background image

User’s Guide

omega.com

e-mail: [email protected]

For Latest Product Manuals

omegamanual.info

®

®

Shop on line at

EIS-2B and EIS-W

Serial to Ethernet and Internet

Summary of Contents for iServer MicroServer EIS-2B

Page 1: ...User sGuide omega com e mail info omega com For Latest Product Manuals omegamanual info Shop on line at EIS 2B and EIS W Serial to Ethernet and Internet...

Page 2: ...is document is believed to be correct but OMEGA Engineering Inc accepts no liability for any errors it contains and reserves the right to alter specifications without notice WARNING These products are...

Page 3: ...ation Interfaces 12 2 5 1 10Base T RJ 45 Pinout 12 2 5 2 10Base T Crossover Wiring 12 Part 3 Network Configuration 13 3 1 Network Protocols 13 3 2 Ethernet MAC Address 13 3 3 DHCP 14 3 4 DNS 14 3 5 IP...

Page 4: ...t 6 Factory Preset Values 51 Appendix A Glossary 52 Appendix B IP Address 53 Appendix C IP Netmask 54 Appendix D ASCII Chart 56 ASCII Chart Control Codes 56 Appendix E iLog Error Messages 57 Part 7 Ap...

Page 5: ...21 Figure 4 9 Error Message 22 Figure 4 10 Read Devices 22 Figure 4 11 Device Query 22 Figure 4 12 Configuration 23 Figure 4 13 Access Control 26 Figure 4 14 DIP Switch 1 28 Figure 4 15 Setting the IP...

Page 6: ...iv...

Page 7: ...NOTE Provides you with information that is important to successfully setup and use the iServer CAUTION or WARNING Tells you about the risk of electrical shock CAUTION WARNING or IMPORTANT Tells you of...

Page 8: ...he container and equipment for signs of damage as soon as you receive the shipment Note any evidence of rough handling in transit Immediately report any damage to the shipping agent The carrier will n...

Page 9: ...TTPget DOS program or Telnet Simulation for network connectivity Install via RS232 RS485 serial port connection Transfer data from RS232 RS485 serial interface to TCP IP using built in socket server U...

Page 10: ...t is recommended that you ground your unit With one end of a wire connected to earth ground the other side can be wraped around the ground screw located on the bottom of the case If unit is to be moun...

Page 11: ...b Push unit towards DIN Rail and it will snap into place Figure 2 2 Mounting DIN Rail iServer 2 1 2 1 Removal from a DIN Rail a Insert flat screw driver into tab and push downwards b Unit will detach...

Page 12: ...iServer fully boots up Set the DIP switch 2 back to OFF position it does not matter if the iServer is powered ON or OFF just make sure that the DIP switch is set to OFF otherwise every time the unit i...

Page 13: ...cates network activities receiving or sending packets NET LINK LED Green Solid Indicates good network link TX LED Yellow Blinking Indicates transmitting data to the serial port RX LED Green Blinking I...

Page 14: ...lti dropped to be connected to the iServer using a two wire connection half duplex Rx Tx and Rx Tx Use of RS485 communications allows up to 31 devices to connect to the iServer with cable length up to...

Page 15: ...inal Block connector Table 2 4 9 Wall Mount iServer DB9 Pin Signal Direction 1 DCD IN 2 Rx IN 3 Tx OUT 4 DTR OUT 5 GND 6 DSR IN 7 RTS OUT 8 CTS IN 9 N C N C These 4 pins can also be used as digital in...

Page 16: ...Duplex RS485 Wiring Wall Mount iServer Value of the termination resistor is not critical and depends on the cable impedance Table 2 5 shows RS485 half duplex hookup between the iServer serial port and...

Page 17: ...il iServer Value of the termination resistor is not critical and depends on the cable impedance Table 2 6 shows RS485 half duplex hookup between the iServer serial port and device with RS485 communica...

Page 18: ...2 5 2 10Base T Crossover Wiring When connecting the iServer directly to the computer the transmit data pins of the computer should be wired to the receive data pins of the iServer and vice versa The...

Page 19: ...physical MAC address The MAC address can be found on the label of your device and contains 6 bytes 12 characters of hexadecimal numbers XX XX XX XX XX XX hex For example 0A 0C 3D 0B 0A 0B Remove the s...

Page 20: ...P address you would use only http eis03ec or any eight character name stored as Host Name under Access Control page in the iServer Home Page The default DNS name for an iServer is eis followed by the...

Page 21: ...ough the TCP IP protocol There are three default TCP port socket numbers assigned to the iServer 1 Port socket number 1000 when using HTTPget program see Section 4 8 2 Port socket number 2000 when try...

Page 22: ...r network cable between your PC s network port and the iServer After you re done with configuring the iServer you can always set your PC back to its original settings On your computer from the MS DOS...

Page 23: ...rtment for obtaining an IP address Figure 4 2 Assigning an IP Address using iConnect 1 Place the IP address in this box 2 Take the MAC address from the label attached to the bottom of the iServer and...

Page 24: ...tion Click on the View Webpage button you will access the iServer s home page refer to Section 4 3 for details Figure 4 3 Accessing the iServer s Home Page Menu iSERVER HOME PAGE Read Devices Device S...

Page 25: ...rst default LOGIN password is 12345678 and the ADMINISTRATOR password is 00000000 then you should be on the Access Control page were you can simply type in the desired Static IP address and click Save...

Page 26: ...STRATOR Password administrator allows certain groups and individual users to access and modify entire iServer parameters without any restrictions The default password is 00000000 This password can be...

Page 27: ...l command is typed The iServer will send this command to the serial device as soon as the Take Reading button is clicked Figure 4 8 Device Parameters DEVICE PARAMETERS DEVICE PARAMETERS http 192 168 1...

Page 28: ...to Save the page and click Device Query option again The Device Query option allows you to send a command to a single serial device connected to the iServer and displays the response back from that s...

Page 29: ...rity Options are Odd Even and None default is None Stop Bits Options are 1 and 2 bits default is 1 bit Flow Control Options are Software Flow Control Xon Xoff Hardware Flow Control CTS RTS and None de...

Page 30: ...o the Ethernet For example if the Timeout is set to 200 ms the iServer will send out the buffered serial data to the LAN if it does not receive any more data on its serial port for a period of 200 ms...

Page 31: ...ay not allow you to specify the iServer s port number it only allows you to enter the iServer s IP address In these cases you should put 23 in the Local Port field of the iServer By doing this the iSe...

Page 32: ...n administrator Password This allows users to access and modify the Access Control page The default password is 00000000 This password can be up to 16 alpha numeric case sensitive characters If there...

Page 33: ...ta that arrives at the gateway If the iServer is sending packets to another network node that is not on the same network on which the iServer is connected a gateway address needs to be given to the iS...

Page 34: ...hange the DIP switch 1 back to the OFF position and reset the power on the iServer Figure 4 15 Setting the IP address via the Serial Port You can access the iServer s complete settings by connecting t...

Page 35: ...ure 4 16 Pinging 192 168 1 70 from the MS DOS Prompt This proves that the connection is proper and you can access the iServer using the Telnet or Web browser C ping 192 168 1 70 Pinging 192 168 1 70 w...

Page 36: ...to any number from 599 to 9999 except numbers 1000 and 2002 4 Press the Save button to store the new settings From your application software on the host machine you can now point to the IP address of...

Page 37: ...aracters will be transmitted out from the serial port of the iServer If you want to send the whole command as a word simple paste the word in the same area This is an excellent tool to retrieve data f...

Page 38: ...n 2002 for logging into the iServer Configuration page or 2000 for accessing the serial device connected to the iServer s serial port Figure 4 19 Tera Term Telnet Connection Screen Figure 4 20 Telnet...

Page 39: ...iguration Command cc description pppppp BD BaudRate 0 300 1 600 2 1200 3 2400 4 4800 5 9600 6 19200 7 38400 8 57600 9 115200 PT Parity 0 none 1 Odd 2 even ST StopBits 0 1bits 1 2bits DT DataBits 0 7bi...

Page 40: ...The Port 1000 access can be used with our software and may be needed with some iServer products when you need to view readings from the web page while simultaneously collecting data through TCPIP com...

Page 41: ...command string 01 is device address in hex format for RS485 communication interface skip for RS232 X01 read measurement data value iSeries protocol r is the carriage return termination character 192 1...

Page 42: ...otocol ARP is the Internet layer protocol responsible for matching or obtaining the MAC hardware address that corresponds to a particular IP address The ARP command allows the user to view the current...

Page 43: ...Reply from 192 168 1 96 bytes 32 time 5ms TTL 32 Reply from 192 168 1 96 bytes 32 time 3ms TTL 32 Reply from 192 168 1 96 bytes 32 time 3ms TTL 32 Reply from 192 168 1 96 bytes 32 time 4ms TTL 32 C ar...

Page 44: ...l lab equipments electronic signboards and many others that are directly connected to PCs via their serial ports These devices can be attached to shared Ethernet networks TCP IP protocol and get acces...

Page 45: ...x to 00 and the Timeout to 0 7 Under Terminal Server section set Number of Connections to 1 or higher 8 Click on Save button for the changes to take place Make sure that the serial cable and communica...

Page 46: ...g connection between the two iServers goes down due to network problems power failure etc the Reconnect option will enable the Local iServer to reconnect with the Remote iServer based on the specified...

Page 47: ...and or the serial settings Baud rate stop bit parity etc throughout the communication path between the PC the iServer and the serial device 4 11 iPORT COM Port Redirector To obtain the iPORT software...

Page 48: ...his should be the same COM port that your application software uses The selected COM port will then appear on the main iPORT window By highlighting the selected COM port you will be able to add the IP...

Page 49: ...43 4 11 2 iPORT Configurations continued Figure 4 29 iPORT Main Window Figure 4 30 COM Port Window 2000 192 168 1 200 5000...

Page 50: ...0 to 10 seconds Status This window shows the connection status as the iPORT makes connection to the iServer or disconnects from the iServer The connection status can be ideal connecting connected or d...

Page 51: ...4 0 2000 and XP in conjunction with existing email that supports the MAPI messaging interface If MS Outlook has been loaded the MAPI support should be available 4 12 1 Installation The Mail Notifier...

Page 52: ...02 to 2005 The Mail Notifier will attempt to automatically identify whether the Outlook is a newer version A red bar appears under the Mail Notifier splash window to confirm that the detection of the...

Page 53: ...value or Low value Specifying Pause Interval It determines how many seconds each subsequential alarm notification will be sent Determining Monitor Interval It establishes the interval or time resoluti...

Page 54: ...data from our instruments over the local network Ethernet or the internet a Download the iLog software from the website listed in this manual b Install iLog software on a networked PC This software i...

Page 55: ...reen Processor CPU Enhanced 8051 22 MHz Processor Memory 512 Kbyte Flash 16 Kbyte SRAM Embedded Web Server Serves dynamic Web pages and Java applets 256 Kbyte capacity Management Device configuration...

Page 56: ...N C 4 53 115 0 99 25 1 3 54 90 2 Material Polycarbonate case with DIN rail mount Weight 113 g 0 25 lbs 2 60 66 0 1 08 27 4 3 67 93 1 0 25 6 4 0 25 6 4 1 78 45 2 2 42 61 6 3 56 90 3 0 14 3 6 0 30 7 7 3...

Page 57: ...Login Password 12345678 Admin Password 00000000 DHCP Disabled Serial Interface Communication Protocol RS232 Flow Control None Baud Rate 9600 Parity None Stop Bit 1 bit Data Bit 8 bits Timeout 0 msec...

Page 58: ...ernet IP address Internet Protocol address is a 32 bit number that identifies each sender or receiver of information that is sent in packets across the Internet IP Netmask is a 32 bit pattern of bits...

Page 59: ...pport approximately 216 65 536 computers per network The IP addresses range in binary from 10000000 00000000 xxxxxxxx xxxxxxxx to 10111111 11111111 xxxxxxxx xxxxxxxx The IP addresses range in decimal...

Page 60: ...Mask Dotted Notation Mask Binary Mask Bits Class A 255 0 0 0 Default 0 255 192 0 0 2 255 224 0 0 3 255 240 0 0 4 255 248 0 0 5 255 252 0 0 6 255 254 0 0 7 255 255 0 0 8 255 255 128 0 9 255 255 192 0...

Page 61: ...01010010 DC3 19 13 00010011 S 83 53 01010011 DC4 20 14 00010100 T 84 54 01010100 NAK 21 15 00010101 U 85 55 01010101 SYN 22 16 00010110 V 86 56 01010110 ETB 23 17 00010111 W 87 57 01010111 CAN 24 18...

Page 62: ...11 Crtl Q Data Control 1 XON SOH 01 01 Crtl A Start of DC2 18 12 Crtl R Data Control 2 Header STX 02 02 Crtl B Start of Text DC3 19 13 Crtl S Data Control 3 XOFF ETX 03 03 Crtl C End of Text DC4 20 1...

Page 63: ...007 Windows socket error Wrong IP or wrong Port number was used 10008 The iSeries failed to respond to a request Wrong IP or wrong Port number was used 10011 Response came empty No data was sent 10012...

Page 64: ...for CE with Double Insulation rating The ac dc power adapter is 9Vdc The minimum output current rating is 500mA EMC EN61000 6 1 2001 Immunity and EN61000 6 3 2001 Emissions Immunity requirements for r...

Page 65: ...NOTES...

Page 66: ...NOTES...

Page 67: ...ONS Equipment sold by OMEGA is not intended to be used nor shall it be used 1 as a Basic Component under 10 CFR 21 NRC used in or with any nuclear installation or activity or 2 in medical applications...

Page 68: ...city Indicators Turbine Paddlewheel Systems Totalizers Batch Controllers pH CONDUCTIVITY pH Electrodes Testers Accessories Benchtop Laboratory Meters Controllers Calibrators Simulators Pumps Industria...

Reviews: