0 0 Read Only Indica...

Page 21: ...Calibrate mode When the calibration function is triggered the device will calculate the Gain and Offset used in the linearization process The calibration process is performed by the following steps 1...

Page 22: ...s IPSO object type information Offset Name Value Description 0x00 Sensor Type 3323 Pressure kPa 0x02 Precision 1 Provides reading of xxx y kPa 0x04 Sensor Trigger Write any value to force a reset of m...

Page 23: ...he overall function of the channel and the signal types used Offset Name Value Description 0x00 Measurement Type 0x01 Temperature in C 0x01 Data Type Format 0x06 Float type 0x02 Configuration Byte See...

Page 24: ...e Smart Sensor Device Interface documentation for further information 6 3 1 4 Temperature Device Byte The Temperature Device Byte is not used 6 3 2 Temperature Parameters There are no user accessible...

Page 25: ...used to detect the state of external switches output off or to monitor the state of the outputs 6 4 1 DIO Descriptor Offset Name Value Description 0x00 Sensor Type 0x18 Digital Type Bit mapped 0x01 Da...

Page 26: ...will be used to adjust the sensor reading Result Raw Reading Gain Offset 6 4 1 3 3 Assigned The Assigned bit will always read as 0 Refer to the Smart Sensor Device Interface documentation for further...

Page 27: ...er Function 7 6 5 4 3 2 1 0 0 0 0 0 0 0 0 Reset Min Max 15 14 13 12 11 10 9 8 0 0 0 0 0 0 0 0 Setting the Reset Min Max bit to 1 will reset the Min Max values recorded by the IPSO process No User Cali...

Page 28: ...e output is mapped the scaling values are used to transform the minimum input value to 0 and the maximum input value to 100 Output Name Modbus Address I2C Address Size Description 0 Output 0 Value 0xf...

Page 29: ...sor 2 1 1 0 Sensor 3 1 1 1 Mapping Enable Not Enabled 0 Enabled 1 Output Type Null 0 0 0 0 ON OFF 0 0 0 1 PWM 0 0 1 0 Servo 0 0 1 1 6 6 1 Rate The Rate determines the repetition rate or frequency of t...

Page 30: ...y Mapping Enabled bit indicates that the output may be optionally directly mapped to a sensor input based on the Sensor Mapping field If the Mapping Enabled bit is clear no mapping is supported and th...

Page 31: ...A if the unit is found to be defective it will be repaired or replaced at no charge OMEGA s WARRANTY does not apply to defects resulting from any action of the purchaser including but not limited to m...

Page 32: ...s M U Turbine Paddlewheel Systems M U Totalizers Batch Controllers pH CONDUCTIVITY M U pH Electrodes Testers Accessories M U Benchtop Laboratory Meters M U Controllers Calibrators Simulators Pumps M U...

Reviews: