17 |
P a g e
7.3.8
Serial Configuration Word
All serial line configuration is done thru the serial channel using Modbus or CLI commands and the
configuration information is retained in non-volatile memory. When altering the communications
parameters any changes occur after the acknowledgement of the Modbus command.
The device serial configuration word is located at Modbus register address 0xeff4.
Serial Configuration
7
6
5
4
3
2
1
0
Reserved
Data Width
Stop Bits
Parity
Baud Rate
0 7 Stop Bits
1 8 Data Bits
0 1 Stop
1 2 Stop
0 No Parity
1 Mark Parity
2 Odd Parity
3 Even Parity
0 9600
1 19,200
2 38,400
3 115,200
15 14 13
12
11
10
9
8
Reserved
7.3.9
Multi-Device Support
The IF-006 does not support multiple Smart Probes. The Modbus Range value is forced to 0.
7.3.10
Interface Control
The Interface Control register determines the characteristics of the IF-006 radio interface.
Note:
The Interface Control register is directly mapped to the Extension Space control register on the IF-006. Access
may be made thru either the IF-006 Interface Control register (0xeffe) or the IF-006 Extension space register
(0xf700).
Interface Control Register
7
6
5
4
3
2
1
0
Radio Type
< see below >
15
14
13
12
11
10
9
8
Radio Options
< see below >
7.3.10.1
Radio Type
The radio type field provides support for Sub GHz radio technology.
Radio Type
None
0
0
0
Omega Sub Ghz
0
0
1
Reserved
.
.
.