6.7. Pressure
Switches
6.7.1. Gas Pressure Switch
1 Adjusting scale
2 Pressure measuring
connection
3 Cover
Adjust the gas pressure switch (min) on a 20 - 40 % lower pressure than the gas inlet pressure
to burner during burner operation at full load. If the gas pressure switch occurs during burner
start-up a temporarily burner shutdown, it has to be set on a lower pressure. For adjustment
open the protective cover of the gas pressure switch and turn the adjustment knob on the scale.
Replace the protective cover.