3
40180036GB
CAUTION!
The burner must be installed firmly. Vibrations may damage burner or its
components.
CAUTION!
Prior to trial start the gas piping must be vented. See chapter ”Example of
an Installation of Gas Supply Line”.
DANGER!
In case of gas leakage:
-
do not
make fire,
do not
touch the electrical equipment
- close the main fuel shut-off valve outside the plant
- make sure, that there is no people in the leakage area
- air the leakage area
- take appropriate actions.
In case of fire or other danger:
- switch off the main switch
- close the main fuel shut-off valve outside the plant
- take appropriate actions.
DANGER!
Never use a naked flame while checking the burner or the boiler. Never
store any inflammable material in the boiler room.
DANGER!
Keep the boiler door closed while starting the burner and during burner
operation.
DANGER!
Wear hearing protectors, if there is noise in the boiler room.
Correct installation and adjustment together with regular servicing are the most reliable
guarantees of trouble-free burner operation.
Note!
Local regulations and requirements must be adhered to when installing or servicing
the gas burner or the gas supply line.
The burner has to be installed in such a way that the motor shaft lies horizontally; however, it is
not allowed to install the burner upside down.
Use only original spare parts. When ordering spare parts please give the burner type and serial
number indicated on the burner nameplate.