INSTALLATION | Preparing to install the appliance
14
www.ochsner.com | 982000-AIR-M2-M4-EN03.1
11_05_200_504_002
Material damage
The air flow through the evaporator must not be
obstructed by surrounding buildings. A reduced air
flow rate can lead to loss of efficiency in the system.
Please note the following with regard to installation in
coastal areas:
►
The standard design of outdoor unit must be installed
at least 1 km from the sea.
►
Outdoor units with special coating, suitable for coast-
al locations, must be installed at least 200 m from the
sea.
►
The installation location selected should always be on
the leeward side of the building (the side facing away
from the sea).
Please note the following with regard to sound emissions
from the outdoor unit:
►
Avoid installing on reverberant flooring.
►
Avoid installing between building walls. The walls can
increase the noise level.
►
Avoid installing next to bedrooms.
i
Information
Plants and cultivated areas around the outdoor
unit, subject to minimum clearances, can reduce
the noise level of the outdoor unit.
9.2.1 Keep minimum clearances
Observing the specified minimum clearances for the out
-
door unit ensures:
►
Correct installation of the appliance
►
Fault-free operation
►
Ability to carry out maintenance on the appliance.
It is permissible to install the outdoor unit under a roof if the
space around the unit is permanently open on three sides.
11_05_200_504_001
A
B
C
A
≥ 3000 mm (minimum clearance to roof)
B
≥ 1000 mm (minimum clearance to a wall)
C
100 mm or ≥ 1000 mm (minimum longitudinal clear
-
ance to a wall)
i
Information
The minimum clearance between two outdoor
units (e.g. connected in cascade) is 1000 mm on
all sides.
9.3 Foundations for the outdoor unit
A permanent foundation is required beneath the outdoor
unit. The foundations must meet the structural require-
ments of the outdoor unit (see Specification).
»
Provide for frost-free drainage (e.g. a gravel bed con-
nected to a drain) for condensation that forms on the
outdoor unit.
»
Where refrigerant lines are to be laid in the ground,
ensure correct positioning of the pipe liner when lay-
ing the foundations.
»
Use underground waste pipes (with a smooth inner
surface) for the pipe liner.