27
40180036GB
8.4. Detector Currents and Connection of Flame Detector FE (Ionization Electrode)
Electrode voltage
operation 330 V
±
10 %
test 380 V
±
10 %
Short-circuit current
max. 0,5 mA
Min. required detector current
6
m
A
Max. possible detector current during operation
150
m
A
Length of detector line
- in the same cable as control lines
not allowed
- separate cable in cable duct
80 m
- shielded cable (insulated shielding)
140 m
shielding to terminal
22
8.5. Technical
Data
Mains
220 VAC -15 %...240 VAC +10 %
Mains frequency
50 - 60 Hz,
±
6 %
Power consumption
3,0 VA
Unit fuse, built-in
T6,3 A / 250 V slow-acting DIN 41571
Unit fuse, external
max. 10 A
Radio interference protection
N according to VDE 0875
Permissible input current at terminal 1
5 A, continuously; peaks of up 20 A
Permissible loading of control terminals
4 A continuously; peaks of up 20 A; total max. 5 A
Required switching capacity
-
between terminals 4 and 5
1 A 250 VAC
-
between terminals 4 and 12
1 A 250 VAC
-
between terminals 4 and 14
load on terminals
16, 17, 18, 19 min. 1 A 250 V AC
Degree of protection
IP40
Permissible ambient temperature
-20...+60
°
C