background image

 

24

 

 

 

 

 

5.

 

Thread control, signal, and power wires into the transmitter housing. 

6.

 

Shielding  from  either  the  controller  or  remote  sensors  should  be 
bonded to the enclosure screw located inside the 

.   

 

IMPORTANT:

 Use of this product in areas where it may be subject to large 

amounts of electromagnetic interference may affect the reliable operation of 
this device and should be avoided. 

 

WARNING:

  Supply  wire  with  a  minimum  rating  of  90°C  must  be  used  for 

interconnection to the 

 

NOTE:

 For classified locations, a “poured” wire seal must be installed within 

18  inches  (457mm)  of  the  main  unit  for  both  power  entry  and  remote 
sensors. 

 

NOTE:

  Remove  power  from  the 

  before  making  any  wiring 

connections. 

Alarm Relay Wiring (J1, J5, and J6) 

To connect the 

 control wires to the three relay terminals on the relay 

board,  wire  the  unit  to  the  connectors  shown  in  Figure  2-4.  The  low  alarm 
relay  is  activated  when  the  low  alarm  threshold  is  met.  This  is  a  non-
latching,  Normally  Open  (NO)  contact.  The  high  alarm  relay  is  activated 
when the high alarm threshold is met. This is a non-latching, Normally Open 
(NO)  contact.  The  fault  alarm  relay  is  activated  upon  power-up  of  the 

.  When  the  fault  condition  is  met,  the  circuit  opens.  This  is  an 

Electronically closed (NC) contact. See Figure 4-1 for relay wiring. 

 

NOTE:

 It is recommended that on-board relays should not be used to drive 

loads directly. On-board relays should be used to drive a secondary, higher-
power  relay  which  is  connected  to  the  control  device  (e.g.,  strobe,  siren, 
exhaust fan, etc.). 

Summary of Contents for iTrans 2

Page 1: ...FIXED POINT SINGLE OR DUAL GAS MONITOR WITH DUAL ANALOG OUTPUTS Installation Operation Wiring Troubleshooting Part Number 77036429 EN Version 01 Release Date June 29 2013...

Page 2: ...other trademarks and registered trademarks are the property of their respective owners Although every effort is made to ensure accuracy the specifications of this product and the content herein are s...

Page 3: ...or which they are designated It should be noted however that the LEL sensors WILL respond to other combustible gases and are not gas specific Silicone compound vapors may affect the catalytic combusti...

Page 4: ...sure change is greater than 10 from the original pressure Do not expose the sensor to corrosive gases such as Hydrogen Sulphide Do not allow condensation to occur inside the sensor CALIBRATION ALERT G...

Page 5: ...a wide variety of gases including toxic and combustible gases as well as oxygen From research and development through final manufacturing we never forget that human lives depend on what we do Workers...

Page 6: ...6...

Page 7: ...siderations 21 Wall Mounting 21 Column Mounting 21 Chapter 4 System Wiring 23 Introduction 23 Wiring Preparation 23 Alarm Relay Wiring J1 J5 and J6 24 Power and Output Wiring J1 25 Sensor Wiring J3 26...

Page 8: ...lt Codes 64 Function Codes 64 Chapter 9 Warranty 67 Warranty 67 Limitation of Liability 67 Appendix A HART Interface 69 Introduction 69 Hardware Overview 70 Installation 71 System Wiring 71 Operation...

Page 9: ...9...

Page 10: ...10...

Page 11: ...control systems The is available with an optional relay board allowing the unit to directly control external devices such as fans pumps alarm horns or warning lights Two of the relays can be programm...

Page 12: ...ngle gas HART Combined Catalytic Infrared 350 mA 24 VDC 1 2 A peak two gas 400 mA 24 VDC 1 2 A peak two gas HART Display Dual channel split screen LED display 4 digit 7 segment arrangement per channel...

Page 13: ...gen Dioxide NO2 0 2 99 9 ppm in 0 1 ppm increments Nitric Oxide NO 0 999 ppm in 1 ppm increments Chlorine Cl2 0 2 99 9 ppm in 0 1 ppm increments Chlorine Dioxide ClO2 0 02 1 00 ppm in 0 01 ppm increme...

Page 14: ...ous Location Electrical Equipment ISA S12 13 Part I 2000 Performance Requirements Combustible Gas Detectors iTrans 2 with catalytic sensors only CSA Std C22 2 No 30 M1986 Explosion Proof Enclosures fo...

Page 15: ...erview Main Electronics Unit Housing The body is a cast aluminum housing that contains the electronics of the gas monitor Details of a single gas housing are shown in Figure 2 1 Figure 2 1 Details of...

Page 16: ...n For Combustibles For test gas concentrations up to and including 50 of full scale the deviation shall not exceed 3 of full scale gas concentration For test gas concentrations above 50 of full scale...

Page 17: ...keys are the mode increment decrement and enter keys Refer to Figure 2 3 For applications that require non intrusive manipulation two magnetically activated reed switches are used to accomplish progr...

Page 18: ...tors and jumpers for wiring and configuring the device The electronics module for a main unit is shown in Figure 2 4 The electronics module for a remote unit is shown in Figure 2 5 Wiring details are...

Page 19: ...19 Figure 2 5 Electronics Board for Remote Sensor...

Page 20: ...20...

Page 21: ...nstallation height depends on the density of the gas being monitored Moreover speed and direction of air flow and relative position to potential leaking points should also be considered IMPORTANT The...

Page 22: ...22 Figure 3 1 Mounting the Gas Monitor on a Wall Figure 3 2 Mounting the Gas Monitor on a Column Using U Bolts...

Page 23: ...AC power should not be run in the same conduit NOTE All field wiring colors are arbitrary unless provided by ISC Wiring Preparation 1 Collect the appropriate types and lengths of wire For control wir...

Page 24: ...making any wiring connections Alarm Relay Wiring J1 J5 and J6 To connect the control wires to the three relay terminals on the relay board wire the unit to the connectors shown in Figure 2 4 The low...

Page 25: ...upply power CH 1 Channel 1 4 20 mA output signal CH 2 Channel 2 4 20 mA output signal GND DC return Figure 4 2 Power and Signal Connector J1 on the NOTE Use supplied green conductor for enclosure grou...

Page 26: ...ows 24 V Red wire from sensor head 485A Yellow wire from sensor head 485B Black wire from sensor head GND Green wire from sensor head NOTE Shielding from either the controller or remote sensors should...

Page 27: ...on J3 should be connected to B in the remote sensor enclosure and 485 A on J3 should be connected to A in the remote sensor enclosure NOTE For remote or standalone sensors there are four terminal blo...

Page 28: ...28 Figure 4 4 Wiring Diagram for a Single On board Sensor...

Page 29: ...4 5 Wiring Diagram for a Remote Sensor Stand Alone NOTE When the remote sensor is at distances of 200 meters or further and the sensor is not communicating the jumper J1 may need to be moved to termin...

Page 30: ...f the jumper J1 is on terminals 1 2 move the jumper to terminals 2 3 For digital ModBus signal and power use a minimum of 4 conductors 18 AWG 0 9 mm insulated and shielded cable Shielding from either...

Page 31: ...31 Figure 4 7 Wiring Remote Sensors Back to...

Page 32: ...Remote Sensors Digital ModBus RTU Interface Wiring J1 ModBus Interface Wiring Overview To interface the to a digital controller PLC or HMI connect the power and ground to the appropriate terminals me...

Page 33: ...onics module is an 8 position DIP switch This switch bank is used to set the ModBus Slave Address for the unit The address can be set from 1 to 255 Use the DIP switches to set the binary representatio...

Page 34: ...r heads used in a ModBus network the address is set in the same manner Once the aluminum sensor head is removed with the sensor board the sensor electronics module is exposed On the back of the sensor...

Page 35: ...35 Figure 4 12 Location of Address DIP Switch on Sensor Electronics Module Figure 4 13 Setting the ModBus Address for a Stand Alone Sensor...

Page 36: ...us interface Note that DIP switches are pre set at the factory for all dual sensor units Wiring Conclusion Once wiring is complete place the electronics module back in the housing by pressing the stan...

Page 37: ...ing Mode If during the warm up period the unit fails a self test the display will show a fault code and the fault relay will be activated Fault codes are located in Chapter 8 Figure 5 1 Sample Fault C...

Page 38: ...mal Operating Mode the can enter into the program mode in one of two ways Figure 5 3 Sample Low and High Alarm Displays To enter the Program Mode without opening the enclosure pass over the embedded r...

Page 39: ...sing the magnetic wand Refer to the sections and subsections within this chapter for detailed information When in the Programming Mode either via the magnetic wand or keypad operation the top line of...

Page 40: ...gnetic wand over the embedded reed switches located under the CH1 and CH2 designations see Figure 5 4 of the faceplate will allow you to scroll through menus and enter the desired function The functio...

Page 41: ...row of the LED display During this 10 second time out if the magnetic wand is placed over CH2 that function is entered Once a function is entered a new timer will appear Zeroing Zeroing is the first...

Page 42: ...process Please make sure that you apply Zero Air to the instrument while it is zeroing The will automatically zero before calibration Zeroing is designated with a flashing 0 in the status bit Once zer...

Page 43: ...he Normal Operating Mode If you initiate the change span option the status bit will start to flash and the span value can now be changed Figure 5 11 Sample Span Gas Concentration Display The current s...

Page 44: ...gramming options include all of the functions available in the non intrusive mode as well as a few others These items are password protected To enter the programming options press the Mode key The acc...

Page 45: ...e button to confirm the channel selection Once a channel is selected the gas type for that sensor is displayed on the top row of the LED display for 5 7 second After that the LED display will show the...

Page 46: ...ew value If the value is not saved before the time out the will go back to the Programming Mode Set High Alarm The high alarm setpoint is designated with an H displayed in the status bit and the curre...

Page 47: ...start to flash and the range setpoint can be changed by using the and keys When the desired value is reached press the key If the value is not saved before the time out the will go back to the Program...

Page 48: ...f the month setting is designated with a d in the status bit and current value next to it To change the day press the button during the 10 second countdown If you do not press during the 10 second cou...

Page 49: ...eroing during the 10 second countdown the will return to the Normal Operating Mode If you initiate zeroing the status bit will start to flash Once zeroing is complete the unit will return to the Norma...

Page 50: ...responds to the gas the current reading will be displayed on the top line of the LED display To abort calibration at any time press the Mode key NOTE Check and verify span setting before starting a c...

Page 51: ...is not pressed the new span value will not be saved NOTE Span Gas Concentration for combustibles can be set from 0 to 100 LEL For the sake of resolution we suggest that Span Gas Concentration should...

Page 52: ...52...

Page 53: ...ce the correct access code has been entered then the user can select to enable 1 or disable 0 the MX43 compatibility mode on using Up or Down key then the selection is confirmed by pressing the Enter...

Page 54: ...e accessible on the refer to the next section ModBus Register List ModBus register addresses are provided in Table 6 1 Addr Inst R W Host R W Range Description 40101 R W R W MSB 01 to FF LSB 01 to F7...

Page 55: ...instrument The least significant byte LSB holds a code which identifies the gas type This can be read by the host MSB Decimal place holder 01 to FF LSB Gas type code 01 to FF 01 CO Carbon Monoxide 02...

Page 56: ...r in zero fault 0008 Sensor zeroing 0006 40106 W R 0000 to FFFF Status Bits Holds 16 bits of status for various parameters in the instrument A bit value of 1 indicates that the associated fault condit...

Page 57: ...SB 01 to 0C LSB 01 to 1F RTC Month and Day Holds the month and day to which the real time clock RTC calendar should be set The most significant byte MSB represents the month from 01 to 0C 1 12 The lea...

Page 58: ...he low alarm display will activate 40125 R R W 0000 to FFFF High Alarm Display Setting Holds the value of the gas reading at which the high alarm display will activate 40126 R R W 0000 to 03E8 Cal Gas...

Page 59: ...odBus further The most complete resource is www modbus org Termination When putting devices on the ModBus network a terminating resistor may be required for the last device on the network please see w...

Page 60: ...60...

Page 61: ...tional tests every 6 months Further Industrial Scientific Oldham recommends prudent testing and or calibration after a gas alarm All calibration service to the sensors should be recorded and accessibl...

Page 62: ...the alignment pin After the new sensor is in place screw the sensor cap back on to the housing and secure the set screw Once the new sensor is in place and has time to settle out it should be zeroed...

Page 63: ...SPAN Sensor has failed Electronics module has failed Replace sensor and calibrate Replace electronics module and calibrate Reading drifts by 10 counts over a short time period in a stable temperature...

Page 64: ...er after calibrating or replacing the sensor 1 FFF Flashing 1 mA SMART sensor error 2 FFF Flashing 1 mA Sensor error U Or Flashing 1mA Sensor under range U Or Flashing 22mA for 5 seconds then settled...

Page 65: ...centration R r Sensor Span Reserve Check the span reserve 2 2 Date The latest alarm time date 3 3 Month The latest alarm time month 6 6 Date The latest calibration time date 7 7 Month The latest calib...

Page 66: ...66...

Page 67: ...mitation of Liability Industrial Scientific Oldham makes no other warranties either expressed or implied including but not limited to the warranties of merchantability or fitness for particular purpos...

Page 68: ...ith their use capabilities and limitations as set forth in the applicable product literature Buyer acknowledges that it alone has determined the intended purpose and suitability of the goods purchased...

Page 69: ...rom anywhere in the 4 20mA loop as long as the handheld device is on the modem side of the 250 ohm load parameterization can also be accomplished through HART interface Figure A 1 HART Board channel 2...

Page 70: ...he electronics module of the gas monitor contains connectors and jumpers for wiring and configuring the device The electronics module for a main unit is shown in the figure The electronics module for...

Page 71: ...most applications the power is supplied from the controller that is receiving the 4 20mA output In these applications only three wires are required in case of single sensor unit and only four wires a...

Page 72: ...72 Figure A 4 Wiring Diagram of Single Sensor HART Supported...

Page 73: ...73 Figure A 5 Wiring Diagram of Dual Sensor HART Supported...

Page 74: ...ough terminating resistor installed from the factory but others may need additional resistance to be added This is accomplished by adding a resistor in series with the output from HART board preferabl...

Page 75: ...unit NOTE When not using isolated 4 20mA or HART 4 20mA outputs use the supplied resistors to connect CH 1 and CH 2 to GND If these resistors are not connected and the 4 20mA outputs are not used a P...

Page 76: ...m up mode which lasts for three minutes During the warm up mode all gas reading related alarms are disabled the current on the HART 4 20mA channel remains fixed at 3mA 16mA for oxygen sensor and the H...

Page 77: ...corresponding fault mode Figure A 11 Calibration Display HART interface is enabled throughout the zeroing and calibration modes Fault Mode The enters the fault mode whenever it is not able to provide...

Page 78: ...f the 4 20mA channels is not being used it should be terminated by inserting the specifically provided 250 ohms for HART CH 1 and 100 ohms for isolated CH 2 resistor between the respective channel out...

Page 79: ...for which is easiest and the quickest way to access all the process variables of The EDD can be either loaded on a PC host simulator or on a handheld unit Figure A 14 shows the EDD loaded using a PC...

Page 80: ...80 Figure A 15 EDD GUI View Figure A 16 PC to HART Interface Wiring Diagram...

Page 81: ...ber Parsing Parameter 0 1 Unsigned 16 iTrans HART Board Firmware Version 2 3 Unsigned 16 iTrans Main Unit Firmware Version 4 5 Unsigned 16 Sensor 1 Firmware Version 6 7 Unsigned 16 Sensor 2 Firmware V...

Page 82: ...alog Output Range Channel 1 12 15 Float IEEE 754 Cal Gas Value Channel 1 16 17 Unsigned 16 Calibration Interval In Days Channel 1 18 21 Float IEEE 754 Low Alarm Threshold Channel 2 22 25 Float IEEE 75...

Page 83: ...1 ASCII Sensor ID Number Channel 1 7 16 Latin 1 ASCII Sensor Part Number Channel 1 17 32 Latin 1 ASCII Sensor Serial Number Channel 1 33 Unsigned 8 Sensor Type Code Channel 2 34 Unsigned 8 Gas Type C...

Page 84: ...ds are dispatched with specific number of data bytes which are written to specified parameters after parsing process In case of a single sensor the parameters of disconnected sensor are also included...

Page 85: ...l 2 30 33 Float IEEE 754 Cal Gas Value Channel 2 34 35 Unsigned 16 Calibration Interval In Days Channel 2 Table A 4 Write Commands Operation Commands Operation commands are similar to write commands w...

Page 86: ...86...

Page 87: ...adiene styrene ASCII American Standard Code for Information Interchange bit binary digit bps bits per second C centigrade C2H4 ethylene C2H6O ethanol C3H6 propylene C3H8 propane C4H10 butane C5H12 pen...

Page 88: ...ydrogen chloride HCN hydrogen cyanide ISC Industrial Scientific Corporation LED light emitting diode LEL lower explosive limit combustible gases LSB least significant bit mA milliampere mm millimeter...

Page 89: ...programmable logic controller ppm parts per million REST restart RH relative humidity RTC real time clock RTU remote terminal unit SO2 sulfur dioxide SPST single pole single throw TOX toxic V Volts T...

Page 90: ...90...

Page 91: ...0x27 039 0x47 071 0x67 103 0x87 135 0xA7 167 0xC7 199 0xE7 231 0x08 008 0x28 040 0x48 072 0x68 104 0x88 136 0xA8 168 0xC8 200 0xE8 232 0x09 009 0x29 041 0x49 073 0x69 105 0x89 137 0xA9 169 0xC9 201 0...

Page 92: ...ary Dec Binary Dec Binary Dec Binary 0 00000000 64 01000000 128 10000000 192 11000000 1 00000001 65 01000001 129 10000001 193 11000001 2 00000010 66 01000010 130 10000010 194 11000010 3 00000011 67 01...

Page 93: ...000 96 01100000 160 10100000 224 11100000 33 00100001 97 01100001 161 10100001 225 11100001 34 00100010 98 01100010 162 10100010 226 11100010 35 00100011 99 01100011 163 10100011 227 11100011 36 00100...

Page 94: ...55 00110111 119 01110111 183 10110111 247 11110111 56 00111000 120 01111000 184 10111000 248 11111000 57 00111001 121 01111001 185 10111001 249 11111001 58 00111010 122 01111010 186 10111010 250 1111...

Page 95: ...tion B Gas sensor 1 F Gas sensor 2 C 4 20 mA output scale for sensor 1 G 4 20 mA output scale for sensor 2 D Optional on board relays A Sensor 1 E Sensor 2 0 No sensor 1 Explosion Proof On board 1 Exp...

Page 96: ...n Null CO H2 F Hydrogen Chloride HCl F Hydrogen Chloride HCl K Phosphine PH3 K Phosphine PH3 L Hydrogen H2 L Hydrogen H2 M Methane IR CH4 by Vol M Methane IR CH4 by Vol N Methane IR CH4 by LEL N Metha...

Page 97: ...0 6 0 2 6 0 2 7 0 1 7 0 1 8 0 20 8 0 20 9 0 200 9 0 200 A 0 5 00 A 0 5 00 B 0 0 50 B 0 0 50 D Optional On Board Relays 0 No Relay Module Modbus 1 With Optional On Board Relays Modbus 2 No Relay Module...

Page 98: ...98...

Page 99: ...pm 10 0 ppm PH3 0 1 00 ppm 0 01 ppm 1 0 ppm 0 30 ppm 0 60 ppm CO H2 NULL 0 999 ppm 1 ppm 100 ppm 35 ppm 70 ppm NO 0 999 ppm 1 ppm 25 ppm 25 ppm 50 ppm NH3 0 200 ppm 1 ppm 25 ppm 25 ppm 50 ppm HCl 0 30...

Page 100: ...100...

Page 101: ...in Figure F 1 the cross sensitivity of the methane IR sensor does not permit accurate measure of other combustible gases It should be noted however that the methane IR sensor WILL respond to other co...

Page 102: ...IR Sensor The output of the IR sensor can be disrupted by sudden changes in temperature If there is an excessive change in the ambient temperature gas sample temperature or flow rate then the output...

Page 103: ...1 80 0 90 JP 4 3 00 1 50 JP 5 3 10 1 55 JP 8 3 20 1 60 Methane 1 00 Methanol 1 35 0 65 n Pentane 2 00 1 00 Propane 1 60 0 80 Styrene 2 40 1 20 Toluene 2 50 1 25 Xylene 2 40 1 20 Example The instrument...

Page 104: ...104...

Page 105: ...105...

Page 106: ...hamgas com AMERICAS Tel 1 412 788 4353 Fax 1 412 788 8353 info indsci com ASIA PACIFIC Tel 86 21 5899 3279 Fax 86 21 5899 3280 sales isc cn com EUROPE Tel 33 321 608 080 Fax 33 321 608 000 info oldham...

Reviews: