D044670 ver. 1
1
A100 Control panel
2
Control switch S1/H1
3
Fuel selector switch S2 (GKP)
Control switch S1
Switch position
State
0 - STOP
Control voltage is cut off from burner automation and burner is shut down.
1 - CONTROL
Control voltage is switched on to burner automation (burner control,
servomotors). Burner control is ready for control and monitoring functions, but
burner start-up by control device is prevented.
2 /
- AUTOMATIC
Burner starts as the start signal is received from control device. Burner
control start-up program begins. Burner operates controlled by the capacity
controller or on a manually preset load. Burner control supervises burner
operation and results in a controlled shutdown or if necessary, safety
shutdown and lockout. During burner operation the green LED illuminates the
switch.
Fuel selector switch S2 (in dual-fuel GKP burner)
Switch position
State
1 - OIL
Burner control chosen to oil use.
0
No fuel chosen.
2 - GAS
Burner control chosen to gas use.
66 (95)
M5164 1640EN