6.3
Characteristics
Table 6-3 Characteristics
BSR-2104/MAR BSR-2114/MAR
2-4 loop, 96 zone addressable fire detection panel.
Power supply
220-240V AC/50-60Hz
Fuse rating
2A-250VAC (slow blow) 5x20mm
Consumption
100 VA
Battery type
2x Sunlight SP-12 12V (7Ah or 12Ah) Lead Acid
Maximum current
consumption from battery
2.4A
Maximum Battery resistance
1ohm
Charge circuit
Stabilized power supply 27.6V / 600mA
Loop circuit
24V up to 200mA(quiescent state). Each loop can accept up to 150 points. Each loop is
protected with a self-resetable fuse.
The maximum number of fire detectors and manual call points connected to a panel
must not exceed 512.
Loop protocol
The communication protocol of the panel to the sensors (devices) is an Olympia Bus
protocol. The only devices connected to the loop must be manufactured by Olympia
Electronics SA.
Siren circuit
4 circuits 24V/500mA, monitored for open and short circuits.
Each output is protected with a self-resetable fuse.
Output Vout
24VDC (+- 4VDC+-ripple 1V peak to peak) continuous output with max current 0,5Α. Each
output is protected with a self-resetable fuse.
Relay4, Relay5, Relay6
General purpose relay (250VAC 5A).
Relay1, Relay2, Relay3
Monitored relay output for open or short circuits. Each output is protected with a self-
resetable fuse.
Output Fault
Open collector output (max 30VDC/6mA)
Output Alarm
Open collector output (max 30VDC/6mA)
Outputs A1,A2 and Α3
3 general purpose inputs (max. input voltage 30VDC)
Total loads (Imax)
The total load on the ( loops, sirens, outputs VOUT, relay) must not exceed 2Α.
Imax.a=Imax.b= 2A.
Safe State
The safe state for the main cpu of BSR-2100 is :
The leds remain at the state that they were before the safe state. Except System
fault which is on, and General Fault which light continuously or blink.
The relay outputs also remain at the state that they were. Except Fault relay
output which is de-energized.
There is no communication with the loops.
Buzzer sounds.
The safe state for the loop cpu of BSR-2100 is :
Shuts down the power of the loop.
Shuts down the power of the alarm devices (Sirens)
There is no communication with the main mcu.
Fault relay output is de-energized.
General Fault which light continuously or blink
Buzzer sounds
Connection cables
The connection cables must be certified for fire detection installations such as FIP200,
MICC, PYROFIL.
The connection cables that are used for data transfer must be of the twisted pair type and
must have insulation.
Cover protection
IP 30
Operating temperature
-5 to 40
o
C
Humidity
Up to 95% relative humidity