Basic settings of a control module are carried out with DIP switches (LCM) and other
settings with a PC application (LSB-remote).
The DIP switches are placed on the cover of the module. In the following tables, the
factory settings are underlined:
DIP-1
0 = no CAN terminator
1 = CAN terminator active
DIP-5–6, product family
DIP-5
DIP-6
Product family
0
0
1
0
1
2
1
0
3
1
1
4
DIP-2–4, choosing temperature sensor
DIP-2
DIP-3
DIP-4
Sensor
0
X
X
PT100, boiler water temperature
1
X
X
PT1000, boiler water temperature
X
0
X
PT100, outside temperature
X
1
X
PT1000, outside temperature
X
X
0
PT100, flue gas temperature
X
X
1
PT1000, flue gas temperature
4.22 Setting load controller parameters
In the following table, the marking (w) stands for water and (s) for steam.
Param. no.
Description
Factory setting
0040
BT300
Type of output regulator. 0-OFF / 1-constant regulator / 2-
weather-controlled regulator
1
0048
BT300
Controller set value 1 minimum
0
0049
BT300
Controller set value 1 maximum
110 (w) / 10 (s)
0054
BT300
Burner start point
2 (w) / 0.5 (s)
0055
BT300
Upper control range
5 (w) / 1 (s)
0056
BT300
Burner off
7 (w) / 1.5 (s)
0057
BT300
P-term of the controller
120 (w) / 600 (s)
0058
BT300
I-term of the controller
60 (w) / 300 (s)
0059
BT300
D-term of the controller
20 (w) / 25 (s)
0060
BT300
Reset time
15 (w) / 20 (s)
0061
BT300
Representation of actual value and setpoint for load
regulator
1 (w) / 2 (s)
0062
BT300
4 mA corresponds to x units
0
0063
BT300
20 mA corresponds to x units
Pressure transmitter
max.
M5164 1640EN
57 (95)