background image

17 | 

M 5 7 7 9

5.4.3

 

    ON/OFF Control Module 

To configure an ON/OFF control module on a device, first ensure that the desired output pin is not 

associated with any input alarms and that it is set as 

No Mapping

 in the Output Mapping menu in the 

Outputs

 tab. The ON/OFF control module can be used with any selected output type including ON/OFF, 

PWM, and SERVO. When enabled in PWM mode, ON corresponds to 100% duty cycle. When enabled in 

SERVO mode, ON corresponds to 100% angular travel. 

In the 

Outputs Tab

 in SYNC click on the 

  icon located to the right of the available outputs. Clicking the 

icon will open the 

Define ON/OFF Control

 dialog box as seen below. 

The 

Enable Control

 checkbox enables the ON/OFF control module. If this box is unchecked, the output will 

be disabled but the module with all its settings will remain available to be enabled at a later time. 

The 

Inputs

 dropdown lists the available input sources and will depend on how the device is configured in the 

Inputs tab. 

The 

Setpoint

 field sets the threshold for activating the ON/OFF control module. The unit of the Setpoint field 

will be the same as the unit of the chosen Input. 

The 

Control Actions

 dropdown has options for direct or reverse control. In direct mode, once the Setpoint 

value is reached then the output will be set to ON. In reverse mode, once the Setpoint value is reached then 

the output will be set to OFF. 

The 

DeadBand

 field together with the direct or reverse control action configures a deadband range around 

the Setpoint where the ON/OFF control does not toggle. The unit of the DeadBand field will be the same as 

the unit of the chosen Input. 

Example 1:

 the setpoint is configured for a 50 Hz rate input with a deadband of 10 Hz with 

direct

control action. The output will activate if the input rises above 60 Hz. Conversely, the output will

become inactive if the input falls below 50 Hz.

Example 2:

 the setpoint is configured for a 50 Hz rate input with a deadband of 10 Hz with 

reverse

control action. The output will activate if the input falls below 40 Hz. Conversely, the output will

become inactive if the input rises above 50 Hz.

The 

Save 

button saves and applies the configurations settings to the ON/OFF control module. The 

Delete

 

button only appears for a previously saved ON/OFF control module and it removes the module and allows 

other output types to be configured such as an alarm or mapping. 

Figure 20: SYNC interface ON/OFF control module functions 

Summary of Contents for SP-006

Page 1: ...1 M 5 7 7 9 TM User sGuide Shop online at omega com e mail info omega com For latest product manuals www omegamanual info SP 006 Layer N Pressure Monitoring and Control Smart Probe...

Page 2: ...6 USA Canada only U S A Headquarters Tel 203 359 1660 e mail info omega com Fax 203 359 7700 The information contained in this document is believed to be correct but OMEGA accepts no liability for any...

Page 3: ...r Output Mapping 15 5 4 3 ON OFF Control Module 17 5 4 4 Setting an Alarm 18 6 Appendix SP 006 Registers 19 6 1 Register Base Addresses 19 6 2 Pressure Sensor 19 6 2 1 Pressure Descriptor 19 6 2 1 1 P...

Page 4: ...Configuration 26 6 4 2 DIO IPSO Definition 27 6 4 2 1 Sensor Trigger Function 27 6 5 Output Configuration Registers 27 6 5 1 Scaling Minimum Maximum Values 28 6 5 2 Output Values 28 6 5 3 Output Names...

Page 5: ...s device as it contains important information relating to safety and EMC Failure to follow all the safety precautions may result in injury and or damage to the equipment The following labels identify...

Page 6: ...autonomous independent decision making capabilities to generate local alarms or provide control outputs based on sensor inputs The optional M12 8 T SPLIT Sensor Splitter can be used to access the Dis...

Page 7: ...on 0 1 kPa Absolute Maximum Pressure 1 5 time full scale for each range Caution Do not exceed 500 psi TEMPERATURE Range 10 to 80 C 14 to 176 F Accuracy 1 5 C Resolution 0 1 C ENVIRONMENTAL Storage Tem...

Page 8: ...t i e ordering code C Inquire with Omega Engineering for other pressure port options Refer to Figure 3 4 Hardware Setup 4 1 Connecting your Layer N Smart Interface The SP 006 requires a Layer N Smart...

Page 9: ...End Device Probe 5 2 1 Communication Interface Set the communication parameters for the Layer N Smart Interface that you are connecting Note The connection type and parameters must be accurate for a...

Page 10: ...s for your device click Finish 5 3 Input Configuration The SP 006 provides readings for pressure temperature and discrete I O DIO To use these features click the Inputs configuration tab on SYNC and c...

Page 11: ...the user must follow the onscreen directions to calibrate the device Figure 8 SYNC pressure user calibration 5 3 2 Temperature The SP 006 Temperature readings may be configured under the advanced sca...

Page 12: ...ol signal to turn on the output driver which will force the output low When the state of the DIO input signal is to be read the processor applies 3 3 VDC to the Input Bias signal and reads the level d...

Page 13: ...must be selected to use the user defined Unit field Unchecking the Lock checkbox and clicking Apply Settings will revert the unit display back to the default setting 5 4 Output Configuration The SP 0...

Page 14: ...ses of a discrete signal PWM consists of a duty cycle and frequency The Duty Cycle measures the amount of time a signal is in the ON state as a percentage The frequency controls how fast the PWM cycle...

Page 15: ...varies between 0 5 and 2 5 msec Example For the percent of angular travel if the pulse width range is set to a range of 1 0 2 0 msec then an output of 50 of angular travel represents 1 5 msec or 90 d...

Page 16: ...output direct mapped to a Rate input The minimum expected input rate is 25 Hz and the maximum expected rate is 150 Hz A value of 50 Hz read at the input is then mapped to a PWM output with an 80 duty...

Page 17: ...the chosen Input The Control Actions dropdown has options for direct or reverse control In direct mode once the Setpoint value is reached then the output will be set to ON In reverse mode once the Se...

Page 18: ...transmit or not transmit a notification can be set The option to enable Turn On an output can also be set The output chosen must not be currently used in a sensor mapping or ON OFF control module The...

Page 19: ...responding sensor values Additional sensor information is provided in sensor specific IPSO object descriptions which include extended measurement type precision and tracking of minimum maximum reading...

Page 20: ...values may not be overwritten 6 2 1 3 Temperature Configuration Byte Pressure Sensor Configuration 7 6 5 4 3 2 1 0 Available Assigned Channel Apply Scaling Lock Sensor Range Type 0 0 Read Only Indica...

Page 21: ...Calibrate mode When the calibration function is triggered the device will calculate the Gain and Offset used in the linearization process The calibration process is performed by the following steps 1...

Page 22: ...s IPSO object type information Offset Name Value Description 0x00 Sensor Type 3323 Pressure kPa 0x02 Precision 1 Provides reading of xxx y kPa 0x04 Sensor Trigger Write any value to force a reset of m...

Page 23: ...he overall function of the channel and the signal types used Offset Name Value Description 0x00 Measurement Type 0x01 Temperature in C 0x01 Data Type Format 0x06 Float type 0x02 Configuration Byte See...

Page 24: ...e Smart Sensor Device Interface documentation for further information 6 3 1 4 Temperature Device Byte The Temperature Device Byte is not used 6 3 2 Temperature Parameters There are no user accessible...

Page 25: ...used to detect the state of external switches output off or to monitor the state of the outputs 6 4 1 DIO Descriptor Offset Name Value Description 0x00 Sensor Type 0x18 Digital Type Bit mapped 0x01 Da...

Page 26: ...will be used to adjust the sensor reading Result Raw Reading Gain Offset 6 4 1 3 3 Assigned The Assigned bit will always read as 0 Refer to the Smart Sensor Device Interface documentation for further...

Page 27: ...er Function 7 6 5 4 3 2 1 0 0 0 0 0 0 0 0 Reset Min Max 15 14 13 12 11 10 9 8 0 0 0 0 0 0 0 0 Setting the Reset Min Max bit to 1 will reset the Min Max values recorded by the IPSO process No User Cali...

Page 28: ...e output is mapped the scaling values are used to transform the minimum input value to 0 and the maximum input value to 100 Output Name Modbus Address I2C Address Size Description 0 Output 0 Value 0xf...

Page 29: ...sor 2 1 1 0 Sensor 3 1 1 1 Mapping Enable Not Enabled 0 Enabled 1 Output Type Null 0 0 0 0 ON OFF 0 0 0 1 PWM 0 0 1 0 Servo 0 0 1 1 6 6 1 Rate The Rate determines the repetition rate or frequency of t...

Page 30: ...y Mapping Enabled bit indicates that the output may be optionally directly mapped to a sensor input based on the Sensor Mapping field If the Mapping Enabled bit is clear no mapping is supported and th...

Page 31: ...A if the unit is found to be defective it will be repaired or replaced at no charge OMEGA s WARRANTY does not apply to defects resulting from any action of the purchaser including but not limited to m...

Page 32: ...s M U Turbine Paddlewheel Systems M U Totalizers Batch Controllers pH CONDUCTIVITY M U pH Electrodes Testers Accessories M U Benchtop Laboratory Meters M U Controllers Calibrators Simulators Pumps M U...

Reviews: