To change the relay press button “3” or “4”. To change the status press button “ENTER”.
With lamp test you can test all the LEDs and LCD backlight for correct operation.
Useful notes to setup the panel BS-316
For the correct mounting and setup of the panel BS-316, the user must do some basic steps:
1) First of all, the technician has to design the schematic which includes the way of installation of the panel
and the devices, the length of the cable and the point where the device is connected. This diagram will be
useful for the fault detection (short-circuits, alarms and faults).
2) The user disables all the system.
3) Next the user configures the sensors and the inputs.
4) When finished the user enables the inputs that are required.
5) The panel must be isolated from the main power supply when we install the sensors. After all connections
are finished, the power to the panel is restored.
6) Leave the panel working for about 20 minutes without cutting off the power supply. Check the current of
every sensor. The current must not be over 4mA. If it isn’t, wait about 1 hour and then re-check. If the
current of the sensor is not about 4mA, then perhaps the sensor needs setup.
7) If there is one short circuit in the power supply of a sensor (ter,-) for a moment, the panel shows a
fault. To clear the fault first we have to correct the short circuit and then to reset the panel via the keyboard.
In case there is a fault you must check point to point, which is out of communication.
Technical Characteristics
BS-316
Gas detection control panel up to 16 inputs
Power Supply
220-240V AC / 50-60Hz
Consumption
60VA
Battery type
12V / 7Ah Pb or 2X12V/7Ah
Charge Circuit
Power supply 13.8V / 500mA
Outputs
17 programmable relays (5Α/230VAC), Standard output 20V/300mA
Wrap protection class
IP 30
Operating temperature range
5 to 40
o
C
Humidity
Up to 95% humidity
Dimensions
445 x 345 x 95 mm
Weight
6160 gr
Produced by
ΕΝ 50270:2006, ΕΝ 60335-1:2012 +A11:2014 +AC:2014, EN 50194-1:2009
Warranty
2 years